選擇您所在的國家/地區
KFD2-STC5-Ex1 SMART Transmitter Power Supply
主要优势一览
- 1-channel isolated barrier
- 24 V DC supply (Power Rail)
- Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources
- Output 4 mA ... 20 mA current sink/current source
- Terminals with test points
- Up to SIL 2 acc. to IEC/EN 61508
显示详情






注意
在轉換前以Pepperl+Fuchs GmbH或Pepperl+Fuchs AG名義發布的所有產品相關文件(如證書、符合性聲明等)也適用於Pepperl+Fuchs SE。
EN
- EN
- DE
- ES
- FR
- PL
KFD2-STC5-Ex1 技術數據
| Signal type | Analog input |
| Safety Integrity Level (SIL) | SIL 2 |
| Connection | Power Rail or terminals 14+, 15- | |
| Rated voltage | Ur | 18 ... 30 V DC |
| Ripple | within the supply tolerance | |
| Power dissipation | ≤ 1 W at maximum load | |
| Power consumption | ≤ 1.6 W at maximum load |
| Connection side | field side | |
| Connection | terminals 1+, 2-, 3 | |
| Input signal | 4 ... 20 mA | |
| Open circuit voltage/short-circuit current | terminals 1+, 3: 23 V / 25 mA | |
| Input resistance | max. 265 Ω terminals 2-, 3 , max. 330 Ω terminals 1+, 3 | |
| Available voltage | ≥ 16 V at 20 mA ; ≥ 20 V at 4 mA , terminals 1+, 3 |
| Connection side | control side | |
| Connection | terminals 7+, 8-, 9- (sink) terminals 7-, 8+, 9+ (source) see additional information | |
| Load | 0 ... 800 Ω | |
| Output signal | 4 ... 20 mA (overload > 25 mA) | |
| Ripple | max. 50 µA rms | |
| External supply (loop) | 2 ... 30 V DC If the external voltage is > 19 V, a load ≥ ((V - 19) / 0.02) Ω is required. V represents the value of the external voltage. The internal 250 Ω resistor at terminal 9 can be used as a load. |
| Deviation | at 20 °C (68 °F), 4 ... 20 mA ≤ 10 µA incl. calibration, linearity, hysteresis, loads and fluctuations of supply voltage | ||||
| |||||
| Frequency range | field side into the control side: bandwidth with 0.5 Vpp signal 0 ... 7.5 kHz (-3 dB) control side into the field side: bandwidth with 0.5 Vpp signal 0.3 ... 7.5 kHz (-3 dB) | ||||
| Settling time | 500 µs | ||||
| Rise time/fall time | 100 µs | ||||
| Output/power supply | functional insulation, rated insulation voltage 50 V AC |
| Display elements | LED | |
| Labeling | space for labeling at the front |
| Electromagnetic compatibility | |||||
| |||||
| Electromagnetic compatibility | NE 21:2012 EN 61326-3-2:2008 | |
| Degree of protection | IEC 60529:2001 | |
| Protection against electrical shock | UL 61010-1:2012 |
| Ambient temperature | -20 ... 70 °C (-4 ... 158 °F) |
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Mass | approx. 150 g | |
| Dimensions | 20 x 124 x 115 mm (0.8 x 4.9 x 4.5 inch) (W x H x D) , housing type B2 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
| EU-type examination certificate | CML 17 ATEX 2029X | |||||||||||||||||||
| ||||||||||||||||||||
| Supply | ||||||||||||||||||||
| ||||||||||||||||||||
| Equipment | terminals 1+, 3- | |||||||||||||||||||
| ||||||||||||||||||||
| Equipment | terminals 2-, 3 | |||||||||||||||||||
| ||||||||||||||||||||
| Equipment | terminals 1+, 2 / 3- | |||||||||||||||||||
| ||||||||||||||||||||
| Certificate | CML 17 ATEX 3028X | |||||||||||||||||||
| ||||||||||||||||||||
| Galvanic isolation | ||||||||||||||||||||
| ||||||||||||||||||||
| Directive conformity | ||||||||||||||||||||
| ||||||||||||||||||||
| UL approval | E106378 | |||||||
| ||||||||
| IECEx approval | ||||||||
| ||||||||
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
相關頁面