Support Industrielle sensorer
Support Explosion Protection

Temperature Multi-Input Device for Cabinet Installation RD0-TI-Ex8.FF.*

RD0-TI-Ex8.FF.*
  • For 8 temperature or analog sensors
  • Installation in Zone 1/Div. 1, intrinsically safe
  • Sensors in Zone 0/Div. 1
  • Connection to fieldbus acc. to FISCO or Entity
  • For FOUNDATION Fieldbus H1
  • PCS integration via device description and function blocks
  • Concentrator method for simplified configuration
  • Monitors sensor condition
  • For T/C, RTD 2-, 3-, 4-wire, voltage and resistance
  • Cold junction compensation
  • Removable terminals

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Uddrag af datablad: Tekniske data for   RD0-TI-Ex8.FF.*

General specifications
Design / MountingCabinet installation
Fieldbus connection
Fieldbus typeFOUNDATION Fieldbus
Physical layer profileprofile type 511 (FISCO), profile type 111 (Entity)
ITK version6.2.0 (DEV_REV 02)
Implementationresource block1x RS
function block8x AI, 1x MAI
transducer block8x sensor TB, 1x concentrator TB
Execution timeAI, MAI 40 ms max.
Macro cycletypical for one device 8xAI or 1xMAI max. 500 ms
Firmware updatevia separate plug connection
FDE (Fault Disconnect Equipment)6.7 mA
Polaritynot polarity sensitive
Rated voltage9 ... 32 V
Rated currentmax. 23 mA
Indicators/operating means
LED PWRgreen: on, bus voltage existent
LED COM ERRred, continuous lightning: hardware error; red, flashing: no bus activities or bus fault; off: no error
LED CHANNEL ERRORred: 2 Hz flashing: lead breakage, overrange; off: no error
Input
Number8
Sensor typessee table 1
Groundinggrounding of thermoelements possible
Error detectionlead breakage, wiring error, hardware device error
Common mode voltageInput to Input 600 Vpeak
Transfer characteristics
Deviation
Cold junction compensation± 0.5 °C (32.9 °F)
Resolution/accuracysee table 2
Influence of ambient temperaturesee table 3
LinearizationT/C input 0.1°C RTD input 0.03°C
Internal measurement cyclefor all sensor types max. 1 s
Galvanic isolation
Fieldbus/inputssafe galvanic isolation acc. to EN 60079-11, voltage peak value 375 V
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013
Standard conformity
Galvanic isolationEN 60079-11
Electromagnetic compatibilityNE 21:2011
Degree of protectionIEC 60529
Fieldbus standardIEC 61158-2
Shock resistanceEN 60068-2-27
Vibration resistanceEN 60068-2-6
Ambient conditions
Ambient temperature-40 ... 70 °C (-40 ... 158 °F) hazardous area
-40 ... 85 °C (-40 ... 185 °F) safe area
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Relative humidity≤ 95 % non-condensing
Shock resistance15 g , 11 ms
Vibration resistance5 g , 10 ... 150 Hz
Corrosion resistanceacc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Connection typeplug-in terminals , spring terminal and screw terminal
Core cross-section
Busup to 2.5 mm2
Inputsup to 2.5 mm2
Housing materialPolycarbonate
Degree of protectionIP20
Mass360 g
Mountingmounting on DIN rail in cabinet
Data for application in connection with hazardous areas
EU-type examination certificatePTB 03 ATEX 2237
MarkingEx-Hexagon II 2 (1) G Ex ia [ia Ga] IIC T4 Gb , Ex-Hexagon II (1) G [Ex ia Ga] IIC , Ex-Hexagon II (1) D [Ex ia Da] IIIC , Ex-Hexagon II 3 G Ex ic IIC T4 Gc
BusFISCO see EC-Type Examination Certificate
Inputssee EC-Type Examination Certificate
CertificatePTB 03 ATEX 2238 X
MarkingEx-Hexagon II 3 G Ex nA IIC T4 Gc
Galvanic isolation
Bussee Statement of Conformity
Inputsee EC-Type Examination Certificate
Directive conformity
Directive 2014/34/EUEN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
IECEx approvalIECEx PTB 05.0001 , IECEx PTB 05.0002X
Approved forEx ia [ia Ga] IIC T4 Gb , [Ex ia Ga] IIC , [Ex ia Da] IIIC , Ex ic IIC T4 Gc , Ex nA IIC T4 Gc
Certificates and approvals
Marine approvalDNV A-14038
General information
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027242610
ECLASS 12.027242610
ECLASS 11.027242610
ECLASS 10.0.127242610
ECLASS 9.027242610
ECLASS 8.027242610
ECLASS 5.127242610
ETIM 9.0EC001601
ETIM 8.0EC001601
ETIM 7.0EC001601
ETIM 6.0EC001601
ETIM 5.0EC001604
UNSPSC 12.139121008

