Support Industrielle sensorer
Support Explosion Protection

Inductive sensor NJ20-40-N

NJ20-40-N
  • 20 mm non-flush


NAMUR sensors must be operated with approved switch amplifiers. Please find suitable devices below:

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Uddrag af datablad: Tekniske data for   NJ20-40-N

General specifications
Switching functionNormally closed (NC)
Output typeNAMUR
Rated operating distance20 mm
Installationnon-flush
Assured operating distance0 ... 16.2 mm
Reduction factor rAl 0.4
Reduction factor rCu 0.3
Reduction factor r304 0.85
Output type2-wire
Nominal ratings
Nominal voltage8.2 V (Ri approx. 1 kΩ)
Switching frequency0 ... 100 Hz
Current consumption
Measuring plate not detectedmin. 3 mA
Measuring plate detected≤ 1 mA
Functional safety related parameters
MTTFd11400 a
Mission Time (TM)20 a
Diagnostic Coverage (DC)0 %
Compliance with standards and directives
Standard conformity
NAMUREN 60947-5-6:2000
IEC 60947-5-6:1999
StandardsEN 60947-5-2:2007
EN 60947-5-2/A1:2012
IEC 60947-5-2:2007
IEC 60947-5-2 AMD 1:2012
Approvals and certificates
IECEx approval
Equipment protection level GbIECEx PTB 11.0037X
Equipment protection level DaIECEx PTB 11.0037X
Equipment protection level MbIECEx PTB 11.0037X
ATEX approval
Equipment protection level GbPTB 00 ATEX 2048 X
Equipment protection level DaPTB 00 ATEX 2048 X
UL approvalcULus Listed, General Purpose
CCC approval
Hazardous Location2020322315002258
NEPSI approval
NEPSI certificateGYJ16.1393X
CML approvalon request
ANZEx18.3018X
Ambient conditions
Ambient temperature-25 ... 100 °C (-13 ... 212 °F)
Mechanical specifications
Connection typeterminal compartment
Core cross sectionup to 2.5 mm2
Housing materialPBT
Sensing facePBT
Degree of protectionIP67
Dimensions
Length95 mm
Diameter40 mm
General information
Use in the hazardous areasee instruction manuals

Classifications

SystemClasscode
ECLASS 13.027274001
ECLASS 12.027274001
ECLASS 11.027270101
ECLASS 10.0.127270101
ECLASS 9.027270101
ECLASS 8.027270101
ECLASS 5.127270101
ETIM 9.0EC002714
ETIM 8.0EC002714
ETIM 7.0EC002714
ETIM 6.0EC002714
ETIM 5.0EC002714
UNSPSC 12.139121550

Details: NJ20-40-N

Datasheet: NJ20-40-N

DatasheetFil typeFil størrelse
Datasheet NJ20-40-NPDF573 KB
Datasheet NJ20-40-NPDF569 KB
Fiche de données NJ20-40-NPDF569 KB
Datenblatt NJ20-40-NPDF570 KB
Scheda tecnica NJ20-40-NPDF569 KB
Datasheet NJ20-40-NPDF575 KB
Folha de dados NJ20-40-NPDF570 KB
Hoja de datos NJ20-40-NPDF569 KB
Datasheet NJ20-40-NPDF583 KB

Documents: NJ20-40-N

Instruction manualsFil typeFil størrelse
ИнструкцииPDF187 KB
Návod k poużitíPDF179 KB
Instruktions manualPDF177 KB
Instruction manualPDF179 KB
KasutusjuhendPDF173 KB
KäyttöohjePDF172 KB
Manuel d'instructionsPDF182 KB
BetriebsanleitungPDF179 KB
Οδηγίες χρήσηςPDF189 KB
HandleidingPDF178 KB
Instruction manual / BetriebsanleitungPDF177 KB
Használati útmutatóPDF181 KB
Manuale di istruzioniPDF179 KB
Lietošanas pamācībaPDF178 KB
Instrukciju vadovasPDF180 KB
Instrukcja obsługiPDF240 KB
Manual de instruçõesPDF181 KB
Manual de utilizarePDF182 KB
Návod na poużitiePDF180 KB
Navodila za uporaboPDF176 KB
Manual de instruccionesPDF181 KB
ManualPDF176 KB

CAD+CAE: NJ20-40-N

CADFil typeFil størrelse
CAD 3-D / CAD 3-DSTP182 KB
CAD Portal / CAD PortalLINK---
EPLAN
CAE EPLAN Data Portal / CAE EPLAN Data PortalLINK---
EPLAN macro EDZ / EPLAN Makro EDZEDZ61 KB

Tilhørende produkter: NJ20-40-N

Accessories
Mounting flange, 40 mmfa

Our amplify article gives interesting insights about the development of the new, modern portfolio of inductive proximity sensors from Pepperl+Fuchs. Get the whole story here! 

 

 

Knowledge Base for Inductive Sensors

The knowledge base for inductive sensors contains extensive expertise and supports you in the highly precise and smooth operation of the sensors in your machinery and plants.

VariKont with Active Shielding Technology

The VariKont inductive sensors with Active Shielding Technology ensure high switching distances, no matter the installation situation and the surrounding material. Benefit from easier equipment design and reduced costs!

Inductive Safety Sensors SIL 2 PL d

As the SIL 2/PL d inductive safety sensors have no dead band, data transfer can occur with no minimum distance between sensor and target. Discover the optimized portfolio for demanding environments.