back-up fuse : B characteristic: 16 A B characteristic: 10 A C characteristic: 6 A
Failure override time
> 75 ms / 230 V AC ; 5 ms / 115 V AC
Connection
terminals 4+, 6-
Current
0 ... 4 A , Power Rail limiting by means of fuse 4 AT , electron. limitation typ. 4.6 A
Output current
max. 4 A
Output voltage
24 V DC
Ripple
< 100 mV ss
Efficiency
typ. 87 %
Voltage limitation
< 28 V DC
Power supply/Output
for 253 V AC design insulation voltage
Display elements
LED
Labeling
space for labeling at the front
Electromagnetic compatibility
Directive 2014/30/EU
EN 55011:2009+A1:2010 , EN 61000-3-2:2014 , EN 61000-3-3:2013 , EN 61000-6-1:2007 , EN 61000-6-2:2005 , EN 61000-6-3:2007+A1:2011 , EN 61000-6-4:2007+A1:2011
Low voltage
Directive 2014/35/EU
EN 61010-1:2010
Degree of protection
IEC 60529:2001
Ambient temperature
-20 ... 60 °C (-4 ... 140 °F)
Degree of protection
IP20
Connection
self-opening connection terminals
Core cross section
max. 2 x 2.5 mm2
Mass
approx. 800 g
Dimensions
140 x 101 x 114 mm (5.5 x 4.0 x 4.5 inch) (W x H x D)
Height
101 mm
Width
140 mm
Depth
114 mm
Mounting
on 35 mm DIN mounting rail acc. to EN 60715:2001
Supplementary information
Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.