工業感測器服務資訊
+886 2 27227708
+886-2-27227782
防爆產品服務資訊
暂不可售
暂不可售

Modular Segment Protector for Cabinet Installation RM-SP*

RM-SP*
  • 2 outputs Ex nL, expandable to up to 26 with short-circuit protection
  • High-power trunk for high device count and long cable lengths
  • Segment Protector in Zone 2/Div. 2
  • Instruments in Zone 2/Div. 2
  • For FOUNDATION Fieldbus H1 and PROFIBUS PA
  • Power, Com, and Error LEDs
  • Integrated overvoltage protection

请注意:所有以Pepperl + Fuchs GmbH或Pepperl + Fuchs AG名义发行的产品相关文件,例如证书,合格声明等,同样适用于Pepperl + Fuchs SE。

產品規格摘要:的技術資料  RM-SP*

General specifications
Design / MountingCabinet installation
Fieldbus connection
Power dissipationsee table "Technical data depending on model"
Main cable (Trunk)
Rated voltage9 ... 31 V DC
Rated currentmax. 4.5 A
Outputs
Number of outputssee table "Technical data depending on model"
Rated voltagemax. 31 V
Rated currentmax. 43 mA
Short-circuit currentmax. 58 mA
Self current consumptionsee table "Technical data depending on model"
Voltage drop main cable/outputsmax. 1.3 V
Terminating resistor100 Ω external
Surge protectionTrunk overvoltage protection if voltage exceeds typ. 39 V, max. 41 V
Indicators/operating means
LED ERRred: short-circuit
LED PWRgreen: Fieldbus voltage > 10 V
LED COMyellow: bus activity
Directive conformity
Electromagnetic compatibility
Directive 2004/108/ECEN 61326-1:2006
Standard conformity
Electromagnetic compatibilityNE 21:2006
Degree of protectionIEC 60529
Fieldbus standardIEC 61158-2
Shock resistanceEN 60068-2-27
Vibration resistanceEN 60068-2-6
Ambient conditions
Ambient temperature-40 ... 70 °C (-40 ... 158 °F)
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Relative humidity< 95 % non-condensing
Shock resistance15 g 11 ms
Vibration resistance1 g , 10 ... 150 Hz
Corrosion resistanceacc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Connection typescrew terminals, removable
Core cross sectionmax. 2.5 mm2 /AWG 12-24
Housing materialPolyamide PA 66
Degree of protectionIP20
Mass75 g per device
Dimensions
Height94 mm
Width17.5 mm per device
Depth54 mm
MountingDIN rail mounting
Data for application in connection with hazardous areas
Main cable (Trunk)
Rated currentsee Statement of Conformity
Outputs
Voltage24 V for IIC gas group, defined by trunk voltage
32 V for IIB gas group
Current65 mA for IIC and IIB gas groups
Inductance0.25 mH for IIC and IIB gas groups
Capacitance60 nF for IIC and IIB gas groups
CertificateTÜV 11 ATEX 081152 X
MarkingEx-Hexagon II 3G Ex nA [nL] IIC T4
Directive conformity
Directive 94/9/ECEN 60079-15:2005 , EN 60079-0:2006
International approvals
UL approvalE106378
Approved forClass I, Division 2, Groups A, B, C, D
Certificates and approvals
Marine approvalDNV A-10798
General information
Supplementary informationStatement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027242610
ECLASS 12.027242610
ECLASS 11.027242610
ECLASS 10.0.127242610
ECLASS 9.027242610
ECLASS 8.027242610
ECLASS 5.127242601
ETIM 9.0EC001601
ETIM 8.0EC001601
ETIM 7.0EC001601
ETIM 6.0EC001601
ETIM 5.0EC001604
UNSPSC 12.139121008

Details: RM-SP*

Datasheet: RM-SP*

Datasheet檔案類型檔案尺寸
Datasheet RM-SP*PDF1105 KB
Datenblatt RM-SP*PDF1109 KB

Approvals+Certificates: RM-SP*

Certificates檔案類型檔案尺寸
USA ULLINK---
Worldwide Fieldbus FoundationPDF29 KB

Ethernet-APL 支持跨所有層級的連續通信。 了解有關開創性技術的更多信息……

RSS Info Service for PANOS Updates

Stay informed when a new software update of PANOS, the operating system for Ethernet-APL switches, is released: With our RSS Feed you will get an email notfication in your inbox immediately after an update has been released.

從決策到規劃、安裝和調試再到操作和維護:了解如何充分利用您的現場總線基礎設施……