Assistance gamme Détecteurs industriels
Support en ligne pour la protection contre le risque d’explosion

Temperature Multi-Input Device with Aluminum Housing F2D0-TI-Ex8.PA.*

FieldConnex® Fieldbus
F2D0-TI-Ex8.PA.*
  • For 8 temperature or analog sensors
  • Installation in Zone 1/Div. 1, intrinsically safe
  • Sensors in Zone 0/Div. 1
  • Connection to fieldbus acc. to FISCO or Entity
  • For PROFIBUS PA
  • DCS integration via GSD and FDT/DTM
  • Monitors sensor condition
  • For T/C, RTD 2-, 3-, 4-wire, voltage and resistance
  • Cold junction compensation
  • Removable terminals

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Téléchargez ici la fiche technique complète en PDF:


Caractéristiques techniques  F2D0-TI-Ex8.PA.*

General specifications
Design / MountingOutside installation
Installation in hazardous areaZone 1 / Div. 1
Electronic componentTemperature Multi-Input Device RD0-TI-Ex8.PA* For technical data on installed electronic component see datasheet.
Fieldbus connection
Fieldbus typePROFIBUS PA
Input
Number8
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013
Standard conformity
Galvanic isolationEN 60079-11
Electromagnetic compatibilityNE 21:2011
Degree of protectionIEC 60529
Fieldbus standardIEC 61158-2
Shock resistanceEN 60068-2-27
Vibration resistanceEN 60068-2-6
Ambient conditions
Ambient temperaturesee table 1
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Relative humidity≤ 95 % non-condensing
Shock resistance15 g , 11 ms
Vibration resistance10 g , 10 ... 150 Hz
Corrosion resistanceacc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Connection typeplug-in terminals , spring terminal and screw terminal
Core cross section
Busup to 2.5 mm2
Inputsup to 2.5 mm2
Cable diametersee table 2
Cable glandsensor inputs M16, fieldbus M20
Housing materialAluminum
Degree of protectionIP67
Mass1800 g
Data for application in connection with hazardous areas
EU-type examination certificatePTB 03 ATEX 2237
MarkingEx-Hexagon II 2 (1) G Ex ia [ia Ga] IIC T4 Gb , Ex-Hexagon II (1) G [Ex ia Ga] IIC , Ex-Hexagon II (1) D [Ex ia Da] IIIC , Ex-Hexagon II 3 G Ex ic IIC T4 Gc
BusFISCO see EC-Type Examination Certificate
Voltage Ui24 V
Inputssee EC-Type Examination Certificate
CertificatePTB 03 ATEX 2238 X
MarkingEx-Hexagon II 3 G Ex nA IIC T4 Gc
Galvanic isolation
Bussee Statement of Conformity
Inputsee EC-Type Examination Certificate
Directive conformity
Directive 2014/34/EUEN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
FM approvalCoC 3025732
CSA approvalCoC 3025732C
IECEx approvalIECEx PTB 05.0001 , IECEx PTB 05.0002X
Approved forEx ia [ia Ga] IIC T4 Gb , [Ex ia Ga] IIC , [Ex ia Da] IIIC , Ex ic IIC T4 Gc , Ex nA IIC T4 Gc
Certificates and approvals
Marine approvalDNV A-14038
General information
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027242610
ECLASS 12.027242610
ECLASS 11.027242610
ECLASS 10.0.127242610
ECLASS 9.027242610
ECLASS 8.027242610
ECLASS 5.127242610
ETIM 9.0EC001601
ETIM 8.0EC001601
ETIM 7.0EC001601
ETIM 6.0EC001601
ETIM 5.0EC001604
UNSPSC 12.139121008

Details: F2D0-TI-Ex8.PA.*

Informative Literature: F2D0-TI-Ex8.PA.*

Language Selection:
LiteratureLangueType de fichierTaille
Application Report - Controlling and Monitoring liquid Helium at the Deutsches Elektronen-SynchrotronENGPDF361 KB
Application Report - Digital Communication in Steel-Plate ManufacturingENGPDF470 KB

