Mobile Advanced Diagnostic Module DM-AM-KIT

DM-AM-KIT
  • Comprehensive diagnostics for the fieldbus physical layer
  • Mobile kit for the fieldbus professional
  • Precise measurements through passive circuits
  • For commissioning and troubleshooting
  • For FOUNDATION Fieldbus H1 and PROFIBUS PA
  • Installation in Zone 2/Class I, Div. 2
  • Connection to energy limited fieldbus segments Ex nL permissible
  • USB interface for PC connection and power supply

请注意:所有以Pepperl + Fuchs GmbH或Pepperl + Fuchs AG名义发行的产品相关文件,例如证书,合格声明等,同样适用于Pepperl + Fuchs SE。

下载PDF版完整参数表:


技术参数节选  DM-AM-KIT

General specifications
Design / MountingHandheld/mobile
Supply
Rated voltage20 ... 30 V
Rated current70 ... 30 mA
Power dissipation0.7 W
Fieldbus connection
Number of segments1
Fieldbus typeFOUNDATION Fieldbus/PROFIBUS PA
Rated voltage9 ... 32 V
Indicators/operating means
LED PWRgreen: Power on
LED COM ERRyellow: bus activity; red 2 Hz flashing: alarm; red: hardware error
Interface
Interface typeUSB: Square type B socket
Directive conformity
Electromagnetic compatibility
Directive 2004/108/ECEN 61326-1:2006
Standard conformity
Electromagnetic compatibilityNE 21:2006
Degree of protectionIEC 60529
Shock resistanceEN 60068-2-27
Vibration resistanceEN 60068-2-6
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Relative humidity< 95 % non-condensing
Shock resistance15 g , 11 ms
Vibration resistance1 g , 10 ... 150 Hz
Mechanical specifications
Connection typefieldbus: removable screw terminals with retaining screws
external power: removable screw terminals with retaining screws
USB: Square type B socket
Core cross section2.5 mm2
Housing materialAluminum
Degree of protectionIP20
Massdevice 100 g , Carrying case, incl. accessories 1000 g
Dimensions
Height114 mm
Width35 mm
Depth85 mm
Data for application in connection with hazardous areas
CertificateTÜV 05 ATEX 2923 X
MarkingEx-Hexagon II 3G Ex nA [nL] IIC T4
Directive conformity
Directive 94/9/ECIEC 60079-15:2003
General information
Supplementary informationStatement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027242692
ECLASS 12.027242692
ECLASS 11.027242692
ECLASS 10.0.127242692
ECLASS 9.027242692
ECLASS 8.027242692
ECLASS 5.127242692
ETIM 9.0EC001604
ETIM 8.0EC001604
ETIM 7.0EC001604
ETIM 6.0EC001604
ETIM 5.0EC001604
UNSPSC 12.139121008
Product category / 产品类的现场总线诊断模块

Details: DM-AM-KIT

Informative Literature: DM-AM-KIT

选择语言:
Literature语言文件类型文件大小
Application Report - Controlling and Monitoring liquid Helium at the Deutsches Elektronen-SynchrotronENGPDF361 KB
Application Report - Digital Communication in Steel-Plate ManufacturingENGPDF470 KB

Product Documentation: DM-AM-KIT

选择语言:
Manuals语言文件类型文件大小
ManualENGPDF1865 KB

Ethernet-APL enables continuous communication across all hierarchy levels. Learn more about the pioneering technology …

RSS Info Service for PANOS Updates

Stay informed when a new software update of PANOS, the operating system for Ethernet-APL switches, is released: With our RSS Feed you will get an email notfication in your inbox immediately after an update has been released.

From decisions to planning, installation, and commissioning up to operation and maintenance: Discover how to make the most out of your fieldbus infrastructure …