Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH, also apply to Pepperl+Fuchs AG.
Download the complete datasheet as a PDF:
Product Description | ||
---|---|---|
Type Z & Ex pzc purge and pressurization system, external mount, rectangular box |
General specifications | ||
---|---|---|
Equipment architecture | max. enclosure size 450 ft3 (12.7 m3) For complete technical data, see the 7500 Control Unit and 7500-MAN-MV-01 datasheets |
|
Operating mode | fully automatic (FA) | |
Series | 7500 | |
Hazardous environment | gas or dust | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 , FCC CFR 47, part 15, subpart B: 2017, Class A ICES-003, Issue 6:2016, Class A ITE | |
RoHS | ||
Directive 2011/65/EU (RoHS) | EN 50581:2012 | |
Conformity | ||
Degree of protection | Directive conformity: see Declaration of Conformity | |
Ambient conditions | ||
Ambient temperature | Ambient temperature ranges depend on the T class. See the certificates. | |
Storage temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Mechanical specifications | ||
Degree of protection | Mounting to enclosure Type 4X / IP66 | |
Material | screws: AISI 316 (1.4401), 304, or 18-8 stainless steel housing: A380, A356, 6061-T6 aluminum casting mounting gasket: Bisco® HT-800 medium cellular silicone |
|
Mass | 2.5 kg (5 lb 10 oz) | |
Data for application in connection with hazardous areas | ||
Certificate | ||
Marking | ![]() ![]() |
|
Directive conformity | ||
Directive 2014/34/EU | IEC/EN 60079-0 , IEC/EN 60079-2 , IEC/EN 60079-7 , IEC/EN 60079-15 , IEC/EN 60079-31 Supplements: EN 61010-1:2010, EN 61326-3-2:2008, EN 61000-6-2:2005 |
|
International approvals | ||
UL approval | ||
cULus | Class I, Division 2, Groups A, B, C, D T4 (-40 °C ≤ Ta ≤ 70 °C) Class I, Division 2, Groups A, B, C, D T5 (-40 °C ≤ Ta ≤ 65 °C) Class I, Division 2, Groups A, B, C, D, T6 (-40 °C ≤ Ta ≤ 50 °C) Class II, Division 2, Groups F, G T4 (-40 °C ≤ Ta ≤ 70 °C) Class II, Division 2, Groups F, G T5 (-40 °C ≤ Ta ≤ 65 °C) Class II, Division 2, Groups F, G T6 (-40 °C ≤ Ta ≤ 50 °C) |
|
IECEx approval | Ex ec nC [pzc] IIC T6...T4 Gc Ex tc [pzc] IIIC T60 °C ... T80 °C Dc |
|
General information | ||
Supplementary information | Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
CAD | File Type | File Size | |
---|---|---|---|
CAD-files 2-D / CAD-Dateien 2-D | ZIP | 370 KB | |
CAD-files 3-D in IGS format / CAD-Dateien 3-D im IGS-Format | IGS | 130891 KB | |
CAD-files 3-D in STP format / CAD-Dateien 3-D im STP-Format | STP | 13130 KB |
Statements of compliance | Certificate No. | File Type | File Size |
---|---|---|---|
EU-Declaration of Conformity / EU-Konformitätserklärung | DOC-B0C4 | 163 KB | |
Certificates | |||
ATEX Certificate | DEMKO 18 ATEX 2025X | 833 KB | |
China NEPSI | GYJ18.1486X | 1765 KB | |
IECEx Certificate of Conformity | IECEx UL 18.0022X | LINK | --- |
Korea KOSHA | 18-AV4BO-0462X | 504 KB | |
UL Hazardous Location | E184741 (RFPW, RFPW7, RFPZ, RFPZ7) | 404 KB |