LB8105* Com Unit
Com unit for PROFIBUS DP/DP-V2
主要优势一览
- Interface between the I/O modules and the PCS/PLC
- Com unit for 80 analog or 184 digital channels
- Communication via PROFIBUS DP
- Mounting in Zone 2, Class I/Div.2 or in the safe area
- HART communication via PROFIBUS DP V1 or service bus
- Configuration via FDT 1.2 DTM
- Non-volatile memory for configuration and parameter settings
- Self configuration in redundant systems
- Permanently self-monitoring
- Outputs drive to safe state in case of failures
- Module can be exchanged under voltage
显示详情






注意
在轉換前以Pepperl+Fuchs GmbH或Pepperl+Fuchs AG名義發布的所有產品相關文件(如證書、符合性聲明等)也適用於Pepperl+Fuchs SE。
EN
- EN
- DE
LB8105* 技術數據
| Connection | backplane bus | |
| Rated voltage | Ur | 5 V DC , only in connection with the power supplies LB9*** |
| Power consumption | 2 W |
| Fieldbus type | PROFIBUS DP/DP-V1 | ||||||||||
| PROFIBUS DP | |||||||||||
| |||||||||||
| Number of stations per bus line | max. 125 (PROFIBUS), max. 119 (service bus) | ||||||||||
| Cyclic process data | 240 bytes in total, either input or output data | ||||||||||
| Number of stations per bus segment | max. 31 (RS-485 standard) | ||||||||||
| Number of repeaters between Master and Slave | max. 3 | ||||||||||
| Supported I/O modules | all LB remote I/O modules | ||||||||||
| Bus length | max. 1000 m (FOL, 1.5 MBaud), max. 1000 m (copper cable, 187.5 kBd), max. 200 m (copper cable, 1.5 MBd) | ||||||||||
| Addressing | via configuration software | ||||||||||
| PROFIBUS address | 0 ... 126 (factory standard setting: 126) | ||||||||||
| GSE file | CGV61710.gsd/gse | ||||||||||
| HART communication | via PROFIBUS or service bus | ||||||||||
| Connection | backplane bus | |
| Redundancy | via backplane |
| LED indication | LED 1 (power supply): On = operating, fast flash = cold start, slow flash = HCIR loading active LED 2 (collective alarm): On = internal fault, flashing = no PROFIBUS connection LED 3 (status process bus): flashing = PROFIBUS receive channel active LED 4 (status service bus): flashing = service bus receive channel active LED 5 (operating mode): flashing 1 (1:1 ratio) = active, normal operation; flashing 2 (7:1 ratio) = active, simulation LED 6 (status process bus): flashing = PROFIBUS response channel active LED 7 (status servicebus): flashing = service bus response channel active |
| Electromagnetic compatibility | |||||
| |||||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Fieldbus standard | IEC 61158-2 | |
| Environmental test | EN 60068-2-14 | |
| Shock resistance | EN 60068-2-27 | |
| Vibration resistance | EN 60068-2-6 | |
| Damaging gas | EN 60068-2-42 | |
| Relative humidity | EN 60068-2-56 |
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Relative humidity | 95 % non-condensing | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 |
| Degree of protection | IP20 (module) , mounted on backplane | |
| Connection | via backplane | |
| Mass | approx. 120 g | |
| Dimensions | 32.5 x 100 x 102 mm (1.28 x 3.9 x 4 inch) |
| Certificate | PF 08 CERT 1234 X | ||||
| |||||
| Directive conformity | |||||
| |||||
| ATEX approval | PF 08 CERT 1234 X | |||||||||||||
| UL approval | E106378 | |||||||||||||
| ||||||||||||||
| IECEx approval | BVS 09.0037X | |||||||||||||
| ||||||||||||||
| EAC approval | Russia: RU C-IT.MIII06.B.00129 | |||||||||||||
| Marine approval | ||||||||||||||
| ||||||||||||||
| System information | The module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity. For use in hazardous areas (e. g. Zone 2, Zone 22 or Div. 2) the module must be installed in an appropriate enclosure. | |
| Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |