選擇您所在的國家/地區
S1SD-1AI-1U.3 Millivolt Converter
主要优势一览
- 1-channel signal conditioner
- 24 V DC supply
- Input bipolar millivolt sources
- Output bipolar current and voltage sources
- Accuracy 0.1 %
- Configurable via DIP switches and potentiometer
- Connection via screw terminals
显示详情






注意
在轉換前以Pepperl+Fuchs GmbH或Pepperl+Fuchs AG名義發布的所有產品相關文件(如證書、符合性聲明等)也適用於Pepperl+Fuchs SE。
EN
- EN
- DE
- ES
- FR
- PL
S1SD-1AI-1U.3 技術數據
| Signal type | Analog input | |
| Operation time | MTBF: 495 a acc. to SN 29500 stationary continuous operating, average ambient temperature 40 °C (104 °F) |
| Connection | Power Bus or terminals 1-, 2+ | |
| Rated voltage | Ur | 16.8 ... 31.2 V DC |
| Power dissipation | 0.6 W | |
| Power consumption | 0.8 W |
| Connection side | field side | |
| Connection | terminals 5+, 6- | |
| Input signal | ±60 mV, ±100 mV, ±150 mV, ±250 mV, ±300 mV, ±500 mV | |
| Input resistance | ≥ 100 kΩ | |
| Transmission range | linearity range: unipolar -1 ... 110 % bipolar -110 ... 110 % |
| Connection side | control side | |
| Connection | terminals 3-, 4+ | |
| Analog voltage output | 0/1 ... 5 V , 0/2 ... 10 V , ± 5 V, ± 10 V , load ≥ 2 kΩ | |
| Analog current output | 0/4 ... 20 mA, ± 10 mA, ± 20 mA, load ≤ 600 Ω | |
| Ripple | ≤ 10 mV eff |
| Accuracy | max. 0.1 % of full-scale value | |
| Influence of ambient temperature | < 100 ppm/K of full-scale value | |
| Frequency range | 0 ... 100 Hz , 0 ... 8 kHz | |
| Settling time | 7 ms , 150 µs |
| Output/power supply | safe electrical isolation by reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff test voltage 3 kV, 50 Hz, 1 min | |
| Input/Other circuits | safe electrical isolation by reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff test voltage 3 kV, 50 Hz, 1 min |
| Control elements | DIP switch potentiometer | |
| Configuration | via DIP switches via potentiometer | |
| Labeling | space for labeling at the front |
| Electromagnetic compatibility | |||||
| |||||
| Degree of protection | IEC 60529:2001 | |
| Protection against electrical shock | EN 61010-1:2010 |
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 |
| Degree of protection | IP20 | ||||||||||
| Connection | screw terminals | ||||||||||
| Core cross section | 0.5 ... 2.5 mm2 (20 ... 14 AWG) | ||||||||||
| Mass | approx. 70 g | ||||||||||
| Dimensions | 6.2 x 97 x 107 mm (0.24 x 3.82 x 4.21 inch) (W x H x D) , housing type S1 | ||||||||||
| |||||||||||
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | ||||||||||
| Certificate | DEMKO 16 ATEX 1750X | ||||
| |||||
| Directive conformity | |||||
| |||||
| UL approval | E106378 | |||||||
| IECEx approval | ||||||||
| ||||||||
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
相關頁面