Serviceline Industrial Sensors
Serviceline Explosion Protection

SMART Transmitter Power Supply KFD2-STC4-Ex2

KFD2-STC4-Ex2
  • 2-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • Input 2-wire SMART transmitters
  • Output 0/4 mA ... 20 mA
  • Terminals with test points
  • Up to SIL 2 acc. to IEC/EN 61508

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  KFD2-STC4-Ex2

General specifications
Signal typeAnalog input
Functional safety related parameters
Safety Integrity Level (SIL)SIL 2
Supply
ConnectionPower Rail or terminals 14+, 15-
Rated voltage20 ... 35 V DC
Ripplewithin the supply tolerance
Power dissipation1.8 W
Power consumptionmax. 2.7 W
Input
Connection sidefield side
Connectionterminals 1+, 3-; 4+, 6-
Input signal0/4 ... 20 mA
Available voltage≥ 16 V at 20 mA, terminals 1+, 3
Output
Connection sidecontrol side
Connectionterminals 7-, 8+; 10-, 11+
Load0 ... 550 Ω at 20 mA
Output signal0/4 ... 20 mA (overload > 25 mA)
Ripplemax. 50 µA rms
Transfer characteristics
Deviationat 20 °C (68 °F), 0/4 ... 20 mA
≤ 10 µA incl. calibration, linearity, hysteresis, loads and fluctuations of supply voltage
Influence of ambient temperature0.25 µA/K
Frequency rangefield side into the control side: band width with 1 Vpp signal 0 ... 7.5 kHz (-3 dB)
safe area to hazardous area: band width with 1 VSS signal 0.3 ... 7.5 kHz (-3 dB)
Settling time200 µs
Rise time/fall time20 µs
Galvanic isolation
Output/power supplyfunctional insulation, rated insulation voltage 50 V AC
Output/Outputfunctional insulation, rated insulation voltage 50 V AC
Indicators/settings
Display elementsLED
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2011
Degree of protectionIEC 60529:2001
Protection against electrical shockUL 61010-1:2012
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Massapprox. 150 g
Dimensions20 x 124 x 115 mm (0.8 x 4.9 x 4.5 inch) , (W x H x D) housing type B2
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificateBAS 99 ATEX 7025 X
MarkingEx-Hexagon II (1)G [Ex ia Ga] IIC , Ex-Hexagon II (1)D [Ex ia Da] IIIC , Ex-Hexagon I (M1) [Ex ia Ma] I
Input[Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
Voltage25.2 V
Current93 mA
Power0.586 W
Supply
Maximum safe voltage250 V (Attention! The rated voltage can be lower.)
CertificateTÜV 99 ATEX 1499 X
MarkingEx-Hexagon II 3G Ex nA II T4 [device in zone 2]
Galvanic isolation
Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Input/power supplysafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
UL approval
Control drawing116-0428 (cULus)
IECEx approval
IECEx certificateIECEx BAS 04.0015X
IECEx CML 15.0055X
IECEx marking[Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I
Ex nA IIC T4 Gc
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 11.027210119
ECLASS 10.0.127210119
ECLASS 9.027210119
ECLASS 8.027210119
ECLASS 5.127210119
ETIM 8.0EC001485
ETIM 7.0EC001485
ETIM 6.0EC001485
ETIM 5.0EC001485
UNSPSC 12.132101514

