Select Your Country
LCL2 Capacitive Limit Switch
Key Benefits at a Glance
- Limit switch for bulk solids
- Device with rope probe
- Rope probe can be shortened for optimum matching to the measuring point
- Complete unit consisting of the probe and electronic insert
- Integrated active build-up compensation: exact switch point, even with strong build-up
- Mechanically rugged: no wearing parts, long operating life, maintenance-free
Show more






Note
All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
EN
- EN
- DE
Technical data of LCL2
| Measuring method | A metal plate at the end of the probe, within the insulation, and the surroundings (e. g. the silo walls) combine to form the two electrodes of a capacitor. If the probe is covered or free of material, then the capacitance changes and the LCL switches. | |
| Equipment architecture | The measuring system consists of: - the device - a supply point - the connected control systems, switching units, signalling systems (e. g. lamps, horns, PCS, PLC, etc.) | |
| Construction type | device with rope probe | |
| Operating mode | MAX = maximum safety: The device switches if the probe is covered or if the supply voltage is disconnected in a safety-oriented manner (signal on alarm). example application: overspill protection MIN = minimum safety: The device switches if the probe is uncovered or if the supply voltage is disconnected in a safetyoriented manner (signal on alarm). example application: dry-running protection | |
| Series | LCL2 |
| Rated voltage | Ur | electrical connection E5: 10.8 ... 45 V DC, short-term pulse on 55 V DC electrical connection WA: 20 ... 235 V AC, 50/60 Hz or 20 ... 55 V DC |
| Current consumption | electrical connection E5: max. 30 mA, reverse-polarity-proof electrical connection WA: max. 130 mA |
| Surge protection | overvoltage category III |
| Measured variable | limit level (limit value) | |
| Measuring range | dielectric constant ≥ 1.6 |
| Switch-on delay | ton | correct switching after max. 2 s |
| Output signal | connection E5: switching PNP, Imax = 200 mA - overload and short circuit protection - residual voltage at transistor at Imax < 2.9 V connection WA: contact change-over, potential-free - Umax = 253 V - Imax = 4 A (AC) - Pmax = 1000 VA, cos φ = 1, Pmax = 500 VA, cos φ > 0.7 | |
| Signal on alarm | connection E5: < 100 µA connection WA: relay de-energized |
| Electromagnetic compatibility | |||||
| |||||
| Low voltage | |||||
| |||||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529:2001 | |
| Vibration resistance | EN 60068-2-64 | |
| Climate class | EN 60068, part 2-38 (test Z/AD) |
| Reference operating conditions | vessel type: plastic vessel, ambient temperature: 73 °F (23 °C, 296 K), medium temperature: 73 °F (23 °C, 296 K) medium pressure pe: 0 bar, medium: dielectric constant = 2.6, conductivity: < 1 µS sensitivity setting: C | |
| Hysteresis | vertical 5 mm (0.2 inch) | |
| Long-term drift | vertical 6 mm (0.24 inch) | |
| Influence of medium temperature | depending on the filling material | |
| Switching time | approx. 0.8 s when covering and uncovering the sensor |
| Installation conditions | |||||||||||||||||
| |||||||||||||||||
| Process conditions | |||||||||||||||||
| |||||||||||||||||
| Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) -40 ... 60 °C (-40 ... 140 °F) (Dust-Ex version) | |
| Storage temperature | -40 ... 80 °C (-40 ... 176 °F) | |
| Shock resistance | device with F34 housing: 7 J | |
| Vibration resistance | a(RMS) = 50 m/s2, ASD = 1.25 (m/s2)2/Hz, f = 5 to 2000 Hz, t = 3 x 2 h |
| Degree of protection | IP66, NEMA 4 | |
| Connection | gland M20 thread G1/2, NPT1/2 | |
| Material | F14 housing: polyester PBT-FR F34 housing F34: aluminum Probe: PPS GF40 probe rope: PE-HD probe rope seal: VMQ | |
| Dimensions | max. ∅94 mm (3.7 inch), length 140 mm (5.5 inch) + L L = 500 ... 6000 mm (19.7 ... 236 inch) | |
| Process connection | thread R1-1/2 acc. to EN 10226, BSPT thread NPT1-1/2 to ANSI B 1.20.1 |
| EU-type examination certificate | see instruction manuals (SI) | ||||
| Directive conformity | |||||
| |||||
| Supplementary documentation | technical information (TI) manuals, brief instructions (BA, KA) instruction manuals (SI) | |
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
| Designation | - LCL-Z10 cover with sight glass for F14 housing - LCL-Z14 rope shortening set |
Related Pages
Are you looking for more information? Feel free to learn more on our related pages.
Related News and Applications
Read more on news and applications related to this product.