Serviceline Industrial Sensors
Serviceline Explosion Protection

Universal Power Rail UPR-03-S

UPR-03-S
  • 35 mm DIN mounting rail with 3-conductor insert
  • Provides DC supply voltage to all equipped K-System modules
  • Standard length 0.8 m (2.6 ft), simple to customize to application space
  • Eliminates daisy-chains

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH, also apply to Pepperl+Fuchs AG.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  UPR-03-S

Product Description
Universal Power Rail with end caps and cover, 3 conductors, length: 0.8 m
Electrical specifications
Rated voltage24 V DC
Rated current4 A
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Connection3 conductors
Supply2 Conductors
Fault output1 Conductors
Dimensions35 x 15 x 800 mm (1.4 x 0.6 x 31.5 inch)
General information
Scope of delivery- DIN mounting rail UPR-MR
- insert UPR-INS-03
- cover UPR-COVER
- end cap UPR-E
Accessories
Optional accessories- end cap UPR-E
- insulation spacer UPR-I
- DIN mounting rail UPR-MR
- insert UPR-INS-03
- cover UPR-COVER

Documents: UPR-03-S

ManualsLanguageFile TypeFile Size
Manual Isolated Barriers K-systemENGPDF760 KB
Manuel pour Barrières Isolées de Système KFRAPDF759 KB
Handbuch Trennbarrieren K-SystemGERPDF745 KB
Manual Isolated Barriers K-systemRUSPDF4107 KB

Approvals+Certificates: UPR-03-S

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of Conformity / EU-KonformitätserklärungDOC-4096PDF395 KB
Certificates
Canada UL cULE106378 cUL (QUZW7)LINK---
USA ULE106378 UL (QUZW)LINK---

Associated Products: UPR-03-S

Accessory of

1-channel isolated barrier, 24 V DC supply (Power Rail), Voltage input -10 V ... 10 V, Voltage output -10 V ... 10 V, Transfer direction: to the control systempa

1-channel isolated barrier, 24 V DC supply (Power Rail), Potentiometer input, Voltage output 0 V ... 10 V, Lead resistance compensation adjustment, Accuracy 0.05 %, Up to SIL 2 acc. to IEC 61508pa

1-channel isolated barrier, 24 V DC supply (Power Rail), Potentiometer input, Current output 0 mA ... 20 mA, Lead resistance compensation adjustment, Accuracy 0.05 %, Up to SIL 2 acc. to IEC 61508pa

1-channel isolated barrier, 24 V DC supply (Power Rail), Voltage input 0 V ... 12 V, Voltage output 0 V ... 12 V, Transfer direction: to the control systempa

1-channel isolated barrier, 24 V DC supply (Power Rail), Potentiometer input, Current output 4 mA ... 20 mA, Lead resistance compensation adjustment, Accuracy 0.05 %, Up to SIL 2 acc. to IEC 61508pa

1-channel isolated barrier, 24 V DC supply (Power Rail), Input for approved dry contacts or SN/S1N sensors, Relay contact output, Fault indication output, Line fault detection (LFD), Up to SIL 3 acc. to IEC 61508, Up to PL d acc. to EN/ISO 13849pa

1-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Usable as signal splitter (1 input and 2 outputs), Relay contact output, Fault relay contact output, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 acc. to IEC 61508/IEC 61511pa

1-channel isolated barrier, 24 V DC supply (Power Rail), Input for 2-wire SMART transmitters and current sources, Output for 4 mA ... 20 mA or 1 V ... 5 V, Sink or source mode, Housing width 12.5 mm, Up to SIL 2 acc. to IEC 61508pa

1-channel isolated barrier, 24 V DC supply (Power Rail), Voltage input 0 mV ... ± 50 mV, Voltage output 0 mV ... ± 50 mV, Selectable up/downscale sensor breakage detection, Transfer direction: to the control systempa

Interface for Power Rail, Supply current ≤ 4 A, Replaceable fuse, Relay contact output, reversible, LED status indicationpa

Interface for Power Rail, Used for redundant configuration, Supply current ≤ 4 A, Replaceable fuse, Relay contact output, reversible, LED status indicationpa

