Select Your Country

Go to global website

KFU8-DW-1.D Rotation Speed Monitor

Key Benefits at a Glance

  • Speed monitoring up to 40 kHz
  • 1 pre-select value with relay output and LED indicator
  • 2-, 3-, 4-wire and NAMUR sensors as well as rotary encoder connectable
  • Start-up delay
  • Menu driven operation via 4 front keys
  • Period measurement
  • Output signal can be inverted
  • Display devices can be set between 0.1 ... 2.5 sec.

Show more

Please contact us for exact delivery estimation.4 519,00 SEK Net price—your individual price will be shown during checkout process.
Product Compliance: USA - CSA
Product Compliance: United Kingdom – UKCA
Product Compliance: Europe – CE
Note

All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

DE
  • DE
  • EN
  • ES
  • FR
  • SL
  • ZH

Technical data of KFU8-DW-1.D

Rotation Speed Monitor
MTTFd100 a
Rated voltageUr200 ... 230 V AC ; 100 … 130 V AC; 50/60 Hz
20 VDC ... 30 VDC
Fusingexternal fusing 4 A
Power consumptionAC: < 5 VA
DC: < 5 W
Connectionterminals 8-, 9+
Connectable sensor typesNAMUR sensors according to DIN EN 60947-5-6
Open loop voltage8.2 V DC
Short-circuit current6.5 mA
Switching point1.2 ... 2.1 mA Switching hysteresis approx. 0.2 mA
Input frequency0.002 ... 10000 Hz, pulse length/duration: ≥ 20µs
Impedance1.2 kΩ
Switching pointhigh: 16 ... 30 V DC; max.10 mA due to integrated constant current sink; Ri ≅ 3 kΩ
low: 0 ... 6 V DC
Input frequency0.002 ... 40000 Hz, pulse length/duration: ≥ 12µs
Connectionterminals 7+, 13- sensor supply
terminals 14, 15 NPN/PNP input (galvanically isolated)
Connectable sensor types2-, 3-, or 4-wire proximity sensor, incremental rotary encoder, or externally generated pulses 16 ... 30 V
Sensor supply19 ... 28 V DC non-stabilised; ≤ 30 mA short-circuit protected
Start-up overrideTriggering by external signal 16 ... 30 V or Place jumper between terminals 2/3 or by switching on supply voltage (terminal 2 and terminal 3 permanently bridged)
Hold-up time0.1 ... 999.9 s (External trigger signal)
Relay1 changeover contact
NO, NC, COM
Sensor supply24 V DC ± 10 %, 30 mA , short-circuit protected
Contact loading250 V AC/2 A/ cos φ ≥ 0.7
40 V DC/2 A
Delay≤ 20 ms (incl. calculation time)
Mechanical life≥ 30.000.000 switching cycles
Changing interval5 ms (Internal processing time)
Time delay before availability≤ 400 ms
Measuring error0 ... 40000 Hz: ≤ ±0,10%
Display: ±1 digit
Timer functionON-delay, OFF-delay, one shot, pulse extension
Time0 ... 999.9 s ; mode of operation reversible
Electromagnetic compatibilityacc. to EN 50081-2 / EN 50082-2
Ambient temperature-25 ... 40 °C (-13 ... 104 °F)
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Relative humiditymax. 80 %, not condensing
Altitude0 ... 2000 m
Operating conditionsThe device has only to be used in an indoor area.
Connection assemblyCaution: Please be aware that the device may only be connected to a switchable power supply. The switch or circuit breaker must be easy to reach and identified as the separator for the device.
Degree of protectionIP20
Connectioncoded, removable terminals , max. core cross section 0.34 ... 2.5 mm2
Construction typemodular terminal housing in Makrolon, System KF
For use in the switch cabinet/switch cabinet module
Mountingsnap-on to 35 mm standard rail or screw fixing