Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Téléchargez ici la fiche technique complète en PDF:
Supply | ||
---|---|---|
Rated voltage | 24 V DC | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 89/336/EEC | EN 61000-6-2 , EN 61000-6-3 | |
Conformity | ||
Galvanic isolation | EN 50178 | |
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 50 °C (-4 ... 122 °F) | |
Mechanical specifications | ||
Degree of protection | IP68 | |
Connection | cable , length 5 m (15 ft) , 2 x 0.75 mm2 cross section | |
Material | nickel-plated steel | |
Mass | approx. 375 g | |
Dimensions | ∅26.9 x 128 mm | |
Length | 128 mm | |
Diameter | 26.9 mm | |
Data for application in connection with hazardous areas | ||
EU-type examination certificate | DEMKO 07 ATEX 142588 | |
Marking | II 1G Ex ia IIB T3 | |
Voltage | 24 V DC | |
Current | 400 mA | |
Power | 1.6 W | |
Internal capacitance | 600 pF 0.1 F for extension cable |
|
Internal inductance | 0.1 mH 0.3 mH for extension cable |
|
Directive conformity | ||
Directive 94/9/EC | EN 50014, EN 50020, EN 60079-14 | |
General information | ||
Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
System | Classcode |
---|---|
ECLASS 13.0 | 27230191 |
ECLASS 12.0 | 27279090 |
ECLASS 11.0 | 27279090 |
ECLASS 10.0.1 | 27279090 |
ECLASS 9.0 | 27279090 |
ECLASS 8.0 | 27279090 |
ECLASS 5.1 | 27230290 |
ETIM 9.0 | EC003619 |
ETIM 8.0 | EC003619 |
ETIM 7.0 | EC003619 |
ETIM 6.0 | EC001447 |
ETIM 5.0 | EC001447 |
UNSPSC 12.1 | 41111954 |