2-channel isolated barrier, 24 V DC supply (Power Rail), Output 45 mA at 11.7 V DC, Logic input, non-polarized, Line fault detection (LFD), Up to SIL 2 acc. to IEC 61508pa

2-channel isolated barrier, 24 V DC supply (Power Rail), Output 45 mA at 11.7 V DC, Logic input, non-polarized, Up to SIL 2 acc. to IEC 61508pa

4-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, 50 % less wiring, 2:1 technology, Relay contact output, Line fault detection (LFD), Reversible mode of operationpa

1-channel isolated barrier, 24 V DC supply (Power Rail), Output 20.4 mA at 13.5 V DC, 19 V DC ... 30 V DC input, Line fault detection (LFD), Conformal coating, Up to SIL 3 acc. to IEC 61508pa

1-channel isolated barrier, 24 V DC supply (Power Rail), Current output up to 700 Ω load, HART I/P and valve positioner, Line fault detection (LFD), Accuracy 0.1 %, Terminal blocks with test sockets, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the fieldpa

1-channel isolated barrier, 24 V DC supply (Power Rail), Voltage input 0 mV ... ± 500 mV, Voltage output 0 mV ... ± 500 mV, Selectable up/downscale sensor breakage detection, Transfer direction: to the control systempa

1-channel isolated barrier, 24 V DC supply (Power Rail), Thermocouple, RTD, potentiometer or voltage input, Redundant TC input, Current output 0/4 mA ... 20 mA, 2 relay contact outputs, Configurable by PACTware or keypad, Line fault (LFD) and sensor burnout detection, Up to SIL 2 acc. to IEC 61508/IEC 61511, Rated voltage: 20 ... 30 V DCpa

1-channel isolated barrier, 24 V DC supply (Power Rail), Current output up to 650 Ω load, HART I/P and valve positioner, Lead breakage monitoring, Accuracy 0.1 %, Housing width 12.5 mm, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the fieldpa

1-channel signal conditioner, 24 V DC supply (Power Rail), Current output up to 650 Ω load, HART I/P and valve positioner, Lead breakage monitoring, Accuracy 0.1 %, Housing width 12.5 mm, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the fieldpa

1-channel isolated barrier, 24 V DC supply (Power Rail), Thermocouple, RTD, potentiometer or voltage input, Voltage output 0/1 V ... 5 V, Configurable by PACTware, Line fault (LFD) and sensor burnout detection, Up to SIL 2 acc. to IEC 61508/IEC 61511pa

2-channel isolated barrier, 24 V DC supply (Power Rail), Thermocouple, RTD, potentiometer or voltage input, Usable as signal splitter (1 input and 2 outputs), Voltage output 0/1 V ... 5 V, Configurable by PACTware, Line fault (LFD) and sensor burnout detection, Up to SIL 2 acc. to IEC 61508/IEC 61511pa

1-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire transmitters and 2-wire current sources, Output 0/4 mA ... 20 mA, 2 relay contact outputs, Adjustable energized/de-energized delay, Programmable high/low alarm, Linearization function (max 20 points), Line fault detection (LFD), Up to SIL 2 acc. to IEC 61508/IEC 61511pa

1-channel signal conditioner, 24 V DC supply (Power Rail), Input 2-wire and 3-wire transmitters and 2-wire current sources, Output 0/4 mA ... 20 mA, 2 relay contact outputs, Adjustable energized/de-energized delay, Programmable high/low alarm, Linearization function (max 20 points), Line fault detection (LFD), Up to SIL 2 acc. to IEC 61508/IEC 61511pa

1-channel isolated barrier, 24 V DC supply (Power Rail), HART field device input with transmitter power supply, Usable as signal splitter (1 input and several outputs), 3 analog outputs 4 mA ... 20 mA, Sink and source mode output, Configurable by keypadpa

1-channel isolated barrier, 24 V DC supply (Power Rail), HART field device input with transmitter power supply, Usable as signal splitter (1 input and several outputs), 2 relay contact outputs (change-over contacts), 3 analog outputs 4 mA ... 20 mA, Sink and source mode output, Configurable by keypadpa

