Sélectionnez votre pays
LVL-M4-C Vibration Limit SwitchVibracon
Vibration limit switch with tube extension
Principaux avantages en un coup d'œil
- Vibration limit switch for liquids
- Device with tube extension
- Wide variety of electronic modules (e. g., relay, thyristor signal output): the right connection for every process control system
- No calibration: quick and low-cost start up
- No mechanically moving parts: maintenance-free, no wear, long operating life
- Operation via push buttons and DIP switches on the electronic insert
- Optional status and fault indication via LED module or via Bluetooth in the P+F Level app
- Up to SIL 3 acc. to IEC/EN 61508
Afficher plus



Remarque
Tous les documents relatifs aux produits, tels que les certificats, les déclarations de conformité, etc., qui ont été émis avant la conversion sous le nom de Pepperl+Fuchs GmbH ou Pepperl+Fuchs AG, s'appliquent également à Pepperl+Fuchs SE.
EN
- EN
- DE
Données techniques relatives à LVL-M4-C
| Function principle | point level detection, maximum or minimum detection for liquids | |
| Measuring method | The change in vibration frequency causes the device to switch. | |
| Construction type | device with tube extension | |
| Series | Vibracon LVL-M4 | |
| Housing | single compartment, aluminum, coated single compartment, 316L, cast single compartment, plastic dual compartment, L-shape, aluminum, coated |
| Safety Integrity Level (SIL) | SIL 3 |
| Rated voltage | Ur | electronic insert FEL61: 19 ... 253 V AC, 50/60 Hz electronic insert FEL62: 10 V DC ... 55 V DC electronic insert FEL64: 19 V AC ... 253 V AC50/60 Hz / 19 V DC ... 55 V DC electronic insert FEL64DC: 9 V DC ... 20 V DC electronic insert FEL68: switch amplifier acc. to IEC 60947-5-6 (NAMUR) |
| Current consumption | electronic insert FEL61: ≤ 3.8 mA electronic insert FEL62: ≤ 10 mA, without load | |
| Power consumption | electronic insert FEL61: ≤ 2 VA electronic insert FEL62: ≤ 0.5 W electronic insert FEL64: ≤ 25 VA/< 1.3 W electronic insert FEL64DC: < 1.0 W electronic insert FEL68: acc. to IEC 60947-5-6 (NAMUR) |
| Interface type | Bluetooth® , optional | |
| Detection range | max. 25 m | |
| Configuration | commissioning, operation and maintenance via P+F Level app - can be activated/deactivated - password encryption | |
| Communication | encrypted |
| Switching point | see section switch point | |
| Measured variable | limit level (limit value) | |
| Measuring range | depends on installation location and the tube extension maxmum sensor length : 6 m |
| Output type | electronic insert FEL61: 2-wire with test button electronic insert FEL62: 3-wire PNP with test button electronic insert FEL64: relay DPDT with test button electronic insert FEL64DC: relay DPDT with contact and test button electronic insert FEL68: 2-wire NAMUR with test button | |
| Switch behaviour | switch-over for minimum/maximum residual current safety on electronic insert MAX = maximum safety: The output switches to the power fail response when the fork is covered. for use with overspill protection for example MIN = minimum safety: The output switches to the power fail response when the fork is exposed. for use with dry running protection for example | |
| Communication | connection for LED module VU120 and Bluetooth module VU121 , optional Bluetooth wireless technology , optional |
| Electromagnetic compatibility | |||||
| |||||
| Low voltage | |||||
| |||||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 , NEMA 250 | |
| Shock resistance | IEC 60068-2-27 | |
| Vibration resistance | EN 60068-2-64 | |
| Climate class | IEC 60068-2-38 test Z/AD | |
| Corrosion resistance | acc. to ISA-71.04, severity level G3 |
| Medium density | adjustment on the electronic insert > 0,5 g/cm3 or > 0,7 g/cm3 (other on request) |
| Reference operating conditions | ambient temperature: 23 °C (73 °F) process temperature: 23 °C (73 °F) density: 1 g/cm3 (water) medium viscosity: 1 mPa·s process pressure: ambietn pressure/unpressurized sensor installation: verticaly from above density selection switch: > 0.7 g/cm3 switch direction of sensor: uncovered to covered | |
| Maximum measured error | max. ± 1 mm | |
| Hysteresis | typ. 2.5 mm | |
| Influence of medium density | see technical information (TI) | |
| Influence of medium temperature | max. +1.4 ... -2.6 mm (-50 ... 150 °C (-58 ... 302 °F)) | |
| Influence of medium pressure | max. 0 ... 2.6 mm (-1 ... 64 bar) |
| Installation conditions | |||||||||||||||||||||||
| |||||||||||||||||||||||
| Process conditions | |||||||||||||||||||||||
| |||||||||||||||||||||||
| Ambient temperature | -60 ... 70 °C (-76 ... 158 °F) For further information see technical information (TI). | |
| Storage temperature | -40 ... 80 °C (-40 ... 176 °F) | |
| Altitude | ≤ 2000 m above MSL |
| Degree of protection | plug M12 : IP66/67, NEMA type 4X Others : IP66/68, NEMA type 4X/6P | |
| Connection | gland M20 thread M20 , G1/2 , NPT1/2 , NPT3/4 plug M12 | |
| Material | see technical information (TI) | |
| Surface quality | Ra < 3.2 µm/126 µinch | |
| Mass | basic weight: 0.65 kg the basic weight comprises: - sensor (compact) - electronic insert - housing: single compartment, plastic with cover - process connection: thread, G3/4 in addition to the basic weight: - modules: 0,1 kg - housing: single compartment, aluminum, coated: 0.8 kg, single compartment, 316L: 1.21 kg, dual compartment, L-shaped, aluminum, coated: 1.22 kg - temperature spacer: 0.6 kg - pressure-tight feed through: 0.7 kg - pipe extension: 1000 mm: 0.9 kg, 100 inch: 2.3 kg - plastic protective cover: 0.2 kg For further information see technical information (TI). | |
| Dimensions | housing: diameter max. 147 mm, heigth max. 163 mm temperature spacer, pressure-tight feed through: additional length 140 mm compact version: length depends on process connection short tube version: length 99 ... 118 mm, depends on process connection pipe extension: - length 117 ... 6000 mm, 316L - length 148 ... 3000 mm, Alloy C22 tuning fork: width 17.2 mm, fork width 10 mm, length 40 mm For further information see technical information (TI). | |
| Process connection | cylindrical threads G3/4, G1 acc. to DIN ISO 228 G for installing in weld-in adapter cylindrical threads G3/4, G1 acc. to DIN ISO 228 G with flat seal conical threads NPT3/4, NPT1 acc. to ANSI B 1.20.3 conical threads R3/4, R1 acc. to EN 10226 flanges RF, RJF, FF from 1 inch acc. to ASME B16.5 flanges form A, B1, C, D, E from DN25 acc. to EN 1092-1 flanges RF from 10K 25A acc. to JIS B2220 Tri-Clamp from DN25 acc. to ISO 2852 For further information see technical information (TI). |
| EU-type examination certificate | see instruction manuals |
| CSA approval | see instruction manuals | |
| IECEx approval | see instruction manuals |
| Display elements | Standard: without display LED module VU120, optional Bluetooth module VU121, optional | |
| Control elements | switches on the electronic insert | |
| Function test | via switches on the electronic insert test magnet , optional |
| Overspill protection | see approval (ZE) |
| Supplementary documentation | technical information (TI) manuals, brief instructions (BA, KA) instruction manuals Functional safety manuals (FY) Special documentation (SD) | |
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |