Support Industrielle sensorer
Support Explosion Protection

Strain Gauge Converter KFD2-WAC2-Ex1.D

KFD2-WAC2-Ex1.D
  • 1-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • Strain gauge input (full or half bridge)
  • Output 0 mA ... ± 20 mA or 0 V ... ± 10 V
  • 2 relay contact outputs
  • Programmable high/low alarm
  • Configurable by PACTware or keypad
  • RS-485 interface
  • Line fault detection (LFD)

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Hent hele databladet som PDF:


Uddrag af datablad: Tekniske data for   KFD2-WAC2-Ex1.D

General specifications
Signal typeAnalog input
Supply
ConnectionPower Rail or terminals 23+, 24-
Rated voltage20 ... 35 V DC
Ripplewithin the supply tolerance
Power consumptionmax. 3 W
Interface
ConnectionPower Rail or terminals 19+, 20 GND, 21-
TypeRS-485
Programming interfaceprogramming socket
Field circuit
Connectionterminals 1+, 2-, 3+, 4-, 5+, 6-
Lead resistancemax. 25 Ω per line
Input I
Connectionterminals 1+, 2-
Sensor supply1 ... 5 V
Connectionterminals 3+, 4- (supply); 5+, 6- (signal)
Short-circuit current50 mA
Load≥ 116 Ω up to 5V, ≥ 85 Ω up to 4V
Input
Connection sidefield side
ConnectionInput I: terminals 1+, 2-; Input II: terminals 13+, 14-; Input III: terminals 15+, 14-
Programmable Tare0 ... 500 % of span
Input ISignal, analog
Input signal-100 ... 100 mV
Input resistance> 1 MΩ for voltage measurement
Input II, IIItare adjustment, calibration and zero
Open circuit voltage/short-circuit current18 V / 5 mA
Active/PassiveI > 4 mA/I < 1.5 mA
Output
Connection sidecontrol side
ConnectionOutput I: terminals 10, 11, 12; Output II: terminals 16, 17, 18; Output III: terminals 7-, 8+, 9-
Output I, IIRelay output
Contact loading253 V AC/2 A/500 VA/cos φ min. 0.7; 40 V DC/2 A resistive load
Mechanical life2 x 107 switching cycles
Output IIIAnalog output
Current range-20 ... 20 mA
Loadmax. 550 Ω
Analog voltage output0 ... ± 10 V; output resistance 500 Ω (bridge between terminal 7 and 9)
Analog current output0 ... ± 20 mA or 4 ... 20 mA; load 0 ... 550 Ω (terminals 7 and 8)
Line fault detectiondownscale -21.5 mA (-10.75 V) or 2 mA (1 V), upscale 21.5 mA (10.75 V)
Collective error messagePower Rail
Transfer characteristics
Deviation
Resolution/accuracy≤ ± 0.05 % incl. non-linearity and hysteresis
Temperature effect ≤ ± 0.01 %/K
Reaction time300 ... 850 ms
Galvanic isolation
Input I/other circuitsreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output I, II against eachotherreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output I, II/other circuitsreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output III/Input II, IIInot available
Output III/Programming socketnot available
Other circuits from each otherfunctional insulation, rated insulation voltage 50 Veff
Indicators/settings
Display elementsLEDs , display
Control elementsControl panel
Configurationvia operating buttons
via PACTware
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Low voltage
Directive 2014/35/EUEN 61010-1:2010
Conformity
Electromagnetic compatibilityNE 21:2006
Degree of protectionIEC 60529:2001
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Massapprox. 250 g
Dimensions40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) (W x H x D) , housing type C2
Height119 mm
Width40 mm
Depth115 mm
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificateTÜV 04 ATEX 2531
MarkingEx-Hexagon II (1)G [Ex ia Ga] IIC
Ex-Hexagon II (1)D [Ex ia Da] IIIC
Ex-Hexagon I (M1) [Ex ia Ma] I
SupplyPower Rail or terminals 23+, 24- non-intrinsically safe
Maximum safe voltage40 V DC (Attention! Um is no rated voltage.)
Input Iterminals 1+, 2- Ex ia IIC, Ex iaD
Voltage Uo14 V
Current Io238 mA
Power Po833 mW (linear characteristic)
Input II and IIIterminals 13+, 14-; 15+, 14- non-intrinsically safe
Maximum safe voltage Um40 V DC (Attention! Um is no rated voltage.)
Output I, IIterminals 10, 11, 12; 16, 17, 18 non-intrinsically safe
Maximum safe voltage253 V AC / 40 V DC (Attention! Um is no rated voltage.)
Contact loading253 V AC/2 A/500 VA/cos φ min. 0.7; 40 V DC/2 A resistive load
Output IIIterminals 7-, 8+, 9- non-intrinsically safe
Maximum safe voltage Um40 V DC (Attention! Um is no rated voltage.)
InterfaceRS 485 programming jack
Maximum safe voltage40 V DC (Attention! Um is no rated voltage.)
Galvanic isolation
Input I/other circuitssafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-11:2012
International approvals
FM approval
Control drawing116-0302 (cFMus)
UL approvalE223772
IECEx approval
IECEx certificateIECEx TUN 06.0005
IECEx marking[Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210125
ECLASS 12.027210125
ECLASS 11.027210125
ECLASS 10.0.127210125
ECLASS 9.027210125
ECLASS 8.027210125
ECLASS 5.127210107
ETIM 9.0EC002477
ETIM 8.0EC002477
ETIM 7.0EC002477
ETIM 6.0EC002477
ETIM 5.0EC001485
UNSPSC 12.132101514

