選擇您所在的國家/地區

轉至全球網站

ICA-16DIO-G16-IO I/O hub

带 IO-Link 接口的 I/O 集线器,用于 16 路可自由配置的数字输入/输出

主要优势一览

  • IO-Link A 类
  • IO-Link 1.1.4
  • 用于开关状态和故障指示的 LED
  • 通过 IO-Link 配置和控制
  • 由 IO-Link 供电
  • 可配置 16 路数字输入/输出

显示详情

Product Compliance: Europe – CE
Product Compliance: USA - cULus
IO-Link interface
注意

在轉換前以Pepperl+Fuchs GmbH或Pepperl+Fuchs AG名義發布的所有產品相關文件(如證書、符合性聲明等)也適用於Pepperl+Fuchs SE。

EN
  • EN
  • DE
  • FR

ICA-16DIO-G16-IO 技術數據

MTBF134 a
LED PWRLED green: flashing with short break (1 Hz) - IO-Link mode
LED IOSwitch state (IO); multicolor LED
yellow: only IO pin 4 is active
blue: only IO pin 2 is active
green: both IO pin 4 and pin 2 are active
red: overload at sensor supply or output
Operating voltageUB18 ... 30 V DC, PELV
No-load supply currentI0≤ 30 mA
Operating currentIBTotal current of all inputs/outputs max. 3A (limited by fuse)
Interface typeIO-Link
IO-Link revision1.1
Device profileIdentification and Diagnosis - I&D
Firmware update
Process dataInputs 3 Byte
- Input signals 16 Bit
- diagnosis signals 5 Bit
Outputs 2 Byte
- Output signals 16 Bit
Vendor ID1 (0x0001)
Device ID985858 (0x0F0B02)
Data transfer rateCOM3 (230.4 kbits/s)
Min. cycle time1 ms
SIO mode supportno
Compatible master port typeClass A
Number/Type16 Inputs for 3-wire sensors (PNP), DC (IO1 ... IO16)
Supplyfrom IO-Link
Current loading capacity180 mA , overload and short-circuit protected
Input current≤ 5 mA (limited internally)
Switching pointType 3 according to IEC 61131-2
Number/Type16 electronic outputs, PNP (IO1 … IO16), overload-proof and short-circuit-proof
Supplyfrom IO-Link
Voltage≥ (UB - 1.5 V)
Current180 mA per output
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013
EN 55011:2016
Degree of protectionEN 60529:2000
InputEN 61131-2:2007
Communication interfaceIEC 61131-9 / IO-Link V1.1.4
Emitted interferenceEN 61000-6-4:2007
Noise immunityEN 61000-6-2:2005, EN 61326-1:2006
UL approvalE223772
Power limitation by fuse in accordance with UL248-1, UL248-14, rated current 3 A.
Protection of the personnel and the plant is not ensured if the product is not being used according to its intended use.
Load specification DC General Use / DC Pilot Duty
Degree of protection not tested by UL; tested by Pepperl+Fuchs SE
Units shall be connected using CYJV or PVVA cord having suitable ratings min.50 V, min 4 A, min. 100 °C.
The product must be installed in accordance with local laws.
The device shall be installed on non-flammable, straight surface.
Ambient temperature-25 ... 70 °C (-13 ... 158 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Relative humidity85 % non-condensing
Climatic conditionsFor indoor use only
Altitude≤ 5000 m above MSL
Shock and impact resistance30 g, 11 ms in 6 spatial directions, 3 shocks 10 g, 16 ms in 6 spatial directions, 1000 shocks
Vibration resistance0.35 mm / 5 g 5 ... 500 Hz
Pollution degree3
Degree of protectionIP67 / IP68 / IP69k
ConnectionIO-Link: M12 round plug connector in accordance with EN 61076-2-101, LM type (4-pin, connector contacts, screw-locking, A-coded)
Female connector: LF type or similar
IO: M8 round plug connector in accordance with EN 61076-2-104, LF type (4-pin, bushing contacts, screw-locking, A-coded)
Mating connector: LM type or similar
Material
HousingPBT
Mass110 g
Tightening torque, cable gland0.4 Nm (M12 connector),
0.2 Nm (M8 connector)
Dimensions
Height29.35 mm
Width30 mm
Length143 mm
Diameter
Mountingscrew mounting
產品目錄