Serviceline Industrielle Sensoren
Serviceline Explosionsschutz

Ex pxb motor purge and pressurization control unit 6100-MP-EX-*

6100-MP-EX-*
  • Certified for ATEX and IECEx Zone 1
  • Maximum flow rate of 14,000 l/min
  • Intrinsically safe user interface for programming and monitoring the system
  • Control Unit monitors system operation and controls enclosure power
  • Auxiliary contact outputs for alarm or control
  • Multiple temperature inputs for monitoring and control
  • Automatic pressure compensation for excess leakage from motor

Hinweis: Alle produktbezogenen Dokumente, wie Zertifikate, Konformitäts- oder Herstellererklärungen, die unter der Firmierung Pepperl+Fuchs GmbH oder Pepperl+Fuchs AG herausgegeben wurden, gelten auch für die Pepperl+Fuchs SE.

Vollständiges Datenblatt als PDF herunterladen:


Technische Daten  6100-MP-EX-*

Produktbeschreibung
6100 series Ex pxb motor purge and pressurization system control unit
General specifications
Operating modemanual, semi-automatic, or fully automatic - programmable
Series6100 Series
Number of volume exchanges4 to 19
Hazardous environmentgas
Supply
Rated voltage100 ... 250 V AC, 50 ... 60 Hz / 0.2 A
20 ... 30 V DC / 0.6 A
Electrical specifications
Connection
PowerEx e terminal blocks
Connection6000-ISB DIN-mounted terminal
Input
Input typeIS 1: Dedicated for 6000-TEMP-01 (optional)
IS 2: Dedicated for 6100-MP-LPP
Input 1: SRM, discrete input, Intrinsically Safe
Input 2: SRM, discrete input, Intrinsically Safe
Input 3: Dedicated for EPV-6100-MP, Flow Signal
Input 4: Dedicated high pressure switch, Max Pressure Signal (optional)
Output
Output IAUX 1
Output typeDry contacts, SPDT
Inrush current5 A
Contact loading2 A at 240 V AC resistive load
2 A at 24 V DC
Output IIAUX 2
Output typeDry contacts, SPDT
Inrush current5 A
Contact loading2 A at 240 V AC resistive load
2 A at 24 V DC
Output IIIenclosure 1 and 2
Output typeDry contacts (2) SPST, NO
Inrush current72 A
Contact loading8 A at 240 V AC / 120 V AC resistive load
8 A at 24 V DC
Indicators/settings
LED indicationSafe pressure: Blue - safe pressure is achieved
Enclosure power: Green - power on; Red - power off
Rapid exchange: Blue - purging is running
System bypass: Yellow - bypass is activated
Alarm fault: Red (blinking) - any alarm input detected; Red (solid) - fault
Pneumatic parameters
Protective gas supplyregulated and filtered air or inert gas
Pressure requirementregulated side: 1.4 ... 8.3 bar [20 ... 120 psig)
unregulated side: 4.1 ... 8.3 bar [65 ... 120 psig)
Safe pressure0.62 mbar [0.25 in wc / 6.4 mm wc] minimum for 6100-MP-LPP-*
Purge flow and enclosure pressure rate2000 l/m ... 14000 l/m
see EPV-6100 datasheet for flow rate steps
Valve flowspressurization valve: manual gate valve
purging valve: pilot drive angle seat valve
pilot valve: intrinsically safe solenoid valve
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013
RoHS
Directive 2011/65/EU (RoHS)EN 50581:2012
Ambient conditions
Ambient temperature0 ... 60 °C (32 ... 140 °F) Standard version
-20 ... 60 °C (-4 ... 140 °F) Low temp version, no regulator version
Storage temperature0 ... 80 °C (32 ... 176 °F) Standard version
-20 ... 80 °C (-4 ... 176 °F) Low temp version, no regulator version
Relative humidity5 ... 95 %, noncondensing
Vibration resistance1 g , 5 ... 100 Hz , all axes
Impact resistance30g, 11 ms, all axes
Mechanical specifications
Connection typeTerminals
Core cross sectionsee manual
Degree of protectionIP66
Cable entry3 x M16 holes, plugs that are included are not hazardous-location rated
4 x M20 holes, plugs that are included are not hazardous-location rated
Materialinlet and outlet: 1¼ inch NPTF, 316 stainless steel
internal piping: copper
bulkhead fittings: 316 stainless steel (no regulator model)
gate valve: bronze, Grafoil seals
purging valve: 316 stainless steel, PTFE seals
solenoid valve: brass
housing: 316L stainless steel
regulator: zinc (standard temp); aluminum (low temp); N/A (no regulator)
filter (pneumatic): aluminum
tubing (pneumatic): nylon
fittings (pneumatic): nickel-plated brass
Mass47.2 kg (104 lb)
Dimensions216 mm x 508 mm x 770 mm (8.5 in x 20 in x 30.3 in)
Height762 mm
Width558 mm
Depth213 mm
Data for application in connection with hazardous areas
CertificateCML 19 ATEX 1425X
MarkingEx-Hexagon II 2G Ex db eb ib [ib Gb][pxb Gb] IIC T4 Gb
Directive conformity
Directive 2014/34/EUEN IEC 60079-0:2018
EN 60079-1:2014
EN 60079-2:2014
EN 60079-7:2015
EN 60079-11:2012
International approvals
IECEx approvalIECEx CML 19.0156X
Ex db eb ib [ib Gb][pxb Gb] IIC T4 Gb
General information
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.
Supplemental Standards : EN 61010-1:2010

