Select Your Country
KCD2-SLD-Ex2.1545-Y1.SP Solenoid Driver
Key Benefits at a Glance
- 2-channel isolated barrier
- 24 V DC supply (bus or loop powered)
- Output 45 mA at 15 V DC
- Line fault transparency (LFT)
- Test pulse immunity
- Housing width 12.5 mm
- Connection via spring terminals with push-in connection technology
Show more






Note
All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
EN
- EN
- DE
Technical data of KCD2-SLD-Ex2.1545-Y1.SP
| Signal type | Digital Output |
| Connection | Power Rail or terminals 9+, 10- bus powered | |
| Rated voltage | Ur | 18 ... 30 V DC |
| Power dissipation | < 2 W | |
| Power consumption | max. 3.5 W at 45 mA output current |
| Connection side | control side | |
| Connection | terminals 5+, 6-; 7+, 8- limited electrical values : max. 30 V , max. 5 A | |
| Test pulse length | max. 2 ms from DO card | |
| Signal level | loop powered 1-signal: 18 ... 30 V DC (current limited to ≥ 20 mA) 0-signal: 0 ... 5 V DC bus powered 1-signal: 15 ... 24 V DC (current limited at 5 mA) 0-signal: 0 ... 5 V DC | |
| Rated current | Ir | loop powered 0-signal: typ. 1.6 mA at 1.5 V DC; typ. 8 mA at 3 V DC (maximum leakage current DO card) 1-signal: ≥ 20 mA (minimum load current DO card) bus powered 1-signal: 5 mA |
| Inrush current | ≤ 200 mA after 100 µs |
| Connection side | field side | ||||
| Connection | terminals 1+, 2-; 3+, 4- | ||||
| Internal resistor | Ri | approx. 167 Ω | |||
| Current | Ie | ≤ 45 mA | |||
| Voltage | Ue | ≥ 15 V | |||
| Current limit | Imax | 45 mA | |||
| Open loop voltage | Us | min. 23.6 V | |||
| Load | nominal 0.05 ... 20 kΩ , valid range for line fault detection (LFD) | ||||
| Energized/De-energized delay | ≤ 20 ms / ≤ 20 ms | ||||
| Line fault detection | |||||
| |||||
| Input/Output | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
| Power supply/Output | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
| Display elements | LEDs | |
| Control elements | DIP switch | |
| Configuration | via DIP switches | |
| Labeling | space for labeling at the front |
| Electromagnetic compatibility | |||||
| |||||
| Electromagnetic compatibility | NE 21:2017 , EN IEC 61326-1:2021 (industrial locations) , EN IEC 61326-3-2:2018 For further information see system description. | |
| Degree of protection | IEC 60529:2013 | |
| Protection against electrical shock | UL 61010-1:2019 |
| Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) |
| Degree of protection | IP20 | |
| Connection | spring terminals | |
| Mass | approx. 105 g | |
| Dimensions | 12.5 x 124 x 114 mm (0.5 x 4.9 x 4.5 inch) (W x H x D) , housing type A2 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
| EU-type examination certificate | UL 23 ATEX 3027 X | |||||||||||||||||||
| ||||||||||||||||||||
| Supply | ||||||||||||||||||||
| ||||||||||||||||||||
| Input | ||||||||||||||||||||
| ||||||||||||||||||||
| Collective error message | ||||||||||||||||||||
| ||||||||||||||||||||
| Certificate | UL 23 ATEX 3065 X | |||||||||||||||||||
| ||||||||||||||||||||
| Galvanic isolation | ||||||||||||||||||||
| ||||||||||||||||||||
| Directive conformity | ||||||||||||||||||||
| ||||||||||||||||||||
| UL approval | E106378 | |||||||
| ||||||||
| IECEx approval | ||||||||
| ||||||||
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Related Pages
Are you looking for more information? Feel free to learn more on our related pages.
Related News and Applications
Read more on news and applications related to this product.