Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH, also apply to Pepperl+Fuchs AG.
Ladda ned datablad som PDF::
Electrical specifications | ||
---|---|---|
Operating voltage | 250 V max. | |
Operating current | 16 A max. | |
Terminal capacity | 2.5 mm2 | |
Terminal torque | 0.8 Nm | |
Function | illuminated pushbutton | |
Color | red | |
Contact configuration | 1x NC | |
Switching diagram | PD-C147616A PD-C147697A see switching diagram overview |
|
Usage category | AC15: 20 ... 250 V AC - 10 A DC13: 20 ... 24 V DC - 1 A |
|
Number of poles | 1 | |
Operator action | spring return | |
Mechanical specifications | ||
Cable type | non-armored cables | |
Clamping range (D) | 5.5 ... 13 mm (D) | |
Covering | Protective cover fully detachable |
|
Cover fixing | Phillips head screw | |
Degree of protection | IP66 | |
Cable entry | ||
Number of cable entries | 1x M20 cable gland in protective cover | |
Material | ||
Housing | Polyamide (PA) | |
Finish | inherent color black | |
Seal | silicone | |
Washer gasket | silicone | |
Mass | 150 g max. | |
Dimensions | ||
Height (A) | 77 mm (A) | |
Width (B) | 44 mm (B) | |
Depth (C) | 105 mm (C) | |
Actuator head diameter (D2) | 39 mm (D2) | |
Panel wall thickness (PT) | 1 ... 6 mm (PT) | |
Diameter thru-hole (DT) | 30.6 mm (DT) | |
Length outside enclosure (H) | 17.5 mm (H) | |
Width across flats (SW1) | 24 mm (SW1) | |
Total length (L) | 130 mm (L) | |
Tightening torque | ||
Nut torque at enclosure (SW1) | 2 Nm (SW1) | |
Mounting | via actuator head | |
Ambient conditions | ||
Ambient temperature | -40 ... 50 °C (-40 ... 122 °F) | |
Data for application in connection with hazardous areas | ||
EU-type examination certificate | CML 16 ATEX 3106X | |
Marking | ![]() Ex de IIC T6 Gb Ex tb IIIC T80 °C Db |
|
International approvals | ||
IECEx approval | IECEx CML 16.0046X | |
Conformity | ||
Degree of protection | EN 60529 | |
Usage category | IEC / EN 60947 | |
CE marking | 0080 or 0102, see type label | |
General information | ||
Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
Instruction manuals | Language | File Type | File Size |
---|---|---|---|
Brief Instructions Panel Mount Control Units PM*.*.* | ENG | 168 KB | |
Kurzanleitung Befehls- und Meldegeräte zum Schalttafeleinbau PM*.*.* | GER | 171 KB |
Statements of compliance | Cert No. | File Type | File Size |
---|---|---|---|
EU-Declaration of Conformity / EU-Konformitätserklärung | DOC-3132A | 142 KB | |
Certificates | |||
CML IECEx Certificate of Conformity | IECEx CML 16.0046X | LINK | --- |
Europe CML ATEX Category 2 D ATEX Category 2 G | CML 16 ATEX 3106X | 123 KB |
Spotlight: Six Questions for Herbert Schober