選擇您所在的國家/地區
LB9006C Power Supply
主要优势一览
- Power supply for 24 V
- Permits vertical or horizontal mounting in Zone 2
- Use three power supplies for redundancy
- Galvanic isolation to mains
- Supply of I/O modules and com units
- Mounting in Zone 2, Class I/Div.2 or in the safe area
显示详情






注意
在轉換前以Pepperl+Fuchs GmbH或Pepperl+Fuchs AG名義發布的所有產品相關文件(如證書、符合性聲明等)也適用於Pepperl+Fuchs SE。
EN
- EN
- DE
LB9006C 技術數據
| Bus coupler | 2 | |
| I/O modules | >12, depending on the type |
| Maximum safe voltage Um | 60 V DC (SELV/PELV) | |
| Input voltage range | U | 18 ... 32 V DC (SELV/PELV) |
| Power dissipation | approx. 15 % of power consumption | |
| Power consumption | max. 30 W for Zone 2 applications max. 45 W for applications in safe area parallel connection with other LB9006C (autom. power sharing) | |
| Inrush current | 1.5 A (10 ms) |
| Voltage | 5.4 V DC +/- 5% , 12 V DC + 4/- 2% | |
| Power | P5V ≤ 5.4 W, P12V ≤ 25 W - P5V for Zone 2 applications P5V ≤ 5.4 W, P12V ≤ 39 W - P5V for applications in safe area |
| LED indication | Power LED (P) green: OFF in case of loss of 24 V or 12 V or 5 V |
| Electromagnetic compatibility | |||||
| |||||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Environmental test | EN 60068-2-14 | |
| Shock resistance | EN 60068-2-27 | |
| Vibration resistance | EN 60068-2-6 | |
| Damaging gas | EN 60068-2-42 | |
| Relative humidity | EN 60068-2-78 |
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Relative humidity | 95 % non-condensing | |
| Altitude | max. 2000 m | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 |
| Degree of protection | IP20 (module) , mounted on backplane | ||||||||||
| Mass | approx. 220 g | ||||||||||
| Dimensions | |||||||||||
| |||||||||||
| Certificate | PF 08 CERT 1234 X | ||||
| |||||
| Galvanic isolation | |||||
| |||||
| Directive conformity | |||||
| |||||
| ATEX approval | PF 08 CERT 1234 X | |||||||
| UL approval | E106378 | |||||||
| IECEx approval | ||||||||
| ||||||||
| System information | The module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity. For use in hazardous areas (e. g. Zone 2, Zone 22 or Div. 2) the module must be installed in an appropriate enclosure. | |
| Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
相關頁面
您是否想查看更多資訊?請隨時通過相關頁面了解更多內容。
