Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Download the complete datasheet as a PDF:
Product Description |
---|
NAMUR Resistor Network |
Supply | ||
---|---|---|
Rated voltage | max. 20 V DC | |
Electrical specifications | ||
Resistor | 1.5 kΩ/0.6 W 10 kΩ/0.6 W |
|
Input | ||
Suitable field devices | ||
Field device | volt-free contact | |
Error detection | lead breakage, short circuit, open switch, closed switch | |
Ambient conditions | ||
Ambient temperature | -40 ... 60 °C (-40 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Core cross section | max. 1.5 mm2 | |
Cable | 0.75 mm2 x 150 mm | |
Mass | approx. 20 g | |
Dimensions | ∅15.5 x 35 mm (0.61 x 1.38 inch) | |
Length | 150 mm | |
Diameter | 15.5 mm | |
Data for application in connection with hazardous areas | ||
Certificate | DOC-0053 , see instruction manuals | |
Temperature class | T5 | |
Voltage | 20 V | |
Power | 0.6 W | |
Ambient temperature | 60 °C (140 °F) | |
Internal capacitance | 0 F | |
Internal inductance | 0 H | |
General information | ||
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
System | Classcode |
---|---|
ECLASS 13.0 | 27260118 |
ECLASS 12.0 | 27024401 |
ECLASS 11.0 | 27024401 |
ECLASS 10.0.1 | 27024401 |
ECLASS 9.0 | 27024401 |
ECLASS 8.0 | 27024401 |
ECLASS 5.1 | 27279290 |
ETIM 9.0 | EC002303 |
ETIM 8.0 | EC002303 |
ETIM 7.0 | EC002303 |
ETIM 6.0 | EC002303 |
ETIM 5.0 | EC003015 |
UNSPSC 12.1 | 32121610 |
The NAMUR Resistor Network is used to monitor lead breakage and short circuit detection in switch amplifier circuits controlled by mechanical contacts.
The component is installed directly to the control contact or inside its terminal box.
The component can be used with all switch amplifiers featuring line fault detection.
Brief Instructions | Language | File Type | File Size |
---|---|---|---|
Instruction Manual F-NR*-Ex1 / Betriebsanleitung F-NR*-Ex1 | ALL | 69 KB |