FB6217E3 Digital Output
Digital output with shutdown input
Principaux avantages en un coup d'œil
- 2-channel
- Outputs Ex ia
- Installation in suitable enclosures in Zone 1
- Module can be exchanged under voltage (hot swap)
- Line fault detection (LFD)
- Positive or negative logic selectable
- Simulation mode for service operations (forcing)
- Permanently self-monitoring
- Output with watchdog
- Output with bus-independent safety shutdown
Afficher plus






Remarque
Tous les documents relatifs aux produits, tels que les certificats, les déclarations de conformité, etc., qui ont été émis avant la conversion sous le nom de Pepperl+Fuchs GmbH ou Pepperl+Fuchs AG, s'appliquent également à Pepperl+Fuchs SE.
EN
- EN
- DE
Données techniques relatives à FB6217E3
| Connection | backplane bus / booster terminals | |
| Rated voltage | Ur | 12 V DC , only in connection with the power supplies FB92** |
| Power dissipation | 1.7 W | |
| Power consumption | 2.7 W |
| Connection | backplane bus | |
| Interface | manufacturer-specific bus to standard com unit |
| Number of channels | 2 | ||||||||||
| Suitable field devices | |||||||||||
| |||||||||||
| Connection | channel I: 1+, 4/5/6/8-; channel II: 7+, 4/5/6/8- | ||||||||||
| Internal resistor | Ri | 131 Ω , both channels parallel 66 Ω | |||||||||
| Current limit | Imax | 50 mA both channels parallel 100 mA | |||||||||
| Open loop voltage | Us | 16.5 V , both channels parallel 16.5 V | |||||||||
| Line fault detection | can be switched on/off for each channel via configuration tool also when turned off (every 2.5 s the valve is turned on for 2 ms) | ||||||||||
| |||||||||||
| Response time | 10 ms (depending on bus cycle time) | ||||||||||
| Watchdog | within 0.5 s the device goes in safe state, e.g. after loss of communication | ||||||||||
| LED indication | Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (1, 2) red: line fault (lead breakage or short circuit) , yellow: state of digital I/O (0/1) Mode LED (M) white: Parallel operation of outputs | |
| Coding | optional mechanical coding via front socket |
| Electromagnetic compatibility | |||||
| |||||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Environmental test | EN 60068-2-14 | |
| Shock resistance | EN 60068-2-27 | |
| Vibration resistance | EN 60068-2-6 | |
| Damaging gas | EN 60068-2-42 | |
| Relative humidity | EN 60068-2-78 |
| Ambient temperature | -40 ... 60 °C (-40 ... 140 °F) | |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Relative humidity | 95 % non-condensing | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 |
| Degree of protection | IP20 (module) , a separate housing is required acc. to the system description | ||||||||||
| Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | ||||||||||
| Mass | approx. 420 g | ||||||||||
| Dimensions | |||||||||||
| |||||||||||
| EU-type examination certificate | Presafe 19 ATEX 14054U | ||||||||||||||||
| |||||||||||||||||
| Output | Ex ia | ||||||||||||||||
| |||||||||||||||||
| Output (both channels parallel) | |||||||||||||||||
| |||||||||||||||||
| Galvanic isolation | |||||||||||||||||
| |||||||||||||||||
| Directive conformity | |||||||||||||||||
| |||||||||||||||||
| ATEX approval | Presafe 19 ATEX 14054U | ||||
| IECEx approval | IECEx PRE 19.0009U | ||||
| |||||
| System information | The module has to be mounted in appropriate backplanes and housings (FB92**) in Zone 1, 2, 21, 22 or outside hazardous areas (gas or dust). Here, observe the corresponding EC-type examination certificate. | |
| Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |