请注意:所有以Pepperl + Fuchs GmbH或Pepperl + Fuchs AG名义发行的产品相关文件,例如证书,合格声明等,同样适用于Pepperl + Fuchs SE。
下载PDF版完整参数表:
产品阐述 |
---|
6500 series Ex pxb and Ex pyb purge and pressurization system |
General specifications | ||
---|---|---|
Operating mode | user programmable | |
Series | 6500 | |
System | ||
Number of volume exchanges | 5 to 19 | |
Hazardous environment | gas, dust, gas and dust | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Rated voltage | 100 ... 240 V AC, 48 ... 62 Hz / 0.2 A 20 ... 30 V DC |
|
Electrical specifications | ||
Connection | EPCU: Terminal blocks and grounding screw UIC: 4-pin conncector and cable (provided), for the 6500-01-PM02, cable length is 5 meters Input type: intrinsically safe |
|
Interface | ||
Physical | Bluetooth® 4.1 | |
Transmitter frequency | 2.4 ... 2.4835 GHz | |
Transmitter radiated power | -19 ... 7.5 dBm | |
Sensitivity | -92.5 dBm at 0.1 % BER | |
Detection range | 100 m in air | |
Antenna | PCB | |
Communication | ||
Bluetooth | declaration ID: D037849 | |
Input | ||
Input I | Voltage free contact or namur proximity sensor | |
Input type | Intrinsically Safe, Ex ib | |
Input II | (1) 2-wire, PT100 RTD | |
Input type | Intrinsically Safe, Ex ib | |
Output | ||
Output I | AUX | |
Output type | Voltage free contact outputs, SPDT configuration | |
Inrush current | 2 A | |
Contact loading | 2 A @ 240VAC, resistive, 2 A @ 24VDC | |
Output II | Enclosure | |
Output type | Voltage free contact outputs, 2 N.O. configuration | |
Inrush current | 8 A | |
Contact loading | 8A @ 240 V AC, resistive up to 60 °C 8A @ 24 V DC up to 60 °C 5A @ 240 V AC, resistive, 60 to 70 °C 5A @ 24 V DC up to 60 to 70 °C |
|
Fuse | External fusing is required at no more than 11 amps/1500 A breaking current | |
Output III | Digital valve When used with the 6500-MAN-DV-01, intrinsically safe Internal resistance 280 Ω |
|
Output IV | Proportional valve When used with the 6500-MAN-PV-01, intrinsically safe Current: 4 to 20 mA Max. load: 300 Ω |
|
Communication | HART via RS485 (PACTware available) | |
Indicators/settings | ||
Display elements | 2x20 LCD for configuration, monitoring, and status of the 65000 system with back light and contrast selection. Capacitive touch buttons | |
LED indication | Safe pressure: Blue - safe pressure is achieved Enclosure power: Green - power on; Red - power off Rapid exchange: Blue - purging is running System bypass: Yellow - bypass is activated Alarm fault: Red (blinking) - any alarm input detected; Red (solid) - 6000 series system fault Key: green - a button on the capacitive touch display has been activated. Momentary indication |
|
Pneumatic parameters | ||
Protective gas supply | instrument grade air or inert gas | |
Pressure requirement | For 6500-MAN-DV: 1.4 to 8.3 bar (20 to 120 psig) regulated For 6500-MAN-PV: 3.5 to 6.9 bar (50 to 100 psig) regulated Note: max. pressure will depend on the vent model used. |
|
Safe pressure | Gas: 0.82 mbar (0.33 in wc) Dust: 0.82 mbar (0.33 in wc) Gas+Dust: 0.82 mbar (0.33 in wc) |
|
Valve flows | Standard vent series: EPV-6500-*-01, 03, 05 Readout on display is from 56 to 850 l/min (2 to 30 scfm) in increments of 28l/min (1 scfm). Minimum and maximum reading depending on type of vent and supply pressure. See datasheet for EPV-6500 series vent. Continuous (Dilution) vent series: EPV-6500-*-07, 08 Readout on display is from 17 to 226 l/min (0.6 to 8 scfm) continuous reading. Maximum reading depending on type of vent and supply pressure. See datasheet for EPV-6500 series vent. |
|
Ambient conditions | ||
Ambient temperature | -20 ... 70 °C (-4 ... 158 °F) | |
Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
Relative humidity | 5 ... 85 %, non-condensing | |
Vibration resistance | 5 ... 100 Hz , 1 g, 12 m/s2, all axes | |
Impact resistance | 30 g, 11 ms, all axes | |
Mechanical specifications | ||
Connection type | See mounting in 6500 manual and cable gland requirements | |
Cable gland | Cable gland requirement: cable glands are not included. Customer can supply their own approved glands or use one of the 6500-CBLG-... cable gland kits. I.S.cable glands: requires (5) M12 approved cable glands Power cable glands: requires (2) M16 and (2) M12 approved cable glands |
|
Degree of protection | IP66 | |
Material | UIC display: Makrolon FI cover and A380 Aluminum anodized casing Housing: 316L stainless steel Hardware: 316L stainless steel |
|
Mass | approx. 5 kg (11.0 lbs) | |
Dimensions | 6500-01-EXT1: 150 x 150 x 145 mm (5.9" x 5.9" x 5.7") 6500-01-PM01: 150 x 150 x 185 mm (5.9" x 5.9" x 7.3") 6500-01-PM02: EPCU: 150 x 150 x 145 mm (5.9" x 5.9" x 5.7"), UIC: 150 x 150 x 45 mm (5.9" x 5.9" x 1.8") |
|
Height | 367.5 mm | |
Width | 183 mm | |
Depth | 152.5 mm | |
Data for application in connection with hazardous areas | ||
Certificate | DEMKO 16 ATEX 1640X | |
Directive conformity | ||
Directive 2014/34/EU | EN IEC 60079-0:2018 , EN 60079-2:2014 , EN 60079-5:2015 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012 , EN 60079-31:2014 | |
International approvals | ||
IECEx approval | IECEx UL 16.0003X | |
General information | ||
Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
System | Classcode |
---|---|
ECLASS 13.0 | 27180508 |
ECLASS 12.0 | 27180508 |
ECLASS 11.0 | 27180508 |
ECLASS 10.0.1 | 27180508 |
ECLASS 9.0 | 27180508 |
ECLASS 8.0 | 27180508 |
ECLASS 5.1 | 40050501 |
ETIM 9.0 | EC000243 |
ETIM 8.0 | EC000243 |
ETIM 7.0 | EC000243 |
ETIM 6.0 | EC000243 |
ETIM 5.0 | EC000243 |
UNSPSC 12.1 | 39121301 |
Product category / 产品类的 |
Literature | 语言 | 文件类型 | 文件大小 |
---|---|---|---|
Application Report - Hydrogen Analysis with Reliable Explosion Protection | ENG | 253 KB | |
Application Report - Label Printer Solution for Zone 1/21 and Zone 2/22 Applications | ENG | 135 KB | |
Application Report - Purge and Pressurization Solutions on FPSO Tankers | ENG | 351 KB |
Product information | 语言 | 文件类型 | 文件大小 |
---|---|---|---|
Basic Explosion Protection Compendium - Type of Protection "Purge and Pressurization" | ENG | 3860 KB | |
Brief Instructions | |||
Purge & Pressurization Smart App - Users Guide / Purge & Pressurization Smart App - Users Guide | ALL | 1771 KB | |
Safety and Security Documentation | |||
Instruction manual / Betriebsanleitung | CHS | 343 KB | |
Manual | ENG | 1625 KB | |
Manuals | |||
Manual | ENG | 8336 KB |
CAD | 语言 | 文件类型 | 文件大小 |
---|---|---|---|
2D / DXF Files for 6500 Series - external mount / CAD 2-D | ALL | ZIP | 258 KB |
CAD 2-D / CAD 2-D | ALL | ZIP | 1308 KB |
3D files for 6500 Series / 3-D-Modell für Serie 6500 | ALL | STP | 25244 KB |
Certificates | 证书号码 | 语言 | 文件类型 | 文件大小 |
---|---|---|---|---|
ATEX Certificate | DEMKO 16 ATEX 1640X | ALL | 488 KB | |
Bluetooth SIG Radio Approval | D037849 | ALL | LINK | --- |
China SITIIAS CCC Ex Certificate | 2020322304002485 (Katy, TX USA) | ALL | 1673 KB | |
IECEx Certificate of Conformity | IECEx UL 16.0003X | ALL | LINK | --- |
Korea KOSHA | 16-AV4BO-0186X | ALL | 1013 KB | |
UK-Type Examination Certificate | UL21UKEX2017X | ALL | 267 KB | |
Worldwide exida Functional Safety Certificate | P+F 1601040 P0006 C016 V1R1 | ALL | 124 KB | |
Declaration of Conformity | ||||
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F) | DOC-B080C | ALL | 160 KB | |
UK Declaration of Conformity (P+F) / UK-Konformitäterklärung (P+F) | DOC-B0F7 | ALL | 156 KB |
Device Description Files/Drivers | Release Info | 文件类型 | 文件大小 |
---|---|---|---|
DTM for 6500 Series / DTM_a | ZIP | 21548 KB |
Accessories | ||||||
---|---|---|---|---|---|---|
|