1-channel signal conditioner, 24 V DC supply (loop powered), Logic input 19 V DC ... 26.5 V DC, non-polarized, Relay contact output for energized to safe function , Test pulse immunity, Up to SIL 3 acc. to IEC 61508pa

1-channel signal conditioner, 24 V DC supply (loop powered), Logic input 19 V DC ... 26.5 V DC, non-polarized, Relay contact output for energized to safe function , Test pulse immunity, Up to SIL 3 acc. to IEC 61508pa

2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, 2 passive transistor outputs, Reversible mode of operation, Line fault detection (LFD), Up to SIL 2 acc. to IEC 61508pa

1-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, 2 active transistor outputs, Usable as signal splitter (1 input and 2 outputs), Reversible mode of operation, Line fault detection (LFD), Up to SIL 2 acc. to IEC 61508pa

1-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Passive transistor output, non-polarized, Passive fault output, non-polarized, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 acc. to IEC 61508pa

2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Active transistor output, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 acc. to IEC 61508pa

1-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Usable as signal splitter (1 input and 2 outputs), Isolated passive transistor output, non-polarized, Isolated passive fault output, non-polarized, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 acc. to IEC 61508pa

2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Isolated passive transistor output, non-polarized, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 acc. to IEC 61508pa

2-channel signal conditioner, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Usable as signal splitter (1 input and 2 outputs), 2 x 2 relay contact outputs with AND logic, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 acc. to IEC 61508/IEC 61511pa

1-channel isolated barrier, 24 V DC supply (Power Rail), Resistance and RTD input (Pt100, Pt500, Pt1000), Resistance output, Accuracy 0.1 %, Line fault detection (LFD) for Pt100, Housing width 12.5 mm, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the control systempa

1-channel signal conditioner, 24 V DC supply (Power Rail), Current and voltage input, 2 relay contact outputs, Programmable high/low alarm, Configurable via DIP switches and potentiometer, Terminal blocks with test socketspa

1-channel isolated barrier, 24 V DC supply (Power Rail), Current input 0 mA ... 20 mA, Current output 0 mA ... 20 mA, Accuracy 0.1 %, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the fieldpa

1-channel isolated barrier, 24 V DC supply (Power Rail), Voltage input 0 V ... -20 V, Vibration sensor inputs, Voltage/current field supply, Voltage output 0 V ... -20 V, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the control systempa

2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Usable as signal splitter (1 input and 2 outputs), 2 x 2 relay contact outputs with AND logic, Reversible mode of operation, Line fault detection (LFD), Up to SIL 2 acc. to IEC 61508pa

1-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Signal splitter (1 input and 2 outputs), Dual output 0/4 mA ... 20 mA, current sink/current source, Terminals with test points, Up to SIL 3 acc. to IEC 61508pa

1-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Signal splitter (1 input and 2 outputs), Dual output 0/4 mA ... 20 mA, current sink/current source, Terminals with test points, High field voltage 17 V DC, Up to SIL 3 acc. to IEC 61508pa

1-channel signal conditioner, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Signal splitter (1 input and 2 outputs), Dual output 0/4 mA ... 20 mA, current sink/current source, Terminals with test points, Up to SIL 3 acc. to IEC 61508pa

1-channel signal conditioner, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Output 0/4 mA ... 20 mA current sink/current source, Terminals with test points, Up to SIL 2 acc. to IEC 61508pa

2-channel signal conditioner, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Output 0/4 mA ... 20 mA current sink/current source, Terminals with test points, Up to SIL 2 acc. to IEC 61508pa

1-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Output 0/4 mA ... 20 mA current sink/current source, Terminals with test points, Up to SIL 2 acc. to IEC 61508pa

1-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Output 0/4 mA ... 20 mA current sink/current source, Terminals with test points, High field voltage 17 V DC, Up to SIL 2 acc. to IEC 61508pa

2-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Output 0/4 mA ... 20 mA current sink/current source, Terminals with test points, Up to SIL 2 acc. to IEC 61508pa

