Línea de servicio de Sensores Industriales
Atención al cliente para protección contra explosiones

Ex pxb and Ex pyb purge and pressurization system 6500-01-*-PNO-LNO

6500-01-*-PNO-LNO
  • Automatic purge and pressurization system for most applications
  • User-friendly, easy programming
  • LCD screen for operation status and LEDs for quick visual system identification
  • HART communication via RS-485 with PACTware and device app via Bluetooth
  • Maximum enclosure size 12.75 cubic meters
  • Compact design with panel mounts or direct mounts available
  • Universal power 20 to 30 VDC / 100 to 250 VAC. 50 to 60 HZ
  • Pressure, temperature, dilution control and monitoring
  • Up to SIL 2 acc. to IEC/EN 61508

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Descargue la hoja de datos completa en PDF:


Extracto de la hoja de datos: Información técnica del  6500-01-*-PNO-LNO

Descripción del producto
6500 series Ex pxb and Ex pyb purge and pressurization system
General specifications
Operating modeuser programmable
Series6500
System
Number of volume exchanges5 to 19
Hazardous environmentgas, dust, gas and dust
Functional safety related parameters
Safety Integrity Level (SIL)SIL 2
Supply
Rated voltage100 ... 240 V AC, 48 ... 62 Hz / 0.2 A
20 ... 30 V DC
Electrical specifications
ConnectionEPCU: Terminal blocks and grounding screw
UIC: 4-pin conncector and cable (provided), for the 6500-01-PM02, cable length is 5 meters
Input type: intrinsically safe
Interface
Physical Bluetooth® 4.1
Transmitter frequency2.4 ... 2.4835 GHz
Transmitter radiated power-19 ... 7.5 dBm
Sensitivity-92.5 dBm at 0.1 % BER
Detection range100 m in air
AntennaPCB
Communication
Bluetoothdeclaration ID: D037849
Input
Input IVoltage free contact or namur proximity sensor
Input typeIntrinsically Safe, Ex ib
Input II(1) 2-wire, PT100 RTD
Input typeIntrinsically Safe, Ex ib
Output
Output IAUX
Output typeVoltage free contact outputs, SPDT configuration
Inrush current2 A
Contact loading2 A @ 240VAC, resistive, 2 A @ 24VDC
Output IIEnclosure
Output typeVoltage free contact outputs, 2 N.O. configuration
Inrush current8 A
Contact loading8A @ 240 V AC, resistive up to 60 °C
8A @ 24 V DC up to 60 °C
5A @ 240 V AC, resistive, 60 to 70 °C
5A @ 24 V DC up to 60 to 70 °C
FuseExternal fusing is required at no more than 11 amps/1500 A breaking current
Output IIIDigital valve
When used with the 6500-MAN-DV-01, intrinsically safe
Internal resistance 280 Ω
Output IVProportional valve
When used with the 6500-MAN-PV-01, intrinsically safe
Current: 4 to 20 mA
Max. load: 300 Ω
CommunicationHART via RS485 (PACTware available)
Indicators/settings
Display elements2x20 LCD for configuration, monitoring, and status of the 65000 system with back light and contrast selection. Capacitive touch buttons
LED indicationSafe pressure: Blue - safe pressure is achieved
Enclosure power: Green - power on; Red - power off
Rapid exchange: Blue - purging is running
System bypass: Yellow - bypass is activated
Alarm fault: Red (blinking) - any alarm input detected; Red (solid) - 6000 series system fault
Key: green - a button on the capacitive touch display has been activated. Momentary indication
Pneumatic parameters
Protective gas supplyinstrument grade air or inert gas
Pressure requirementFor 6500-MAN-DV: 1.4 to 8.3 bar (20 to 120 psig) regulated
For 6500-MAN-PV: 3.5 to 6.9 bar (50 to 100 psig) regulated
Note: max. pressure will depend on the vent model used.
Safe pressureGas: 0.82 mbar (0.33 in wc)
Dust: 0.82 mbar (0.33 in wc)
Gas+Dust: 0.82 mbar (0.33 in wc)
Valve flowsStandard vent series: EPV-6500-*-01, 03, 05
Readout on display is from 56 to 850 l/min (2 to 30 scfm) in increments of 28l/min (1 scfm).
Minimum and maximum reading depending on type of vent and supply pressure.
See datasheet for EPV-6500 series vent.
Continuous (Dilution) vent series: EPV-6500-*-07, 08
Readout on display is from 17 to 226 l/min (0.6 to 8 scfm) continuous reading.
Maximum reading depending on type of vent and supply pressure.
See datasheet for EPV-6500 series vent.
Ambient conditions
Ambient temperature-20 ... 70 °C (-4 ... 158 °F)
Storage temperature-40 ... 70 °C (-40 ... 158 °F)
Relative humidity5 ... 85 %, non-condensing
Vibration resistance5 ... 100 Hz , 1 g, 12 m/s2, all axes
Impact resistance30 g, 11 ms, all axes
Mechanical specifications
Connection typeSee mounting in 6500 manual and cable gland requirements
Cable glandCable gland requirement: cable glands are not included. Customer can supply their own approved glands or use one of the 6500-CBLG-... cable gland kits.
I.S.cable glands: requires (5) M12 approved cable glands
Power cable glands: requires (2) M16 and (2) M12 approved cable glands
Degree of protectionIP66
MaterialUIC display: Makrolon FI cover and A380 Aluminum anodized casing
Housing: 316L stainless steel
Hardware: 316L stainless steel
Massapprox. 5 kg (11.0 lbs)
Dimensions6500-01-EXT1: 150 x 150 x 145 mm (5.9" x 5.9" x 5.7")
6500-01-PM01: 150 x 150 x 185 mm (5.9" x 5.9" x 7.3")
6500-01-PM02: EPCU: 150 x 150 x 145 mm (5.9" x 5.9" x 5.7"), UIC: 150 x 150 x 45 mm (5.9" x 5.9" x 1.8")
Height367.5 mm
Width183 mm
Depth152.5 mm
Data for application in connection with hazardous areas
CertificateDEMKO 16 ATEX 1640X
Directive conformity
Directive 2014/34/EUEN IEC 60079-0:2018 , EN 60079-2:2014 , EN 60079-5:2015 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012 , EN 60079-31:2014
International approvals
IECEx approvalIECEx UL 16.0003X
General information
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027180508
ECLASS 12.027180508
ECLASS 11.027180508
ECLASS 10.0.127180508
ECLASS 9.027180508
ECLASS 8.027180508
ECLASS 5.140050501
ETIM 9.0EC000243
ETIM 8.0EC000243
ETIM 7.0EC000243
ETIM 6.0EC000243
ETIM 5.0EC000243
UNSPSC 12.139121301