Details: RD0-TI-Ex8.FF.*

Datasheet: RD0-TI-Ex8.FF.*

DatasheetFil typeFil størrelse
Datasheet RD0-TI-Ex8.FF.*PDF704 KB
Datenblatt RD0-TI-Ex8.FF.*PDF733 KB

Documents: RD0-TI-Ex8.FF.*

ManualsFil typeFil størrelse
Manual from 6.2.0 (DEV_REV 02)PDF1769 KB
Manual until 4.51PDF664 KB
Manual from 6.2.0 (DEV_REV 02) / Handbuch ab 6.2.0 (DEV_REV 02)PDF4870 KB
Manual until 4.51PDF855 KB
Instruction manuals
ИнструкцииPDF235 KB
Instruction manual / BetriebsanleitungPDF339 KB
Návod k poużitíPDF230 KB
Instruktions manualPDF228 KB
Instruction manualPDF235 KB
KasutusjuhendPDF225 KB
KäyttöohjePDF224 KB
Manuel d'instructionsPDF232 KB
BetriebsanleitungPDF234 KB
Οδηγίες χρήσηςPDF239 KB
HandleidingPDF228 KB
Instruction manual / BetriebsanleitungPDF228 KB
Használati útmutatóPDF230 KB
Manuale di istruzioniPDF228 KB
Lietošanas pamācībaPDF228 KB
Instrukciju vadovasPDF230 KB
Instrukcja obsługiPDF231 KB
Manual de instruçõesPDF230 KB
Manual de utilizarePDF229 KB
Návod na poużitiePDF230 KB
Navodila za uporaboPDF228 KB
Manual de instruccionesPDF229 KB
ManualPDF227 KB
Application reports
Application Report - Controlling and Monitoring liquid Helium at the Deutsches Elektronen-SynchrotronPDF361 KB
Application Report - Digital Communication in Steel-Plate ManufacturingPDF470 KB
Application Report - Installation-Ready Solution Replaces LEPIU SystemsPDF228 KB
Applikationsbericht - Digitale Kommunikation in der Produktion von GrobblechenPDF473 KB
Applikationsbericht - Steuerung und Überwachung der Kälteanlagen im Deutschen Elektronen-SynchrotronPDF643 KB
Applikationsbericht - Vorinstallierte Lösung ersetzt LEPIU-SystemePDF232 KB

CAD+CAE: RD0-TI-Ex8.FF.*

CADFil typeFil størrelse
CAD 3-D / CAD 3-DSTP8801 KB

Tilhørende produkter: RD0-TI-Ex8.FF.*

Matching System Components
For 8 temperature or analog sensors, Installation in Zone 1/Div. 1, intrinsically safe, Sensors in Zone 0/Div. 1, Connection to fieldbus acc. to FISCO or Entity, For FOUNDATION Fieldbus H1, IECEx approval, Dust protection, International, Europe, USA, Canada, Device coupler location: non-explosion hazardous area
Zone 2 - high-power trunk
Zone 1 - high-power trunk
Division 2 - high-power trunk
Division 1 - high-power trunk, Device coupler location [2]: Zone 2 - high-power trunkpa
8 channel universal temperature interface, Glass fiber reinforced polyester, impact resistant, IP66, Configurable cable entries for bus lines and field signal lines, International approvals, For FOUNDATION Fieldbus H1, Device coupler location: non-explosion hazardous area
Zone 2 - high-power trunk
Zone 1 - high-power trunk
Zone 1/2 - intrinsically safe high-power trunk
Zone 1 - intrinsically safe trunk, Device coupler location [2]: Zone 2 - high-power trunkpa
8 channel universal temperature interface, Stainless steel, electropolished, IP66, Configurable cable entries for bus lines and field signal lines, International approvals, For FOUNDATION Fieldbus H1, Device coupler location: non-explosion hazardous area
Zone 2 - high-power trunk
Zone 1 - high-power trunk
Zone 1/2 - intrinsically safe high-power trunk
Zone 1 - intrinsically safe trunk, Device coupler location [2]: Zone 2 - high-power trunkpa

Ethernet-APL enables continuous communication across all hierarchy levels. Learn more about the pioneering technology …

RSS Info Service for PANOS Updates

Stay informed when a new software update of PANOS, the operating system for Ethernet-APL switches, is released: With our RSS Feed you will get an email notfication in your inbox immediately after an update has been released.

From decisions to planning, installation, and commissioning up to operation and maintenance: Discover how to make the most out of your fieldbus infrastructure …