Select Your Country
RLK28-FC-55-Z/31/116 Fire protection retroreflective sensor
Key Benefits at a Glance
- Compact fire protection photoelectric sensor for safety devices on fire barriers
- Approval in accordance with VdS Test Report FSA and externally monitored manufacture (Ü Symbol)
- Not sensitive to ambient light, even with switched energy saving lamps




Note
All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
EN
- DE
- EN
- ES
- FR
- IT
- ZH
Technical data of RLK28-FC-55-Z/31/116
Compact fire protection photoelectric sensor |
Effective detection range | 1 ... 3 m | |
Reflector distance | 1 ... 3 m | |
Threshold detection range | 3 m | |
Reference target | reflector C110-2 | |
Light source | LED | |
Light type | modulated visible red light , 660 nm | |
Diameter of the light spot | approx. 50 mm at a distance of 3 m | |
Opening angle | emitter 1.2° receiver 2° | |
Ambient light limit | 80000 Lux | |
Accessories provided | reflector C110-2 Bracket |
MTTFd | 600 a | |
Mission Time (TM) | 20 a | |
Diagnostic Coverage (DC) | 0 % |
Operation indicator | LED green | |
Function indicator | 2 LEDs yellow, light up when light beam is free, flash when falling short of the operating reserve, are off when light beam is interrupted | |
Control elements | Time adjuster , Light-on/dark-on changeover switch |
Operating voltage | UB | 12 ... 240 V AC/DC |
Power consumption | P0 | ≤ 3.5 VA |
Switching type | light/dark on, switchable (selectable, light/dark switching is only activated if the receiver has 'dark on' selected.) | |
Signal output | Relay, 1 alternator | |
Switching voltage | max. 250 V AC/DC | |
Switching current | max. 2 A | |
Switching power | DC: max. 50 W AC: max. 500 VA | |
Switching frequency | f | 25 Hz |
Response time | 20 ms | |
Timer function | ON delay (GAN), OFF delay (GAB), one shot (IAB), ON delay-one shot (GAN-IAB), ON delay-OFF delay (GAN-GAB), programmable adjustment interval 0.1 ... 10 s |
Standards | EN 60947-5-2 smoke insensitive up to 2 dB/m ( EN 54-12 ) |
Protection class | II, rated insulation voltage ≤ 250 V AC with pollution degree 1-2 according to IEC 60664-1 Output circuit insulated from control circuit in accordance with IEC 61140. Caution! The protection class 2 is only valid when the terminal compartment is closed. | |
CCC approval | Certified by China Compulsory Certification (CCC) | |
Approvals | VdS/DIBt certificate of compliance No. 25022 , approval number Z-6.510-2384 |
Ambient temperature | -40 ... 60 °C (-40 ... 140 °F) | |
Storage temperature | -40 ... 60 °C (-40 ... 140 °F) | |
Relative humidity | 30% ... 85% non-condensing ; Non-icing |
Degree of protection | IP67 | ||||||||||
Connection | terminal compartment with 8 spring-loaded terminals for wire cross section 0.5 ... 1.5 mm2, insulation stripping 7.5 ... 8.5 mm, M16 x 1.5 cable gland | ||||||||||
Material | |||||||||||
| |||||||||||
Mass | 112 g | ||||||||||
Dimensions | |||||||||||
|