1-channel signal conditioner, 24 V DC supply (Power Rail), Input for 2- or 3-wire sensors, NAMUR sensors or dry contacts, Input frequency 1 mHz ... 10 kHz, Current output 0/4 mA ... 20 mA, Relay contact and transistor output, Start-up override, Line fault detection (LFD), Up to SIL 2 acc. to IEC 61508/IEC 61511pa
1-channel isolated barrier, 24 V DC supply (Power Rail), Input for approved dry contacts or SN/S1N sensors, Active voltage output, Relay contact output, Fault indication output, Line fault detection (LFD), Up to SIL 3 acc. to IEC 61508, Up to PL d acc. to EN/ISO 13849pa
1-channel isolated barrier, 24 V DC supply (Power Rail), Voltage input -10 V ... 10 V, Transmission frequency up to 50 kHz, Voltage output -10 V ... 10 V, Transfer direction: to the control systempa
2-channel isolated barrier, 24 V DC supply (Power Rail), Current output up to 700 Ω load, HART I/P and valve positioner, Line fault detection (LFD), Accuracy 0.05 %, Terminal blocks with test sockets, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the fieldpa
1-channel signal conditioner, 24 V DC supply (Power Rail), Current input 0 mA ... 20 mA, Current output 0 mA ... 20 mA, Accuracy 0.1 %, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the fieldpa
1-channel signal conditioner, 24 V DC supply (Power Rail), Current output up to 700 Ω load, HART I/P and valve positioner, Line fault detection (LFD), Accuracy 0.05 %, Terminal blocks with test sockets, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the fieldpa
2-channel signal conditioner, 24 V DC supply (Power Rail), Current output up to 700 Ω load, HART I/P and valve positioner, Line fault detection (LFD), Accuracy 0.05 %, Terminal blocks with test sockets, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the fieldpa
1-channel isolated barrier, 24 V DC supply (Power Rail), Current output up to 700 Ω load, HART I/P and valve positioner, Line fault detection (LFD), Accuracy 0.05 %, Terminal blocks with test sockets, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the fieldpa
1-channel isolated barrier, 24 V DC supply (Power Rail), RS 232 input/output, Transfer direction: to the control systempa
1-channel isolated barrier, 24 V DC supply (Power Rail), Current input 4 mA ... 20 mA, Current output 4 mA ... 20 mA, Current output up to 700 Ω load, I/P and valve positioners, Accuracy 0.05 %, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the fieldpa
2-channel isolated barrier, 24 V DC supply (Power Rail), Current input 0 mA ... 20 mA, Current output 0 mA ... 20 mA, Current output up to 700 Ω load, I/P and valve positioners, Accuracy 0.05 %, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the fieldpa
1-channel isolated barrier, 24 V DC supply (Power Rail), Voltage input 0 V ... 9 V, Voltage output 0 V ... 9 V, Transfer direction: to the control systempa
2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Isolated passive transistor output, TTL level, Line fault detection (LFD), Reversible mode of operationpa
1-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Active transistor output, Active fault output, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 acc. to IEC 61508pa
2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Active transistor output, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 acc. to IEC 61508pa
2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Passive transistor output, non-polarized, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 acc. to IEC 61508pa
1-channel, 24 V DC supply (Power Rail), Potentiometer input, Voltage output 0 V ... 10 V, Accuracy 0.05 %, Up to SIL 2 acc. to IEC 61508pa
1-channel isolated barrier, 24 V DC supply (Power Rail), Output 45 mA at 11.7 V DC, Logic input, non-polarized, Line fault detection (LFD), Up to SIL 2 acc. to IEC 61508pa
1-channel isolated barrier, 24 V DC supply (Power Rail), Output 45 mA at 11.7 V DC, Logic input, non-polarized, Up to SIL 2 acc. to IEC 61508pa
1-channel isolated barrier, 24 V DC supply (Power Rail), Output 45 mA at 11.2 V DC, Logic input, non-polarized, Fault indication output, Line fault detection (LFD), Up to SIL 2 acc. to IEC 61508pa
1-channel, 24 V DC supply (Power Rail), Potentiometer input, Current output 0 mA ... 24 mA, Accuracy 0.05 %, Up to SIL 2 acc. to IEC 61508pa