Documents: KFD2-STC4-Ex2

ManualsLanguageFile TypeFile Size
Functional Safety ManualENGPDF557 KB
System Manual ENGPDF3835 KB
SystemhandbuchGERPDF3846 KB
Instruction manuals
ИнструкцииBULPDF170 KB
Návod k poużitíCZEPDF164 KB
Instruktions manualDANPDF163 KB
Instruction manualENGPDF168 KB
KasutusjuhendESTPDF160 KB
KäyttöohjeFINPDF159 KB
Manuel d'instructionsFRAPDF166 KB
BetriebsanleitungGERPDF170 KB
Οδηγίες χρήσηςGREPDF173 KB
HandleidingHOLPDF165 KB
Instruction manual / BetriebsanleitungHRVPDF162 KB
Használati útmutatóHUNPDF166 KB
Manuale di istruzioniITAPDF164 KB
Lietošanas pamācībaLAVPDF163 KB
Instrukciju vadovasLITPDF164 KB
Instrukcja obsługiPOLPDF166 KB
Manual de instruçõesPORPDF165 KB
Manual de utilizareRONPDF164 KB
Návod na poużitieSLKPDF164 KB
Navodila za uporaboSLVPDF162 KB
Manual de instruccionesSPAPDF165 KB
ManualSWEPDF161 KB

CAD+CAE: KFD2-STC4-Ex2

CADFile TypeFile Size
3-D model / 3-D-ModellSTP3048 KB
EPLAN
EPLAN macro EDZ / EPLAN Makro EDZEDZ61 KB

Approvals+Certificates: KFD2-STC4-Ex2

CertificatesCertificate No.File TypeFile Size
Australia SIMTARSANZEx 10.2002XPDF359 KB
Baseefa IECEx Certificate of ConformityIECEx BAS 04.0015XLINK---
CML IECEx Certificate of Conformity Zone 2IECEx CML 15.0055XLINK---
Canada UL cULE106378 cUL (QUZW7)LINK---
China SITIIAS CCC Ex Certificate2021322316004096 (Singapore)PDF1027 KB
DNV GL MarineTAA00001WXPDF77 KB
Europe Baseefa ATEX Category (1) GDBAS 99 ATEX 7025XPDF3124 KB
Europe TUV Nord ATEX Category 3 GTÜV 99 ATEX 1499XPDF1999 KB
India PESO (India) CCOEA/P/HQ/MH/104/3770 (P345749)PDF551 KB
Japan TIISTC16175PDF3442 KB
Korea KOSHA12-AV4BO-0438PDF283 KB
USA Canada UL Hazardous Location Certificate of Compliance cULus UL E106378CoC 20161215 - E106378 RepRef 20161215PDF403 KB
USA ULE106378 UL (QUZW)LINK---
exida Functional Safety Assessment SummaryP+F 05/09-21 R024PDF349 KB
Control Drawings
Control Drawing UL / Control Drawing UL   PDF28 KB
Declaration of Conformity
EU-Declaration of conformity / EU-KonformitätserklärungDOC-0038FPDF83 KB

Associated Products: KFD2-STC4-Ex2

Matching System Components

35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 2 m (6 foot), simple to customize to application space, Eliminates daisy-chainspa

35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 0.8 m (2.6 ft), simple to customize to application space, Eliminates daisy-chainspa
35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 1.6 m (5 foot), simple to customize to application space, Eliminates daisy-chainspa
Accessories
3-pin screw terminal, For KF modules of K-System, Integrated test sockets for connection of HART communicators, Packaging unit: 5 pieces bluepa
3-pin screw terminal, For KF modules of K-System, Integrated test sockets for connection of HART communicators, Packaging unit: 5 pieces greenpa
3-pin screw terminal, For KF modules of K-System, Packaging unit: 5 pieces greenpa
Coding of K-System terminal blocks, Coding of LB/FB-System front sockets, Packaging unit: 20 x 6 coding pinspa

Function: KFD2-STC4-Ex2

This isolated barrier is used for intrinsic safety applications.

The device supplies 2-wire SMART transmitters in a hazardous area.

It transfers the analog input signal to the safe area as an isolated current value.

Digital signals may be superimposed on the input signal in the hazardous or safe area and are transferred bi-directionally.

If the HART communication resistance in the loop is too low, the internal resistance of 250 Ω between terminals 8 and 9 can be used.

Test sockets for the connection of HART communicators are integrated into the terminals of the device.