Datasheet excerpt: Technical data of  HiC2853R1

General specifications
Signal typeDigital Input
Functional safety related parameters
Safety Integrity Level (SIL)SIL 3
Supply
ConnectionSL1: 1a(-), 1b(-); 2a(+), 2b(+)
Rated voltage19 ... 30 V DC bus powered via Termination Board
Ripple≤ 10 %
Rated current≤ 55 mA
Power dissipation≤ 800 mW
Power consumption≤ 1300 mW
Input
Connection sidefield side
ConnectionSL2: 5a(+), 5b(-)
Open circuit voltage/short-circuit currentapprox. 8.4 V DC / approx. 11.7 mA
Lead resistancemax. 50 Ω , consider capacitances and inductances
Switching point1-signal: I > 2.8 mA
0-signal: I < 2.1 mA
Response delay≤ 1 ms
Output
Connection sidecontrol side
ConnectionSL1: 8a(+), 7a(-); 10a(+), 9a(-)
Rated voltageoutput I: 19 ... 30 V DC with external resistance > 2 kΩ, e. g. 16-channel ProSafe DI card SDV144 from Yokogawa
Output Ipassive transistor output (resistive)
0-signal: 39 kΩ ± 5 %
1-signal: voltage drop 6.5 V ± 0.5 V
fault: > 100 kΩ
Output IIactive voltage output, short-circuit proof
0-signal: 0 V
1-signal: 20 ... 31 V DC at max. 15 mA
fault: 0 V
Fault indication output
ConnectionSL1: 6b
Output typeopen collector transistor (internal fault bus)
Transfer characteristics
Switching frequency
Output I≤ 50 Hz
Output II≤ 50 Hz
Galvanic isolation
Output/power supplyfunctional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Output/Outputfunctional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Indicators/settings
Display elementsLEDs
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2006
For further information see system description.
Degree of protectionIEC 60529:2001
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Massapprox. 180 g
Dimensions12.5 x 128 x 106 mm (0.5 x 5.1 x 4.2 inch)
Mountingon Termination Board
Codingpin 1 and 2 trimmed
For further information see system description.
Data for application in connection with hazardous areas
EU-Type Examination CertificateBASEEFA 07 ATEX 0302X
MarkingEx-Hexagon II (1)G [Ex ia] IIC , Ex-Hexagon II (1) D [Ex ia] IIIC , Ex-Hexagon I (M1) [Ex ia] I
InputEx ia
Voltage10.5 V
Current17.1 mA
Power45 mW (linear characteristic)
Supply
Maximum safe voltage253 V AC (Attention! Um is no rated voltage.)
Output
Maximum safe voltage253 V AC (Attention! Um is no rated voltage.)
CertificatePF 09 CERT 1440 X
MarkingEx-Hexagon II 3G Ex nA IIC T4 Gc
Galvanic isolation
Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Input/power supplysafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
UL approval
Control drawing116-0364
IECEx approvalIECEx BAS 07.0097X
Approved for[Ex ia Ga] IIC, [Ex ia] I , [Ex ia] IIIC
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Documents: HiC2853R1

ManualsLanguageFile TypeFile Size
Manual H-System Isolated Barriers and Termination BoardsENGPDF5551 KB
Safety ManualENGPDF186 KB
Handbuch Trennbarrieren und Termination Boards H-SystemGERPDF5543 KB
Instruction manuals
ИнструкцииBULPDF63 KB
Návod k poużitíCZEPDF59 KB
Instruktions manualDANPDF57 KB
Instruction manualENGPDF49 KB
KasutusjuhendESTPDF54 KB
KäyttöohjeFINPDF55 KB
Manuel d'instructionsFRAPDF69 KB
BetriebsanleitungGERPDF51 KB
Οδηγίες χρήσηςGREPDF67 KB
HandleidingHOLPDF68 KB
Instruction manual / BetriebsanleitungHRVPDF67 KB
Használati útmutatóHUNPDF68 KB
Manuale di istruzioniITAPDF67 KB
Lietošanas pamācībaLAVPDF67 KB
Instrukciju vadovasLITPDF66 KB
Instrukcja obsługiPOLPDF70 KB
Manual de instruçõesPORPDF69 KB
Manual de utilizareRONPDF68 KB
Návod na poużitieSLKPDF128 KB
Manual de instruccionesSPAPDF68 KB
ManualSWEPDF65 KB

Approvals+Certificates: HiC2853R1

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of conformity / EU-KonformitätserklärungDOC-0034CPDF148 KB
Certificates
Baseefa IECEx Certificate of ConformityIECEx BAS 07.0097XLINK---
Canada UL cULE106378 cUL (QUZW8)LINK---
DNV GL MarineTAA00002EDPDF72 KB
EAC EAC TP TC 020/2011TC RU C-DE.MH04.B.00397PDF680 KB
Europe Baseefa ATEX Category (M1) ATEX Category (1) GDBaseefa 07 ATEX 0302XPDF1615 KB
Europe Pepperl+Fuchs ATEX Category 3 G CertificatePF 09 CERT 1440 XPDF208 KB
Russia Belarus Kazakhstan EAC EAC TP TC 012/2011EAEC RU C-DE.EX01.B.00102/19PDF9815 KB
USA Canada UL Hazardous Location Certificate of Compliance cULus UL E106378CoC 20130429 - E106378 RepRef 20130429PDF425 KB
USA ULE106378 UL (QUZW2)LINK---
Control drawings
Control Drawing UL / Control Drawing UL   PDF154 KB

Function: HiC2853R1

This isolated barrier is used for intrinsic safety applications.

The device transfers digital signals (SN/S1N proximity sensors or approved dry contacts) from a hazardous area to a safe area.

The input controls one 24 V DC active voltage output and one passive transistor output with a resistive output characteristic.

The outputs have three defined states: 1-Signal = 6.5 V voltage drop, 0-Signal = 39 kΩ and fault > 100 kΩ.

Lead breakage (LB) and short circuit (SC) conditions of the control circuit are continuously monitored.

Unlike a SN/S1N series safety sensor, an approved dry contact requires a 10 kΩ resistor to be placed across the contact in addition to a 1.5 kΩ resistor in series.

This device mounts on a HiC Termination Board.