2-channel signal conditioner, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Usable as signal splitter (1 input and 2 outputs), 2 x 2 relay contact outputs with AND logic, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 acc. to IEC 61508/IEC 61511pa
1-channel isolated barrier, 24 V DC supply (Power Rail), Output 45 mA at 10 V DC, Logic input, non-polarized, Fault indication output, Line fault detection (LFD), Up to SIL 2 acc. to IEC 61508pa
1-channel isolated barrier, 24 V DC supply, Input for approved dry contacts or SN/S1N sensors, Active voltage output, Relay contact output, Fault indication output, Line fault detection (LFD), Up to SIL 3 acc. to IEC 61508, Up to PL d acc. to EN/ISO 13849pa
2-channel isolated barrier, 24 V DC supply (Power Rail), Current output up to 700 Ω load, HART I/P and valve positioner, Lead breakage monitoring, Accuracy 0.05 %, Terminal blocks with test sockets, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the fieldpa
1-channel isolated barrier, 24 V DC supply (Power Rail), Current output up to 700 Ω load, HART I/P and valve positioner, Lead breakage monitoring, Accuracy 0.05 %, Terminal blocks with test sockets, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the fieldpa
1-channel isolated barrier, 24 V DC supply (Power Rail), Input for 2-wire SMART transmitters and current sources, Output for 4 mA ... 20 mA or 1 V ... 5 V, Sink or source mode, Line fault detection (LFD), Housing width 12.5 mm, Up to SIL 3 acc. to IEC 61508pa
1-channel signal conditioner, 24 V DC supply (Power Rail), Current output up to 650 Ω load, HART I/P and valve positioner, Lead breakage monitoring, Accuracy 0.1 %, Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the fieldpa
1-channel signal conditioner, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Usable as signal splitter (1 input and 2 outputs), Relay contact output, Fault relay contact output, Line fault detection (LFD), Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 2 acc. to IEC 61508pa
2-channel signal conditioner, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Relay contact output, Line fault detection (LFD), Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 2 acc. to IEC 61508pa
1-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Usable as signal splitter (1 input and 2 outputs), Relay contact output, Fault relay contact output, Line fault detection (LFD), Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 2 acc. to IEC 61508pa
2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Relay contact output, Line fault detection (LFD), Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 2 acc. to IEC 61508pa
1-channel signal conditioner, 24 V DC supply (Power Rail), Input for 2-wire SMART transmitters and current sources, Output for 4 mA ... 20 mA or 1 V ... 5 V, Sink or source mode, Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 2 acc. to IEC 61508pa
1-channel isolated barrier, 24 V DC supply (Power Rail), Input for 2-wire SMART transmitters and current sources, Output for 4 mA ... 20 mA or 1 V ... 5 V, Sink or source mode, Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 2 acc. to IEC 61508pa
1-channel isolated barrier, 24 V DC supply (Power Rail), Input for 2-wire SMART transmitters and current sources, Output for 4 mA ... 20 mA or 1 V ... 5 V, Sink or source mode, Line fault detection (LFD), Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 3 acc. to IEC 61508pa
Interface for Power Rail, Supply current ≤ 4 A, Replaceable fuse, Relay contact output, reversible, LED status indication, Connection via spring terminals with push-in connection technologypa
Interface for Power Rail, Used for redundant configuration, Supply current ≤ 4 A, Replaceable fuse, Relay contact output, reversible, LED status indication, Connection via spring terminals with push-in connection technologypa
1-channel isolated barrier, 24 V DC supply (Power Rail), Increased input load, Output 45 mA at 11.2 V DC, Logic input, non-polarized, Fault indication output, Line fault detection (LFD), Up to SIL 2 acc. to IEC 61508pa