Product Documentation: F2D0-TI-Ex8.PA.*

Language Selection:
Safety and Security DocumentationLangueType de fichierTaille
Manuel d'instructionsFRAPDF232 KB
Manuals
ManualENGPDF4255 KB
Software Information
Release information Device Description (EDDL) for Siemens SIMATIC PDMENGPDF403 KB

Design / Simulation: F2D0-TI-Ex8.PA.*

Language Selection:
CADLangueType de fichierTaille
CAD 3-D / CAD 3-DALLSTP5195 KB

Approvals: F2D0-TI-Ex8.PA.*

Language Selection:
CertificatesIdentificationLangueType de fichierTaille
Brasil TUV Rheinland BrazilTÜV 13.1136ALLPDF1200 KB
Brasil TUV Rheinland BrazilTÜV 13.1134 XALLPDF1198 KB
Canada FMCoC 3025732CALLPDF316 KB
China SITIIAS CCC Ex Certificate2020322314002489 (Singapore)ALLPDF2152 KB
Europe PTB ATEX Category 2 (1)PTB 03 ATEX 2237ALLPDF884 KB
Europe PTB ATEX Category 3 GPTB 03 ATEX 2238XALLPDF617 KB
India PESO (India) CCOEA/P/HQ/KA/104/5828 (P489740)ALLPDF79 KB
PTB IECEx Certificate of ConformityIECEx PTB 05.0001ALLLINK---
PTB IECEx Certificate of ConformityIECEx PTB 05.0002XALLLINK---
USA FMCoC 3025732ALLPDF316 KB
Control Drawings
Control drawing FM / Control drawing FM   ALLPDF249 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-0148FALLPDF2042 KB

Software: F2D0-TI-Ex8.PA.*

Language Selection:
Device Description Files/DriversParutionType de fichierTaille
GSD / GSDRev. 1.0ZIP6 KB
DTM Collection FieldConnex / DTM Collection FieldConnex1.9.0.2268ZIP35363 KB
Device Description (EDDL) for Siemens SIMATIC PDM / Gerätebeschreibung (EDDL) für Siemens SIMATIC PDM1.0.0.585ZIP473 KB

Produits associés : F2D0-TI-Ex8.PA.*

Matching System Components
FieldConnex® Fieldbus, Temperature multi-input, electronic component for control cabinet installation, For 8 temperature or analog sensors, Installation in Zone 1/Div. 1, intrinsically safe, Sensors in Zone 0/Div. 1, Connection to fieldbus acc. to FISCO or Entity, For PROFIBUS PA, IECEx approval, Dust protection, Europe, USA, Canadapa
Accessories
User interface for PROFIBUS components, Simple access to measurements, diagnostic and configuration data, Supports any FDT/DTM hostpa
Software for connecting people, information, systems, and devices, For applications developed using .NET, Required to run PACTwarepa
Universal DTM host platform, For all DTMs of Pepperl+Fuchs, Approved FDT/DTM technology, Free of charge, Download from Pepperl+Fuchs websitepa
Universal DTM host platform, For all DTMs of Pepperl+Fuchs, Approved FDT/DTM technology, Free of charge, Internet download possiblepa

Ethernet-APL assure une communication continue à tous les niveaux hiérarchiques. En savoir plus sur cette technologie pionnière…

Mises à jour RSS Info Service pour PANOS

Soyez informé dès qu'une nouvelle mise à jour logicielle de PANOS, le système d'exploitation des commutateurs Ethernet-APL, est disponible : Grâce à notre flux RSS vous serez immédiatement informé par e-mail de la publication d'une mise à jour.

De la prise de décisions à la planification, en passant par l'installation et la mise en service, sans oublier l'exploitation et la maintenance : Découvrez comment tirer le meilleur parti de votre infrastructure de bus de terrain…