VBA-2E-KE5-IJL/UJL AS-Interface analog module
Ventajas clave de un vistazo
- Housing with push-in connection technology and mechanically coded terminal blocks
- Housing width 19 mm, installation in the switch cabinet on DIN mounting rail
- Sensors can be supplied either from the AS-Interface or external auxiliary voltage, as preferred
- Function indicator for the bus, external auxiliary voltage, internal sensor supply, and inputs




Nota
Todos los documentos relacionados con los productos, como certificados, declaraciones de conformidad, etc., que se emitieron antes de la conversión con el nombre de Pepperl+Fuchs GmbH o Pepperl+Fuchs AG también se aplican a Pepperl+Fuchs SE.
EN
- EN
- DE
- FR
Hoja de datosFunciónClasificaciónProduct DocumentationDesign / SimulationHomologacionesProductos relacionados
Datos técnicos de VBA-2E-KE5-IJL/UJL
Switch cabinet module, 2 analog Inputs |
Node type | Standard node | |
AS-Interface specification | V3.0 | |
Required gateway specification | ≥ V2.1 | |
UL File Number | E223772 | |
MTBF | 154 a |
LED FAULT | Fault indication: red LED Red: communication error or address is 0 Red flashing: peripheral fault | |
LED INT | Internal input supply active; LED green | |
LED PWR | AS-Interface voltage; green LED Green: voltage OK Flashing green: address 0 or peripheral error | |
LED AUX | ext. auxiliary voltage UAUX; dual LED green/red green: voltage OK red: reverse voltage | |
LED IN | status of input signal; LED yellow off: not active on: signal within measuring range flashing: signal outside of measuring range |
Auxiliary voltage (output) | UAUX | 20 ... 30 V DC PELV |
Rated operating voltage | Ue | 26.5 ... 31.6 V from AS-Interface |
Rated operating current | Ie | ≤ 70 mA (without sensors) / max. 200 mA |
Protection class | III | |
Current consumption | IAUX ≤ 650 mA | |
Surge protection | UAUX, Ue: overvoltage category II, safe isolated power supplies (PELV) |
Number/Type | 2 analog inputs Current: 0 ... 20 mA/4 ... 20 mA voltage: 0 ... 10 V | |
Supply | From AS-Interface (switch setting INT, default setting) or from auxiliary voltage UAUX (switch setting AUX) | |
Current loading capacity | ≤ 100 mA from AS-Interface; overload and short-circuit resistant ≤ 600 mA From auxiliary voltage UAUX (AUX switch position) , overload and short-circuit protected | |
Input resistance | current input: max. 70 Ω voltage input: 100 kΩ | |
Accuracy | 0.1 % of input signal range at 25 °C (298 K) | |
Resolution | 15 Bit | |
Temperature influence | 0.0025 %/K of input signal range |
Temperature influence | 1 µA/K or 0,3 mV/K |
Electromagnetic compatibility | |||||
|
Degree of protection | EN 60529:2000 | |
Fieldbus standard | EN 62026-2:2013 | |
Emitted interference | EN 61000-6-4:2007 | |
AS-Interface | EN 62026-2:2013 | |
Noise immunity | EN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013 |
Profile | S-7.3.D | |||||||||||||
IO code | 7 | |||||||||||||
ID code | 3 | |||||||||||||
ID1 code | F | |||||||||||||
ID2 code | D | |||||||||||||
Data bits (function via AS-Interface) | The transfer of the data value is based on AS-Interface Profile 7.3. | |||||||||||||
Parameter bits (programmable via AS-i) | function | |||||||||||||
|
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
Relative humidity | 85 % , noncondensing | |
Climatic conditions | For indoor use only | |
Altitude | ≤ 2000 m above MSL | |
Shock and impact resistance | 15 g, 11 ms in 6 spatial directions, 3 shocks 10 g, 16 ms in 6 spatial directions, 1000 shocks | |
Vibration resistance | 0.35 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles | |
Pollution degree | 2 |
Degree of protection | IP20 | ||||||||||
Connection | Removable push-in terminals rated connection capacity: rigid: 0.20 mm2 ... 1.5 mm2 flexible (without wire end ferrule): 0.20 mm2 ... 2.5 mm2 flexible (with wire end ferrule): 0.25 mm2 ... 1.5 mm2 | ||||||||||
Material | |||||||||||
| |||||||||||
Mass | 110 g | ||||||||||
Dimensions | |||||||||||
| |||||||||||
Mounting | DIN mounting rail | ||||||||||
Note | Max. length of jumpers = 5 cm |