1-channel signal conditioner, 24 V DC supply (Power Rail), Thermocouple, RTD, potentiometer or voltage input, Voltage output 0/1 V ... 5 V, Configurable by PACTware, Line fault (LFD) and sensor burnout detection, Up to SIL 2 acc. to IEC 61508/IEC 61511pa
2-channel signal conditioner, 24 V DC supply (Power Rail), Thermocouple, RTD, potentiometer or voltage input, Usable as signal splitter (1 input and 2 outputs), Voltage output 0/1 V ... 5 V, Configurable by PACTware, Line fault (LFD) and sensor burnout detection, Up to SIL 2 acc. to IEC 61508/IEC 61511pa
2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, 2 active transistor outputs, Reversible mode of operation, Line fault detection (LFD), Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 2 acc. to IEC 61508pa
1-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR input, 2 active transistor outputs, Usable as signal splitter (1 input and 2 outputs), Reversible mode of operation, Line fault detection (LFD), Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 2 acc. to IEC 61508pa
2-channel signal conditioner, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, 2 active transistor outputs, Reversible mode of operation, Line fault detection (LFD), Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 2 acc. to IEC 61508pa
1-channel signal conditioner, 24 V DC supply (Power Rail), Dry contact or NAMUR input, 2 active transistor outputs, Usable as signal splitter (1 input and 2 outputs), Reversible mode of operation, Line fault detection (LFD), Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 2 acc. to IEC 61508pa
2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, 2 passive transistor outputs, Reversible mode of operation, Line fault detection (LFD), Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 2 acc. to IEC 61508pa
1-channel signal conditioner, 24 V DC supply (Power Rail), Dry contact or NAMUR input, 2 passive transistor outputs, Usable as signal splitter (1 input and 2 outputs), Reversible mode of operation, Line fault detection (LFD), Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 2 acc. to IEC 61508pa
1-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR input, 2 passive transistor outputs, Usable as signal splitter (1 input and 2 outputs), Reversible mode of operation, Line fault detection (LFD), Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 2 acc. to IEC 61508pa
2-channel signal conditioner, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, 2 passive transistor outputs, Reversible mode of operation, Line fault detection (LFD), Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 2 acc. to IEC 61508pa
2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, 2 passive transistor outputs (resistive acc. to EN 60947-5-6), Line fault transparency (LFT), Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 2 acc. to IEC 61508pa
1-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR input, 2 passive transistor outputs (resistive acc. to EN 60947-5-6), Line fault transparency (LFT), Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 2 acc. to IEC 61508pa
1-channel isolated barrier, 24 V DC supply (Power Rail), Resistance and RTD input (Pt100, Pt500, Pt1000), Resistance output, Accuracy 0.1 %, Housing width 12.5 mm, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the control systempa
1-channel isolated barrier, 24 V DC supply (Power Rail), Resistance and RTD input (Pt100, Pt500, Pt1000), Resistance output, Accuracy 0.1 %, Line fault detection (LFD) for Pt100, Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the control systempa
1-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Output 0/1 V ... 5 V, Terminals with test points, Up to SIL 2 acc. to IEC 61508pa
1-channel isolated barrier, 24 V DC supply (Power Rail), HART field device input with transmitter power supply, Usable as signal splitter (1 input and several outputs), 4 relay contact outputs (NO contact), 3 analog outputs 4 mA ... 20 mA, Sink and source mode output, Configurable by keypadpa
1-channel isolated barrier, 24 V DC supply (bus or loop powered), Output 45 mA at 10 V DC, Line fault transparency (LFT), Test pulse immunity, Housing width 12.5 mm, Up to SIL 3 acc. to IEC 61508pa
1-channel isolated barrier, 24 V DC supply (Power Rail), Input for 2-wire SMART transmitters and current sources, Signal splitter (1 input and 2 outputs), Dual output 0/4 mA ... 20 mA or 0/1 V ... 5 V, Terminal blocks with test sockets, Up to SIL 2 acc. to IEC 61508pa
