Select Your Country
KFD2-SH-Ex1.T.OP Switch Amplifier
Key Benefits at a Glance
- 1-channel isolated barrier
- 24 V DC supply (Power Rail)
- Input for approved dry contacts or SN/S1N sensors
- Active voltage output
- Relay contact output
- Fault indication output
- Line fault detection (LFD)
- Up to SIL 3 acc. to IEC/EN 61508
- Up to PL d acc. to EN/ISO 13849
Show more
Preferred Type











Note
All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
EN
- EN
- DE
- ES
- FR
- PL
Technical data of KFD2-SH-Ex1.T.OP
| Signal type | Digital Input |
| Safety Integrity Level (SIL) | SIL 3 | |
| Systematic capability (SC) | SC 3 | |
| Performance level (PL) | PL d |
| Connection | Power Rail or terminals 14+, 15- | |
| Rated voltage | Ur | 20 ... 30 V DC |
| Ripple | ≤ 10 % | |
| Rated current | Ir | ≤ 100 mA |
| Power dissipation | 1.5 W | |
| Power consumption | max. 1.7 W |
| Connection side | field side | |||||||
| Connection | terminals 4+, 6- | |||||||
| Open circuit voltage/short-circuit current | approx. 8.4 V DC / approx. 11.7 mA | |||||||
| Lead resistance | max. 50 Ω , cable capacitances and inductances must be observed in hazardous areas | |||||||
| Switching point | ||||||||
| ||||||||
| Response delay | ≤ 1 ms | |||||||
| Connection side | control side | |||||||
| Connection | output I: terminals 7+, 8- ; output II: terminals 9, 10 ; output III: terminals 11, 12 | |||||||
| Output I | active voltage output, short-circuit proof 0-signal: 0 V 1-signal: 19 V DC at 15 mA ... 31 V DC at no-load fault: 0 V | |||||||
| Output II | relay | |||||||
| ||||||||
| Output III | relay , fault signal | |||||||
| ||||||||
| Switching frequency | |||||||||||
| |||||||||||
| Display elements | LEDs | |
| Labeling | space for labeling at the front |
| Electromagnetic compatibility | |||||
| |||||
| Machinery Directive | |||||
| |||||
| Electromagnetic compatibility | NE 21:2017 , EN 61326-3-2:2008 | |
| Degree of protection | IEC 60529:2001 | |
| Safety | IEC/EN 61508:2010 |
| Ambient temperature | -20 ... 70 °C (-4 ... 158 °F) extended ambient temperature range up to 70 °C (158 °F) , refer to manual and derating characteristics in the datasheet for necessary mounting conditions |
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Mass | approx. 150 g | |
| Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
| EU-type examination certificate | PTB 00 ATEX 2041 | ||||||||||||||||
| |||||||||||||||||
| Supply | |||||||||||||||||
| |||||||||||||||||
| Output | |||||||||||||||||
| |||||||||||||||||
| Certificate | TÜV 99 ATEX 1493 X | ||||||||||||||||
| |||||||||||||||||
| Galvanic isolation | |||||||||||||||||
| |||||||||||||||||
| Directive conformity | |||||||||||||||||
| |||||||||||||||||
| IECEx approval | ||||||||
| ||||||||
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |