Serviceline Industrial Sensors
Serviceline Explosion Protection
暂不可售
暂不可售

Interface NVOR-200

NVOR-200
  • Interface between warning device and smoke detector
  • Approved for zone 0
  • Easy installation on DIN rail

请注意:所有以Pepperl + Fuchs GmbH或Pepperl + Fuchs AG名义发行的产品相关文件,例如证书,合格声明等,同样适用于Pepperl + Fuchs SE。

技术参数节选  NVOR-200

Indicators/operating means
Control elementsRESET button: reset of the alarm at the smoke detector
Input
Connectionterminal 7
Output
Connectionterminal 6
Directive conformity
Electromagnetic compatibility
Directive 89/336/EECEN 61000-6-2 , EN 61000-6-3
Conformity
Galvanic isolationEN 50178
Degree of protectionIEC 60529
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Massapprox. 200 g
Dimensions36 x 86 x 58 mm (1.4 x 3.4 x 2.3 inch)
Height86 mm
Width36 mm
Length58 mm
MountingDIN rail, system M36
Data for application in connection with hazardous areas
EU-type examination certificateDEMKO 07 ATEX 142591
MarkingEx-Hexagon II 1G Ex ia IIB
OutputEx ia IIB
Voltage21 V
Voltage21 V
Current90 mA
Current300 mA
Power0.24 W
Power1.55 W
External capacitance0.6 µF
External inductance0.5 mH
Directive conformity
Directive 94/9/ECEN 50014, EN 50020, EN 60079-14
General information
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027230191
ECLASS 12.027279090
ECLASS 11.027279090
ECLASS 10.0.127279090
ECLASS 9.027279090
ECLASS 8.027279290
ECLASS 5.127279290
ETIM 9.0EC003619
ETIM 8.0EC003619
ETIM 7.0EC003619
ETIM 6.0EC001447
ETIM 5.0EC001447
UNSPSC 12.141111954
Product category / 产品类的

Details: NVOR-200

Datasheet: NVOR-200

Datasheet文件类型文件大小
Datasheet NVOR-200PDF219 KB
Datenblatt NVOR-200PDF220 KB

Documents: NVOR-200

Manuals文件类型文件大小
Operating instructions NVOR-200 / Betriebsanleitung NVOR-200PDF1723 KB