1-channel isolated barrier, 24 V DC supply (Power Rail), Input for 2-wire SMART transmitters and current sources, Signal splitter (1 input and 2 outputs), Dual output 0/4 mA ... 20 mA or 0/1 V ... 5 V, Terminal blocks with test sockets, Up to SIL 2 acc. to IEC 61508pa
1-channel isolated barrier, 24 V DC supply (bus or loop powered), Output 65 mA at 10 V DC, Line fault transparency (LFT), Test pulse immunity, Housing width 12.5 mm, Up to SIL 3 acc. to IEC 61508pa
1-channel isolated barrier, 24 V DC supply (bus or loop powered), Output 45 mA at 12 V DC, Line fault transparency (LFT), Test pulse immunity, Housing width 12.5 mm, Up to SIL 3 acc. to IEC 61508pa
2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Isolated passive transistor output, TTL level, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 acc. to IEC 61508pa
1-channel isolated barrier, 24 V DC supply (Power Rail), Input for 2-wire SMART transmitters and current sources, Signal splitter (1 input and 2 outputs), Dual output 0/4 mA ... 20 mA or 0/1 V ... 5 V, Terminal blocks with test sockets, Up to SIL 3 acc. to IEC 61508pa
1-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Output 0/4 mA ... 20 mA, Terminals with test points, Up to SIL 2 acc. to IEC 61508pa
1-channel signal conditioner, 24 V DC supply, Logic input 19 V DC ... 26.4 V DC, Recommended connectable voltage 50 V AC ... 230 V AC, 60 V DC ... 110 V DC, Relay contact output for de-energized to safe function, Line fault transparency (LFT), Diagnostic function, Up to SIL 3 acc. to IEC 61508, Up to PL e acc. to EN/ISO 13849pa
1-channel signal conditioner, 24 V DC supply, Logic input 19 V DC ... 26.4 V DC, Recommended connectable voltage 8 V DC ... 60 V DC, Relay contact output for de-energized to safe function, Line fault transparency (LFT), Diagnostic function, Up to SIL 3 acc. to IEC 61508, Up to PL e acc. to EN/ISO 13849pa
1-channel signal conditioner, 24 V DC supply, Logic input 19 V DC ... 26.4 V DC, Recommended connectable voltage 8 V DC ... 60 V DC, Relay contact output for energized to safe function , Line fault transparency (LFT), Diagnostic function, Up to SIL 3 acc. to IEC 61508pa
1-channel signal conditioner, 24 V DC supply, Logic input 19 V DC ... 26.4 V DC, Recommended connectable voltage 50 V AC ... 230 V AC, 60 V DC ... 110 V DC, Relay contact output for energized to safe function , Line fault transparency (LFT), Diagnostic function, Up to SIL 3 acc. to IEC 61508pa
1-channel isolated barrier, 24 V DC supply (Power Rail), 2-wire SMART transmitter, Output 4 mA ... 20 mA, SMART capable up to 40 kHz (-1dB), Suitable for Honeywell DE protocol, Terminals with test pointspa
1-channel signal conditioner, 24 V DC supply (Power Rail), Input for 2-wire SMART transmitters and current sources, Signal splitter (1 input and 2 outputs), Dual output 0/4 mA ... 20 mA or 0/1 V ... 5 V, Terminal blocks with test sockets, Up to SIL 2 acc. to IEC 61508pa
1-channel isolated barrier, 24 V DC supply (Power Rail), Logic input, Output 100 mA at 13 V DC, Alternating outputs for the operation of solenoids with 2 coils, High output power for IIB gas group, Line fault transparency (LFT), Test pulse immunity, Up to SIL 3 acc. to IEC 61508pa
1-channel isolated barrier, 24 V DC supply (Power Rail), Current input 4 mA ... 20 mA, Current output 0 mA ... 20 mA, Accuracy 0.1 %, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the fieldpa
1-channel isolated barrier, 24 V DC supply (Power Rail), Current input 0 mA ... 20 mA, Current output 4 mA ... 20 mA, Accuracy 0.1 %, Transfer direction: to the fieldpa
1-channel isolated barrier, 24 V DC supply (Power Rail), Voltage input 0 V ... 5 V, Current output 0 mA ... 20 mA, Accuracy 0.1 %, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the fieldpa
1-channel isolated barrier, 24 V DC supply (Power Rail), Voltage input 0 V ... 5 V, Current output 4 mA ... 20 mA, Accuracy 0.1 %, Transfer direction: to the fieldpa
1-channel isolated barrier, 24 V DC supply (Power Rail), Voltage input 0 V ... 10 V, Current output 0 mA ... 20 mA, Accuracy 0.1 %, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the fieldpa
