選擇您所在的國家/地區

轉至全球網站

ICA-16DI-G11-IO I/O hub

带 IO-Link 接口的 I/O 集线器,用于 16 路数字输入

主要优势一览

  • 服务和过程数据 IO-link 接口
  • 16 路数字输入
  • 可以为每个端口配置逻辑电平
  • 可以根据端口配置滤波时间
  • 可以为每个端口配置脉冲扩展

显示详情

Product Compliance: Europe – CE
Product Compliance: USA - cULus
IO-Link interface
注意

在轉換前以Pepperl+Fuchs GmbH或Pepperl+Fuchs AG名義發布的所有產品相關文件(如證書、符合性聲明等)也適用於Pepperl+Fuchs SE。

EN
  • EN
  • DE
  • FR

ICA-16DI-G11-IO 技術數據

MTBF189 a
LED PWRLED green: flashing with short break (1 Hz) - IO-Link mode
LED PSwitch state (IN); multicolor LED
yellow: only IN pin 4 is active
blue: only IN pin 2 is active
green: both IN pin 4 and pin 2 are active
red: overload at sensor supply
Operating voltageUB18 ... 30 V DC, PELV
No-load supply currentI0≤ 30 mA
Operating currentIBTotal current of all inputs max. 3A (limited by fuse)
Interface typeIO-Link
IO-Link revision1.1
Device profileIdentification and Diagnosis - I&D
Firmware update
Process dataInputs 3 Byte
- Input signals 16 Bit
- diagnosis signals 5 Bit
Vendor ID1 (0x0001)
Device ID985601 (0x0F0A01)
Data transfer rateCOM3 (230.4 kbits/s)
Min. cycle time1 ms
SIO mode supportno
Compatible master port typeClass A
Number/Type16 Inputs for 3-wire sensors (PNP), DC (P1 ... P8)
Supplyfrom IO-Link
Current loading capacity180 mA , overload and short-circuit protected
Input current≤ 5 mA (limited internally)
Switching pointType 3 according to IEC 61131-2
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013
EN 55011:2016
Degree of protectionEN 60529:2000
InputEN 61131-2:2007
Communication interfaceIEC 61131-9 / IO-Link V1.1.4
Emitted interferenceEN 61000-6-4:2007
Noise immunityEN 61000-6-2:2005, EN 61326-1:2006
UL approvalE223772
Power limitation by fuse in accordance with UL248-1, UL248-14, rated current 3 A.
Protection of the personnel and the plant is not ensured if the product is not being used according to its intended use.
Load specification DC General Use / DC Pilot Duty
Degree of protection not tested by UL; tested by Pepperl+Fuchs SE
Units shall be connected using CYJV or PVVA cord having suitable ratings min.50 V, min 4 A, min. 100 °C.
The product must be installed in accordance with local laws.
Ambient temperature-25 ... 70 °C (-13 ... 158 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Relative humidity85 % non-condensing
Climatic conditionsFor indoor use only
Altitude≤ 5000 m above MSL
Shock and impact resistance30 g, 11 ms in 6 spatial directions, 3 shocks 10 g, 16 ms in 6 spatial directions, 1000 shocks
Vibration resistance0.35 mm / 5 g 5 ... 500 Hz
Pollution degree3
Degree of protectionIP68 / IP69K
ConnectionIO-Link: M12 round plug connector in accordance with EN 61076-2-101, LM type (4-pin, connector contacts, screw-locking, A-coded)
Female connector: LF type or similar
P: M12 round plug connector in accordance with EN 61076-2-101, LF type (4-pin, socket contacts, screw-locking, A-coded)
Mating connector: LM type or similar
Material
HousingPBT PC
Mounting screwStainless steel 1.4305 / AISI 303
Mass200 g
Tightening torque, housing screws1.8 Nm
Tightening torque, cable gland0.4 Nm
Dimensions
Height46 mm
Diameter85 mm
Connectionheight 11 mm
Construction typeField housing
MountingMounting plate
產品目錄