Klassifikationen

SystemClasscode
ECLASS 13.027180591
ECLASS 12.027180591
ECLASS 11.027180591
ECLASS 10.0.127293101
ECLASS 9.027293101
ECLASS 8.027293101
ECLASS 5.140050501
ETIM 9.0EC000243
ETIM 8.0EC000243
ETIM 7.0EC000243
ETIM 6.0EC000243
ETIM 5.0EC000243
UNSPSC 12.139121303

Details: 6100-MP-EX-*

Funktion

Das Motor-Überdruckkapselungs-/Spülsystem Bebco EPS® 6100 der Serie Ex pxb, Zone 1, besteht aus folgenden Komponenten in einem IP66-Gehäuse: Steuereinheit und Benutzerschnittstelle, eigensichere und Stromversorgungsklemmen, manuelles Druckventil und elektropneumatisches Ventil für automatische Spülung und Leckageausgleich.

Die konfigurierbare Steuereinheit verfügt über einen Temperatur- und Druckausgleich, einen zusätzlichen Ausgang für Steuerung oder Alarm, zwei wählbare eigensichere Eingänge für verschiedene Aktionen und bis zu drei Temperatursensoreingänge, die verschiedene Punkte in einem Motorgehäuse überwachen können. Die eigensichere Benutzerschnittstelle kann auch in einem separaten Gehäuse in der Nähe des Bedienpersonals installiert werden, um einen schnellen Zugriff und eine einfache Systemüberwachung zu ermöglichen. Das Überdruckkapselungs-/Spülsystem 6100 kann auch zum Spülen und Schützen großer Gehäuse verwendet werden, die einen hohen Mengenstrom erfordern.

Informative Literature: 6100-MP-EX-*

Sprachauswahl:
Zu ihrer Sprachauswahl gibt es leider keine Dokumente. Bitte wählen Sie eine andere Sprache aus.

Product Documentation: 6100-MP-EX-*

Sprachauswahl:
Product informationSpracheDateitypDateigröße
Basic Explosion Protection Compendium - Type of Protection "Purge and Pressurization"ENGPDF3860 KB
Safety and Security Documentation
ManualENGPDF6146 KB
BetriebsanleitungGERPDF233 KB
Manuals
ManualENGPDF4787 KB

Approvals: 6100-MP-EX-*

Sprachauswahl:
CertificatesKennungSpracheDateitypDateigröße
Europe CML ATEX Certificate II 2 GCML 19ATEX1425XALLPDF118 KB
IECEx Certificate of ConformityIECEx CML 19.0156XALLLINK---
UK-Type Examination CertificateCML 21UKEX1380XALLPDF127 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-B0D7BALLPDF163 KB
UK Declaration of Conformity (P+F) / UK-Konformitäterklärung (P+F)DOC-B0F6ALLPDF160 KB

Zugehörige Produkte : 6100-MP-EX-*

Accessories
pa
pa