Serviceline Industrial Sensors
Serviceline Explosion Protection

暂不可售

暂不可售
暂不可售

Ultrasonic sensor UC10000-F260-IE8R2-Y235155

UC10000-F260-IE8R2-Y235155
  • Large sensing range
  • Adjustable Bracket
  • Programmable by means of Interface (see accessories) and SONPROG
  • 1 analog output, 0-20 mA current source
  • 2 switch outputs
  • Synchronization options
  • Temperature compensation

请注意:所有以Pepperl + Fuchs GmbH或Pepperl + Fuchs AG名义发行的产品相关文件,例如证书,合格声明等,同样适用于Pepperl + Fuchs SE。

技术参数节选  UC10000-F260-IE8R2-Y235155

产品阐述
Single head system
General specifications
Sensing range800 ... 10000 mm
Adjustment range800 ... 10000 mm
Dead band0 ... 800 mm
Standard target plate100 mm x 100 mm
Transducer frequencyapprox. 60 kHz
Nominal ratings
Time delay before availability280 ms
Limit data
Permissible cable lengthmax. 300 m
Indicators/operating means
LED yellowsolid: switching state switch output
flashing: misadjustment
Electrical specifications
Rated operating voltage24 V DC
Operating voltage15 ... 30 V (including ripple)
In supply voltage interval 15 ... 20 V sensitivity reduced to 20% ... 0%
Ripple≤ 10 %
No-load supply current≤ 75 mA
Input/Output
Input/output type1 synchronization connection, bidirectional
0 Level≤ 3 V
1 Level15 ... 30 V
Input impedancetyp. 0.9 kΩ
Number of sensorsmax. 10
Switching output
Output type2 switch outputs PNP, NO
Repeat accuracy± 15 mm
Operating current300 mA , short-circuit/overload protected
Voltage drop≤ 3 V
Switch-on delay800 ms
Analog output
Output type1 current output 0 ... 20 mA rising ramp  
Default setting800 ... 10000 mm
Linearity error≤ 1.5 %
Load resistor≤ 300 Ω
Compliance with standards and directives
Standard conformity
StandardsEN 60947-5-2:2007+A1:2012
IEC 60947-5-2:2007 + A1:2012
EN 60947-5-7:2003
IEC 60947-5-7:2003
Approvals and certificates
UL approvalcULus Listed, General Purpose
CSA approvalcCSAus Listed, General Purpose
Ambient conditions
Ambient temperature-25 ... 70 °C (-13 ... 158 °F)
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Shock resistance30 g , 11 ms period
Vibration resistance10 ... 55 Hz , Amplitude ± 1 mm
Mechanical specifications
Connection typescrew terminals , PG 13.5 cable gland
Degree of protectionIP65
Material
HousingUP 1225 SF/R8
Transducerepoxy resin/hollow glass sphere mixture; polyurethane foam
Installation positionany position
Mass1800 g
Dimensions
Depth112 mm
Diameter160 mm

Classifications

SystemClasscode
ECLASS 13.027272803
ECLASS 12.027272803
ECLASS 11.027272803
ECLASS 10.0.127272803
ECLASS 9.027272803
ECLASS 8.027272803
ECLASS 5.127272803
ETIM 9.0EC001849
ETIM 8.0EC001849
ETIM 7.0EC001849
ETIM 6.0EC001849
ETIM 5.0EC001849
UNSPSC 12.141111960
Product category / 产品类的

Details: UC10000-F260-IE8R2-Y235155

Datasheet: UC10000-F260-IE8R2-Y235155

Datasheet文件类型文件大小
Datasheet UC10000-F260-IE8R2-Y235155PDF409 KB
Fiche de données UC10000-F260-IE8R2-Y235155PDF423 KB
Datenblatt UC10000-F260-IE8R2-Y235155PDF418 KB
Hoja de datos UC10000-F260-IE8R2-Y235155PDF433 KB

CAD+CAE: UC10000-F260-IE8R2-Y235155

CAD文件类型文件大小
CAD 3-D / CAD 3-DSTP229 KB

Approvals+Certificates: UC10000-F260-IE8R2-Y235155

Certificates文件类型文件大小
Canada USA CSA Ordinary LocationPDF99 KB
Canada USA UL Ordinary LocationLINK---

配套产品: UC10000-F260-IE8R2-Y235155

Accessories
Male cordset single-ended M12 straight A-coded, 5-pin, PVC cable greyfa
USi-safety Sensor System