921FS5-T-030-Z600 Inductive Sensor

Key Benefits at a Glance

  • Comfort series

NAMUR sensors must be operated with approved switch amplifiers. Please find suitable devices below:

View switch amplifiers
Product Compliance: Europe – CE
Product Compliance: United Kingdom – UKCA
Note

All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

SV
  • SV
  • EN
  • CS
  • DE
  • ES
  • FR
  • IT
  • PL
  • PT

Technical data of 921FS5-T-030-Z600

Switching functionNormally closed (NC)
Output typeNAMUR
Rated operating distancesn5 mm
Installationflush
Assured operating distancesa0 ... 4.05 mm
Reduction factor rAl 0.3
Reduction factor rCu 0.2
Reduction factor r304 0.7
Output type2-wire
Nominal voltageUo8.2 V (Ri approx. 1 kΩ)
Switching frequencyf0 ... 500 Hz
Short-circuit protectionyes
Current consumption
Measuring plate not detectedmin. 2.2 mA
Measuring plate detected≤ 1 mA
Standard conformity
NAMUREN 60947-5-6:2000
IEC 60947-5-6:1999
StandardsEN IEC 60947-5-2
CCC approvalCCC approval / marking not required for products rated ≤36 V
Ambient temperature-20 ... 110 °C (-4 ... 230 °F)
Connection typecable
Housing materialStainless steel
Sensing faceCeramic
Degree of protectionIP67
Cable
Wire end ferrulesyes
Cable diameter4 mm ± 0.2 mm
Bending radius> 7.5 x cable diameter
MaterialFEP
Colorwhite
Number of cores2
Core cross section0.355 mm2
LengthL3 m
Dimensions
Height30 mm
Diameter20 mm
General Notes