Explosion Proof Power Contactors |
Electrical specifications | ||
---|---|---|
Operating voltage | 115 ... 460 V | |
Rated frequency | 50/60 Hz | |
Short circuit current limitation | see data table | |
Operating current | 18 A - 170 A | |
Rated insulation voltage | 690 V | |
Function | Power control | |
Contact configuration | see data table | |
Usage category | see data table | |
Number of poles | see data table | |
Auxiliary contacts | One (1) normally open contact | |
Auxiliary contacts usage category | see data table | |
Mechanical specifications | ||
Thread type | metric ISO pitch 1.5 mm or NPT ANSI ASME B1.20.1 | |
Enclosure range | EJB | |
Enclosure cover | fully detachable | |
Cover fixing | stainless steel socket cap head screws | |
Screws | see data table | |
Yield stress | min. 450 N/mm2 | |
Cover seal | none | |
Flamepath grease | Greasil MS4 or NEVER SEEZ Marine Grade | |
Degree of protection | Type 4, 4X, 7, 9 / IP66 | |
Cable entry | see data table | |
Defined entry area | face B | |
Material | ||
Enclosure | Copper-free aluminum alloy or 316L stainless steel | |
Finish | For aluminum: epoxy coated RAL 7005 (grey) | |
Mass | see data table | |
Dimensions | see data table values might differ slightly due to casting and manufacturing tolerances |
|
Tightening torque | ||
Nut torque at enclosure (SW1) | see datasheets of stopping plugs | |
Mounting | see data table | |
Grounding | M6 external grounding points | |
Ambient conditions | ||
Ambient temperature | -20 ... 50 °C (-4 ... 122 °F) @ T6 | |
Data for application in connection with hazardous areas | ||
EU-type examination certificate | INERIS 14 ATEX 0022X | |
Marking | II 2 GD Ex d IIB+H2 T* Gb Ex tb IIIC Db |
|
International approvals | ||
UL approval | Enclosure only | |
cULus | Class I, Division 1, Groups B, C, D Class II, Division 1, Groups E, F, G | |
IECEx approval | IECEx INE 14.0029X | |
Conformity | ||
Degree of protection | EN60529 | |
Usage category | IEC / EN 60947 | |
CE marking | 0539 | |
General information | ||
Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
System | Classcode |
---|---|
ECLASS 13.0 | 27180508 |
ECLASS 12.0 | 27180508 |
ECLASS 11.0 | 27180508 |
ECLASS 10.0.1 | 27180508 |
ECLASS 9.0 | 27180508 |
ECLASS 8.0 | 27180508 |
ECLASS 5.1 | 40050501 |
ETIM 9.0 | EC000243 |
ETIM 8.0 | EC000243 |
ETIM 7.0 | EC000243 |
ETIM 6.0 | EC000243 |
ETIM 5.0 | EC000243 |
UNSPSC 12.1 | 39121301 |
Model EXPC Explosion Proof Power contactors are non-reversing electrical "relays" contained within an explosionproof housing. The contactors have inductive power ranges from 18 ...170 amps and are offered with 120 VAC, 220 VAC, or 24 VDC operating coils to accommodate a wide array of power control applications.
The explosionproof enclosures housing the contactors are suitable for Class I, Division I, Groups B, C, and D; Class II, Division 1, Groups E, F, and G; and Class I, Zone I, Group IIB hazardous location ratings. The housings are rated for Type 4X / IP66 service capability and are furnished with door hinges. The housings graduate in size to accommodate each contactor while providing adequate space for wire bend radius limitations established by the National Electric Code (NEC).
The contactor is activated by the application of control voltage to the operating coil. The contactor then engages the non-reversing normally-open contactor poles to apply power to the protected enclosure or controlled device. The contactor is deactivated by removing control voltage from the operating coil. The contactor then disengages the poles, thus removing power from the protected enclosure or controlled device.