Assistance gamme Détecteurs industriels
Support en ligne pour la protection contre le risque d’explosion

6500 proportional Valve 6500-MAN-PV-01

6500-MAN-PV-01
  • Intrinsically Safe, 4 ... 20 mA proportional valve
  • Pneumatic connections 10 mm compression ferrule tube fittings
  • ATEX certification
  • Maximum flow of around 8 scfm
  • Closed loop flow rate control for precise dilution applications

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Téléchargez ici la fiche technique complète en PDF:


Caractéristiques techniques  6500-MAN-PV-01

Description produit
Type Ex px purge and pressurization system
General specifications
Operating modeautomatic purging + pressurization
Electrical specifications
SupplyI.S. 4 to 20 mA loop powered

Entity Parameters:
Ui = 30 V
Ii = 200 mA
C = μS
L = 0 μH
P1 = 1 w total
Pneumatic parameters
Protective gas supplyinstrument grade air or inert gas
Pressure requirement1.0 bar (15 psi) to 8.3 bar (120 psi)
Safe pressureGas: 0.35'' wc (8,88 mm wc) (0.88 mbar/ 88 pa)
Dust: 0.35'' wc (8,88 mm wc) (0.88 mbar/ 88 pa)
Gas+Dust: 0.35'' wc (8,88 mm wc) (0.88 mbar/ 88 pa)
Valve flows6500-MAN-PV: Proportional valve
Purging/pressurization/dilution: 17 l/min to 226 l/min (0.6 to 8 scfm)
ConnectionsInlet and outlet of valves
6500-MAN-PV-01: 3/8"NPT, double ferrule 10mm compression fittings (included)
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Storage temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Connection type10 mm stainless steel ferrule tube fittings
Cable glandI.S. connection: Hirschmann DIN 43650-A connector
Degree of protectionIP65 (DIN connector)
Materialpainted aluminum body
Mass700 g (1.5 lbs)
Dimensions134 x 57 x 80 mm (5.3" x 2.3" x 3.2")
Data for application in connection with hazardous areas
EU-Type Examination CertificateATEX II 1 G EEx ia IIC T4 Tamb= -20 to 60 °C
Directive conformityCE

Classifications

SystemClasscode
ECLASS 13.027180591
ECLASS 12.027180591
ECLASS 11.027180591
ECLASS 10.0.127291390
ECLASS 9.027291390
ECLASS 8.027291390
ECLASS 5.140050501
ETIM 9.0EC000243
ETIM 8.0EC000243
ETIM 7.0EC000243
ETIM 6.0EC000243
ETIM 5.0EC000243
UNSPSC 12.139121303

Details: 6500-MAN-PV-01

Informative Literature: 6500-MAN-PV-01

Language Selection:
LiteratureLangueType de fichierTaille
Application Report - Hydrogen Analysis with Reliable Explosion ProtectionENGPDF253 KB
Application Report - Label Printer Solution for Zone 1/21 and Zone 2/22 ApplicationsENGPDF135 KB

Approvals: 6500-MAN-PV-01

Language Selection:
CertificatesIdentificationLangueType de fichierTaille
EU Sira EC-Type Exam. Certificate ATEX Declaration of ConformityBAS01ATEX1407XALLPDF1680 KB

Découvrez la façon la plus intelligente de garantir la protection des zones à risques d'explosion et de configurer votre système individuel de purge et pressurisation !

Application de contrôle de purge

La nouvelle application du contrôleur de purge série 6500 de Pepperl+Fuchs permet une configuration et une surveillance en temps réel du système de purge et de pressurisation série 6500. Téléchargez dès maintenant l'application pour iOS ou Android…