1-channel isolated barrier, 24 V DC supply (Power Rail), Voltage input 0 V ... 10 V, Current output 4 mA ... 20 mA, Accuracy 0.1 %, Transfer direction: to the fieldpa
1-channel isolated barrier, 24 V DC supply (Power Rail), Current input 0 mA ... 20 mA, Voltage output 1 V ... 5 V, Accuracy 0.1 %, Transfer direction: to the fieldpa
1-channel isolated barrier, 24 V DC supply (Power Rail), Current input 4 mA ... 20 mA, Voltage output 0 V ... 5 V, Accuracy 0.1 %, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the fieldpa
1-channel isolated barrier, 24 V DC supply (Power Rail), Current input 0 mA ... 20 mA, Voltage output 0 V ... 10 V, Accuracy 0.1 %, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the fieldpa
1-channel isolated barrier, 24 V DC supply (Power Rail), Current input 4 mA ... 20 mA, Voltage output 0 V ... 10 V, Accuracy 0.1 %, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the fieldpa
1-channel isolated barrier, 24 V DC supply (Power Rail), Voltage input 0 V ... 10 V, Voltage output 0 V ... 10 V, Accuracy 0.1 %, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the fieldpa
1-channel isolated barrier, 24 V DC supply (Power Rail), Voltage input 0 V ... 10 V, Voltage output 0 V ... 5 V, Accuracy 0.1 %, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the fieldpa
1-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR input, Application-specific outputs, Usable as signal splitter (1 input and 2 outputs), 2 passive transistor outputs (resistive), Line fault transparency (LFT), Housing width 12.5 mm, Up to SIL 2 acc. to IEC 61508pa
1-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR input, Application-specific outputs, Usable as signal splitter (1 input and 2 outputs), 2 passive transistor outputs (resistive), Line fault transparency (LFT), Housing width 12.5 mm, Up to SIL 2 acc. to IEC 61508pa
2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Application-specific outputs, 2 passive transistor outputs (resistive), Line fault transparency (LFT), Housing width 12.5 mm, Up to SIL 2 acc. to IEC 61508pa
2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Application-specific outputs, 2 passive transistor outputs (resistive), Line fault transparency (LFT), Housing width 12.5 mm, Up to SIL 2 acc. to IEC 61508pa
1-channel isolated barrier, 24 V DC supply (Power Rail), Input for 2-wire SMART transmitters, Output for 4 mA ... 20 mA or 1 V ... 5 V, Sink or source mode, Housing width 12.5 mm, Up to SIL 2 acc. to IEC 61508pa
1-channel isolated barrier, 24 V DC supply (bus or loop powered), Output 45 mA at 10 V DC, Line fault transparency (LFT), Test pulse immunity, Housing width 12.5 mm, Up to SIL 3 acc. to IEC 61508pa
1-channel isolated barrier, 24 V DC supply (bus or loop powered), Output 65 mA at 10 V DC, Line fault transparency (LFT), Test pulse immunity, Housing width 12.5 mm, Up to SIL 3 acc. to IEC 61508pa
1-channel isolated barrier, 24 V DC supply (bus or loop powered), Output 45 mA at 12 V DC, Line fault transparency (LFT), Test pulse immunity, Housing width 12.5 mm, Up to SIL 3 acc. to IEC 61508pa
1-channel isolated barrier, 24 V DC supply (Power Rail), Input for 2-wire SMART transmitters and current sources, Output for 4 mA ... 20 mA or 1 V ... 5 V, Sink or source mode, Line fault detection (LFD), Housing width 12.5 mm, Up to SIL 3 acc. to IEC 61508pa
1-channel isolated barrier, 24 V DC supply (Power Rail), Current output up to 650 Ω load, HART I/P and valve positioner, Lead breakage monitoring, Accuracy 0.1 %, Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the fieldpa

Function: UPR-03-S

The Power Rail consists of a DIN mounting rail UPR-MR and a insert UPR-INS-03.

The component has two conductors for power and one conductor for collective error messaging.

The component reduces wiring and maintenance costs because it eliminates the need to daisy-chain the wires. It also simplifies expansion – just snap in a new isolator when you’re ready to expand a system.

The component comes in 0.8 m segments but can be cut to any size.

The Power Rail is delivered with two UPR-E end caps and UPR-COVER cover. All components of the Power Rail can be ordered separately.

In conjunction with K-System modules the component can be mounted in Zone 2.