選擇您所在的國家/地區
KFD0-CC-Ex1 Current/Voltage Converter
主要优势一览
- 1-channel isolated barrier
- 24 V DC supply (loop powered)
- Current or voltage input
- Output: 4 ... 20 mA
- Potentiometer or DIP switch selectable ranges
- Line fault detection (LFD)
显示详情






注意
在轉換前以Pepperl+Fuchs GmbH或Pepperl+Fuchs AG名義發布的所有產品相關文件(如證書、符合性聲明等)也適用於Pepperl+Fuchs SE。
EN
- EN
- DE
- ES
- FR
- PL
KFD0-CC-Ex1 技術數據
| Signal type | Analog input |
| Rated voltage | Ur | 12 ... 35 V DC loop powered |
| Power dissipation | 0.4 W |
| Connection side | field side | |
| Connection | terminals 1+, 2- | |
| Current range | 0 ... 20 mA , load ≤ 50 Ω | |
| Voltage range | 0 ... 10 V , load ≥ 100 kΩ |
| Connection side | control side | |
| Connection | terminals 9+, 8- | |
| Load | (U -12 V) / 0.02 A | |
| Current output | 4 ... 20 mA , limited to ≤ 35 mA | |
| Fault signal | downscaling ≤ 3 mA |
| Deviation | ||||||||||||||
| ||||||||||||||
| Rise time | 250 ms | |||||||||||||
| Input/Output | safe isolation according to EN 50178, rated insulation voltage 253 Veff |
| Control elements | DIP switch potentiometer | |
| Configuration | via DIP switches via potentiometer | |
| Labeling | space for labeling at the front |
| Electromagnetic compatibility | |||||
| |||||
| Galvanic isolation | EN 50178:1997 | |
| Degree of protection | IEC 60529:2001 |
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
| Degree of protection | IP20 | ||||||||||
| Connection | screw terminals | ||||||||||
| Mass | approx. 100 g | ||||||||||
| Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2 | ||||||||||
| |||||||||||
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | ||||||||||
| EU-type examination certificate | ZELM 00 ATEX 0034 | ||||||||||||||||
| |||||||||||||||||
| Output | |||||||||||||||||
| |||||||||||||||||
| Certificate | TÜV 01 ATEX 1777 X | ||||||||||||||||
| |||||||||||||||||
| Galvanic isolation | |||||||||||||||||
| |||||||||||||||||
| Directive conformity | |||||||||||||||||
| |||||||||||||||||
| CSA approval | |||||
| |||||
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |