Solenoid Driver KCD0-SD-Ex1.1245.SP

KCD0-SD-Ex1.1245.SP
  • 1-channel isolated barrier
  • 24 V DC supply (loop powered)
  • Current limit 45 mA at 12 V DC
  • Housing width 12.5 mm
  • Connection via spring terminals with push-in connection technology
  • Up to SIL 3 acc. to IEC/EN 61508

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

데이타 시트 발췌: 기술 사양  KCD0-SD-Ex1.1245.SP

General specifications
Signal typeDigital Output
Functional safety related parameters
Safety Integrity Level (SIL)SIL 3
Supply
Rated voltageloop powered
Power dissipation< 1 W
Input
Connection sidecontrol side
Connectionterminals 5, 6
Rated voltage19 ... 30 V DC
Current≤ 72 mA at Ui = 19 V, ≤ 50 mA at Ui = 30 V with 265 Ω output load
≤ 45 mA at Ui = 19 V, ≤ 31 mA at Ui = 30 V with shorted output
≤ 14 mA at Ui = 19 V, ≤ 11 mA at Ui = 30 V no load at output
Inrush current≤ 200 mA after 100 µs
Output
Connection sidefield side
Connectionterminals 1+, 2-
Internal resistormax. 238 Ω
Current≤ 45 mA
Voltage≥ 12 V
Open loop voltagemin. 22.7 V
Output current45 mA
Output signalThese values are valid for the rated operating voltage 19 ... 30 V DC.
Energized/De-energized delaysingle operation: typ. 1.7 ms/50 µs; periodical: typ. 5 µs/50 µs
Galvanic isolation
Input/Outputreinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff
Indicators/settings
Display elementsLED
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21
Degree of protectionIEC 60529
Protection against electrical shockUL 61010-1
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Connectionspring terminals
Massapprox. 100 g
Dimensions12.5 x 119 x 114 mm (0.5 x 4.7 x 4.5 inch) (W x H x D) , housing type A2
Height119 mm
Width12.5 mm
Depth114 mm
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificateBASEEFA 06 ATEX 0170
MarkingEx-Hexagon II (1)G [Ex ia Ga] IIC , Ex-Hexagon II (1)D [Ex ia Da] IIIC , Ex-Hexagon I (M1) [Ex ia Ma] I
Output[Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
Voltage25.2 V
Current110 mA
Power693 mW
Input
Maximum safe voltage250 V (Attention! The rated voltage can be lower.)
CertificatePF 06 CERT 0971 X
MarkingEx-Hexagon II 3G Ex nA IIC T4 Gc
Galvanic isolation
Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
FM approval
Control drawing116-0419 (cFMus)
UL approval
Control drawing116-0420 (cULus)
IECEx approval
IECEx certificateIECEx BAS 06.0032
IECEx marking[Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210101
ECLASS 12.027210190
ECLASS 11.027210190
ECLASS 10.0.127210190
ECLASS 9.027210190
ECLASS 8.027210190
ECLASS 5.127210121
ETIM 9.0EC001485
ETIM 8.0EC001485
ETIM 7.0EC001485
ETIM 6.0EC001485
ETIM 5.0EC001485
UNSPSC 12.139121008

Details: KCD0-SD-Ex1.1245.SP

Datasheet: KCD0-SD-Ex1.1245.SP

Datasheet파일 타입파일 크기
Datasheet KCD0-SD-Ex1.1245.SPPDF661 KB
Fiche de données KCD0-SD-Ex1.1245.SPPDF684 KB
Datenblatt KCD0-SD-Ex1.1245.SPPDF664 KB
Datasheet KCD0-SD-Ex1.1245.SPPDF733 KB
Hoja de datos KCD0-SD-Ex1.1245.SPPDF688 KB

Documents: KCD0-SD-Ex1.1245.SP

Manuals파일 타입파일 크기
ManualPDF3685 KB
HandbuchPDF3693 KB
Instruction manuals
ИнструкцииPDF170 KB
Instruction manual / BetriebsanleitungPDF332 KB
Návod k poużitíPDF164 KB
Instruktions manualPDF163 KB
Instruction manualPDF168 KB
KasutusjuhendPDF160 KB
KäyttöohjePDF159 KB
Manuel d'instructionsPDF166 KB
BetriebsanleitungPDF170 KB
Οδηγίες χρήσηςPDF174 KB
HandleidingPDF164 KB
Instruction manual / BetriebsanleitungPDF163 KB
Használati útmutatóPDF166 KB
Manuale di istruzioniPDF164 KB
Lietošanas pamācībaPDF163 KB
Instrukciju vadovasPDF164 KB
Instrukcja obsługiPDF166 KB
Manual de instruçõesPDF165 KB
Manual de utilizarePDF164 KB
Návod na poużitiePDF165 KB
Navodila za uporaboPDF162 KB
Manual de instruccionesPDF166 KB
ManualPDF161 KB
Technical information
Application Guideline Solenoid DriversPDF734 KB
Anwendungsbeschreibung VentilsteuerbausteinePDF737 KB
Application reports
Application Report - Energy Generation in Wastwater Treatment PlantsPDF532 KB
Application Report - Generating Electricity in Coal-Fired Power PlantsPDF412 KB
Application Report - Screening Systems in Sewage Treatment PlantsPDF577 KB
Application Report - Sicherer Brennstofftransport in KohlekraftwerkenPDF391 KB
Application Report - Water Inlet in Wastewater Treatment PlantsPDF526 KB
Applikationsbericht - Energiegewinnung in KläranlagenPDF535 KB
Applikationsbericht - Rechenanlagen in KläranlagenPDF578 KB
Applikationsbericht - Sicherer Brennstofftransport in KohlekraftwerkenPDF393 KB
Applikationsbericht - Stromerzeugung in KohlekraftwerkenPDF416 KB
Applikationsbericht - Wasserzulauf in KläranlagenPDF527 KB
Documents
Safety ManualPDF414 KB

CAD+CAE: KCD0-SD-Ex1.1245.SP

CAD파일 타입파일 크기
CAD 3-D / CAD 3-DSTP3049 KB
CAD Portal / CAD PortalLINK---

관련문서: KCD0-SD-Ex1.1245.SP

Matching System Components
Cable trunking is integrated in the mounting profile, Safe spacious separation of safe and hazardous signals, No additional cable guides necessary, Standard length 1.8 m (5.8 ft), simple to customize to application space, With mounting aidspa
Accessories
2-pin spring terminal with push-in connection technology, For KC modules of K-System, Integrated test sockets for connection of HART communicators, Packaging unit: 3 pieces green, 2 pieces bluepa
2-pin spring terminal with push-in connection technology, For KC modules of K-System, Integrated test sockets for connection of HART communicators, Packaging unit: 5 pieces bluepa
2-pin spring terminal with push-in connection technology, For KC modules of K-System, Integrated test sockets for connection of HART communicators, Packaging unit: 5 pieces greenpa
Safety Products Selector

Choose from various selection criteria like safety integrity level, performance level, device function, and signal type and find the SIL/PL assessed device that you are looking for.