Details: KFD2-WAC2-Ex1.D

Informative Literature: KFD2-WAC2-Ex1.D

Language Selection:
LiteratureSprogFil typeFil størrelse
Application Report - Energy Generation in Wastwater Treatment PlantsENGPDF532 KB
Application Report - Generating Electricity in Coal-Fired Power PlantsENGPDF412 KB
Application Report - Screening Systems in Sewage Treatment PlantsENGPDF577 KB
Application Report - Sicherer Brennstofftransport in KohlekraftwerkenENGPDF391 KB
Application Report - Water Inlet in Wastewater Treatment PlantsENGPDF526 KB

Product Documentation: KFD2-WAC2-Ex1.D

Language Selection:
Brief InstructionsSprogFil typeFil størrelse
Operator card KF**-WAC2-**1.D / Bedienkarte KF**-WAC2-**1.DALLPDF928 KB
Safety and Security Documentation
Instruktions manualDANPDF167 KB
Manuals
Manual KF**-WAC2-(Ex)1.DENGPDF1799 KB
ManualENGPDF3685 KB
Installation and configuration guide Device Type Manager (DTM)ENGPDF8665 KB

Design / Simulation: KFD2-WAC2-Ex1.D

Language Selection:
CADSprogFil typeFil størrelse
CAD 3-D / CAD 3-DALLSTP2722 KB
CAD Portal / CAD PortalALLLINK---
CAE
CAE EPLAN Data Portal / CAE EPLAN Data PortalALLLINK---
EPLAN macro EDZ / EPLAN Makro EDZALLEDZ68 KB

Approvals: KFD2-WAC2-Ex1.D

Language Selection:
CertificatesCertifikat nr.SprogFil typeFil størrelse
Australia Test SafeANZEx 22.3012ALLPDF199 KB
Canada FMFM 18 CA 0121XALLPDF290 KB
China SITIIAS CCC Ex Certificate2021322316004119 (Singapore)ALLPDF1086 KB
Europe TUV Nord ATEX Category (1) D ATEX Category (M1) ATEX Category (1) GTÜV 04 ATEX 2531ALLPDF384 KB
Korea KOSHA19-AV4BO-0392ALLPDF120 KB
South Africa MASCMASC MS/17-0878ALLPDF721 KB
USA Canada UL cULus Hazardous Location UL E223772 ULCoC 20200622 - E223772 RepRef 20071210ALLPDF82 KB
USA FMFM 18 US 0254XALLPDF290 KB
United Kingdom CML UK-Type Examination Certificate UKEX Category (1) D UKEX Category (1) G UKEX Category (M1)CML 22UKEX2504ALLPDF138 KB
Worldwide TUV Nord IECEx Certificate of ConformityIECEx TUN 06.0005ALLLINK---
Control Drawings
Control drawing FM / Control drawing FM   ALLPDF38 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-0647DALLPDF54 KB

Software: KFD2-WAC2-Ex1.D

Language Selection:
Device Description Files/DriversUdgivelses infoFil typeFil størrelse
DTM Collection Interface Technology 2 / DTM Collection Interface Technology 21.4.110.77ZIP---
Software Tools
PACTware 4.1 SP6 / PACTware 4.1 SP64.1.0.53ZIP43327 KB
PACTware 5.0 / PACTware 5.05.0.5.31ZIP44203 KB
PACTware 6.X / PACTware 6.X6.1ZIP335938 KB

Tilhørende produkter: KFD2-WAC2-Ex1.D

Matching System Components

Interface for Power Rail, Supply current ≤ 4 A, Replaceable fuse, Relay contact output, reversible, LED status indicationpa

35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 2 m (6 foot), simple to customize to application space, Eliminates daisy-chainspa

35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 0.8 m (2.6 ft), simple to customize to application space, Eliminates daisy-chainspa
Device DTM, For K-, E- and H-System, Frame application, like e. g. PACTware, must be installed separatelypa
Universal DTM host platform, For all DTMs of Pepperl+Fuchs, Approved FDT/DTM technology, Free of charge, Download from Pepperl+Fuchs websitepa
Isolated USB interface cable, Used with K-, E- and H-System devices, Used with PACTwarepa
35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 1.6 m (5 foot), simple to customize to application space, Eliminates daisy-chainspa
Cable trunking is integrated in the mounting profile, Safe spacious separation of safe and hazardous signals, No additional cable guides necessary, Standard length 1.8 m (5.8 ft), simple to customize to application space, With mounting aidspa
Cable trunking with integrated Power Rail UPR-03, Safe spacious separation of safe and hazardous signals, No additional cable guides necessary, Provides DC supply voltage to all equipped K-System modules, Standard length 1.8 m (5.8 ft), simple to customize to application space, With end caps UPR-E, cover and mounting aidspa
Universal DTM host platform, For all DTMs of Pepperl+Fuchs, Approved FDT/DTM technology, Free of charge, Download from Pepperl+Fuchs websitepa
Accessories
3-pin screw terminal, For KF modules of K-System, Packaging unit: 5 pieces greenpa
3-pin screw terminal, For KF modules of K-System, Packaging unit: 5 pieces bluepa
Coding of K-System terminal blocks, Coding of LB/FB-System front sockets, Packaging unit: 20 x 6 coding pinspa
Safety Products Selector

Choose from various selection criteria like safety integrity level, performance level, device function, and signal type and find the SIL/PL assessed device that you are looking for.