Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Téléchargez ici la fiche technique complète en PDF ::
General specifications | ||
---|---|---|
Design / Mounting | Motherboard based | |
Supply | ||
Connection | redundant | |
Rated voltage | 19.2 ... 35 V SELV/PELV | |
Rated current | 3230 ... 1820 mA | |
Fieldbus connection | ||
Number of segments | ||
Redundant | 4 | |
Rated voltage | 20.8 ... 22.3 V | |
Rated current | 360 ... 10 mA | |
Short-circuit current | 413 mA | |
Host-side | 25-pin Sub-D socket | |
Host-rated voltage | 10.1 ... 11 V | |
Host-rated current | ... 40 mA | |
Host short-circuit current | ... 50 mA | |
Terminating resistor | 100 Ω , integrated | |
Indicators/operating means | ||
LED ERR | red flashing: short-circuit or undervoltage at output | |
LED PWR | green if Uout > 21 V | |
Fault signal | VFC alarm output via connectors | |
Rated voltage | 50 V | |
Rated current | 1 A | |
Galvanic isolation | ||
Host-side/Supply | 50 V functional insulation acc. to IEC 62103 | |
Fieldbus segment/Host-side | 250 V safe galvanic isolation acc. to EN 60079-11:2007 | |
Fieldbus segment/Fieldbus segment | 60 V safe galvanic isolation acc. to EN 60079-11:2007 | |
Fieldbus segment/Supply | 250 V safe galvanic isolation acc. to EN 60079-11:2007 | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2004/108/EC | EN 61326-1:2006 | |
Standard conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529 | |
Fieldbus standard | IEC 61158-2 | |
Shock resistance | EN 60068-2-27 | |
Vibration resistance | EN 60068-2-6 | |
Ambient conditions | ||
Ambient temperature | -40 ... 60 °C (-40 ... 140 °F) when mounted on a horizontal DIN rail | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Relative humidity | < 95 % non-condensing | |
Shock resistance | 15 g , 11 ms | |
Vibration resistance | 1 g , 10 ... 150 Hz | |
Pollution degree | max. 2, according to IEC 60664 | |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 | |
Mechanical specifications | ||
Connection type | plug with screw flange | |
Core cross section | 2.5 mm2 | |
Housing material | Polycarbonate | |
Degree of protection | IP20 | |
Mass | approx. 2.4 kg | |
Dimensions | see dimensions | |
Mounting | DIN mounting rail , according to DIN EN 60715 | |
Data for application in connection with hazardous areas | ||
EU-type examination certificate | PTB 10 ATEX 2034 , PTB 10 ATEX 2020 X , PTB 11 ATEX 2010 X | |
Marking | II 2 G Ex ib IIC T4 , II (2) D [Ex ib] IIIC , II 3(2) G Ex nAc [ib] IIC T4 | |
Supply | ||
Maximum safe voltage | 35 V | |
Host interface | ||
Maximum safe voltage | 35 V | |
Alarm output | ||
Maximum safe voltage | 35 V | |
Directive conformity | ||
Directive 94/9/EC | EN 60079-0:2009 , EN 60079-11:2007 , EN 60079-15:2006 , EN 60079-25:2010 , EN 61241-11:2006 | |
International approvals | ||
IECEx approval | IECEx PTB 12.0022X IECEx PTB 12.0023X IECEx PTB 12.0024X | |
Approved for | [Ex ib] IIC [Ex ib] IIIC Ex nAc II T4 |
|
Certificates and approvals | ||
FOUNDATION Fieldbus | FF-831 | |
Marine approval | DNV A-14038 | |
General information | ||
Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
System | Classcode |
---|---|
ECLASS 13.0 | 27242610 |
ECLASS 12.0 | 27242610 |
ECLASS 11.0 | 27242610 |
ECLASS 10.0.1 | 27242610 |
ECLASS 9.0 | 27242610 |
ECLASS 8.0 | 27242610 |
ECLASS 5.1 | 27242610 |
ETIM 9.0 | EC001600 |
ETIM 8.0 | EC001600 |
ETIM 7.0 | EC001600 |
ETIM 6.0 | EC001600 |
ETIM 5.0 | EC001604 |
UNSPSC 12.1 | 39121004 |
Le Power Hub haute densité DART de la gamme FieldConnex ® est une alimentation modulaire pour bus de terrain pour quatre segments. Il supporte en option un système de diagnostic avancé pour un démarrage rapide et une surveillance en ligne du bus de terrain. Le kit comprend une carte mère et huit modules d'alimentation (2 modules par segment).
DART (Dynamic Arc Recognition and Termination) permet d'optenir un tronc haute puissance de sécurité intrinsèque pour un segment entièrement de sécurité intrinsèque selon IEC 60079-11.
Un connecteur Sub-D à 25 pôles avec alimentation de bus de terrain se raccorde au coupleur de segment pour une connexion PROFIBUS DP directe. Grâce à des câbles conçus sur mesure cette plate-forme d'alimentation est facilement adaptable à tout système de contrôle FF. Les emplacements prévus pour les modules permettent une installation simple et un remplacement sans outils. L'alimentation redondante implique une répartition de la charge par le partage du courant de charge sur chaque module. L'isolation des trois points de connexions, entre le segment, la tension auxiliaire et le système hôte améliore la fiabilité du système.
Disponibilité et longue durée de vie est assurée par : un seul filtre d'impédance passive par segment, une construction optimisée pour une faible dissipation thermique, une terminaison de bus de haute disponibilité et des connecteurs avec des vis de fixation.
Literature | Langue | Type de fichier | Taille |
---|---|---|---|
Application Report - Controlling and Monitoring liquid Helium at the Deutsches Elektronen-Synchrotron | ENG | 361 KB | |
Application Report - Digital Communication in Steel-Plate Manufacturing | ENG | 470 KB |
Manuals | Langue | Type de fichier | Taille |
---|---|---|---|
Manual | ENG | 4188 KB |
CAD | Langue | Type de fichier | Taille |
---|---|---|---|
CAD 2-D / CAD 2-D | ALL | ZIP | 2933 KB |
Certificates | Identification | Langue | Type de fichier | Taille |
---|---|---|---|---|
DNV Marine | TAA0000272 | ALL | 100 KB | |
Declaration of Conformity | ||||
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F) | DOC-0813 | ALL | 1171 KB |
Matching System Components | ||||||
---|---|---|---|---|---|---|
|
||||||
|
||||||
|
||||||
|