Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Download the complete datasheet as a PDF:
Product Description |
---|
Starter Kit for PROFIBUS PA Infrastructure |
General specifications | ||
---|---|---|
Design / Mounting | Cabinet installation | |
Connections | ||
Field devices | 6 , any PA field device | |
Supply voltage | 90 ... 253 V AC | |
Fieldbus connection | ||
Number of segments | 2 | |
Rated voltage | 24 ... 26 V DC | |
Rated current | ... 400 mA | |
Terminating resistor | integrated | |
Fieldbus distribution | ||
Number of outputs | 6 | |
Rated output voltage | max. 31 V DC | |
Rated output current | max. 43 mA | |
Short-circuit current | max. 58 mA | |
Terminator | external | |
General information | ||
Supplementary information | Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
System | Classcode |
---|---|
ECLASS 13.0 | 27242692 |
ECLASS 12.0 | 19170104 |
ECLASS 11.0 | 27242692 |
ECLASS 10.0.1 | 27242692 |
ECLASS 9.0 | 27242692 |
ECLASS 8.0 | 27242692 |
ECLASS 5.1 | 27242692 |
ETIM 9.0 | EC002584 |
ETIM 8.0 | EC002584 |
ETIM 7.0 | EC002584 |
ETIM 6.0 | EC002584 |
ETIM 5.0 | EC001604 |
UNSPSC 12.1 | 39121008 |
The starter kit for PROFIBUS PA includes all hardware components in order to power and connect field devices to a host system. The starter kit is designed to conveniently build out-ofthe- box test environments. The test environment can be supplied by regular 90 … 253 V AC power.
The basic Segment Coupler transparently connects field devices to the PROFIBUS DP master. PROFIBUS PA devices are configured as ordinary PROFIBUS DP slaves. The basic Segment Coupler requires zero configuration and provides a current load of up to 400 mA.
A Segment Protector enables connection of up to 6 field devices to the host with individual short circuit current limitation. The system can be expanded at any time with additional components from the FieldConnex® system.
Note: The PROFIBUS DP master, field devices, cables and wiring are not included. The starter kit is limited to 1 per customer and location.