Details: 6500-01-*-PNO-LNO

Informative Literature: 6500-01-*-PNO-LNO

Seleccionar idioma:
LiteratureIdiomaTipo de archivoTamaño
Application Report - Hydrogen Analysis with Reliable Explosion ProtectionENGPDF253 KB
Application Report - Label Printer Solution for Zone 1/21 and Zone 2/22 ApplicationsENGPDF135 KB
Application Report - Purge and Pressurization Solutions on FPSO TankersENGPDF351 KB

Product Documentation: 6500-01-*-PNO-LNO

Seleccionar idioma:
Product informationIdiomaTipo de archivoTamaño
Basic Explosion Protection Compendium - Type of Protection "Purge and Pressurization"ENGPDF3860 KB
Brief Instructions
Purge & Pressurization Smart App - Users Guide / Purge & Pressurization Smart App - Users GuideALLPDF1771 KB
Safety and Security Documentation
Manual de instruccionesSPAPDF164 KB
ManualENGPDF1625 KB
Manuals
ManualENGPDF8336 KB

Design / Simulation: 6500-01-*-PNO-LNO

Seleccionar idioma:
CADIdiomaTipo de archivoTamaño
2D / DXF Files for 6500 Series - external mount / CAD 2-DALLZIP258 KB
CAD 2-D / CAD 2-DALLZIP1308 KB
3D files for 6500 Series / 3-D-Modell für Serie 6500ALLSTP25244 KB

Approvals: 6500-01-*-PNO-LNO

Seleccionar idioma:
CertificatesNúmero de CertificadoIdiomaTipo de archivoTamaño
ATEX CertificateDEMKO 16 ATEX 1640XALLPDF488 KB
Bluetooth SIG Radio ApprovalD037849ALLLINK---
China SITIIAS CCC Ex Certificate2020322304002485 (Katy, TX USA)ALLPDF1673 KB
IECEx Certificate of ConformityIECEx UL 16.0003XALLLINK---
Korea KOSHA16-AV4BO-0186XALLPDF1013 KB
UK-Type Examination CertificateUL21UKEX2017XALLPDF267 KB
Worldwide exida Functional Safety CertificateP+F 1601040 P0006 C016 V1R1ALLPDF124 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-B080CALLPDF160 KB
UK Declaration of Conformity (P+F) / UK-Konformitäterklärung (P+F)DOC-B0F7ALLPDF156 KB

Software: 6500-01-*-PNO-LNO

Seleccionar idioma:
Device Description Files/DriversLiberar InfoTipo de archivoTamaño
DTM for 6500 Series / DTM_aZIP21548 KB

Productos asociados: 6500-01-*-PNO-LNO

Accessories
pa
Functional Safety Hub de Pepperl+Fuchs

Varios cientos de productos con evaluación de SIL/PL, herramientas gratuitas y folletos en un mismo lugar: el "Functional Safety Hub" es su punto de partida para la implementación de funciones de seguridad.

K-System by Pepperl+Fuchs: Globally certified protection for people, plants, and the environment!

The largest portfolio of its kind: K-System components and systems are established in process industries around the world. Learn more!