NJ2,5-14GM-N-V1-Y21146 Inductive Sensor

Belangrijkste voordelen in één oogopslag

  • Usable up to SIL 2 acc. to IEC 61508
  • 2.5 mm flush
  • NAMUR output

NAMUR-sensoren moeten worden gebruikt in combinatie met apparaten met goedkeuring voor schakelaarversterkers. Hieronder vindt u geschikte apparaten:

Schakelaarversterkers bekijken
Product Compliance: Europe – CE
Approval symbol
Approval symbol
Product Compliance: USA - cULus
Product Compliance: China – CCC
Opmerking

Alle productgerelateerde documenten, zoals certificaten, conformiteitsverklaringen, enzovoort, die vóór de omzetting onder de naam Pepperl+Fuchs GmbH of Pepperl+Fuchs AG zijn afgegeven, zijn ook van toepassing op Pepperl+Fuchs SE.

EN
  • EN
  • CS
  • DE
  • ES
  • FR
  • IT
  • PL
  • PT
  • SV

Technische gegevens van NJ2,5-14GM-N-V1-Y21146

Switching functionNormally closed (NC)
Output typeNAMUR
Rated operating distancesn2.5 mm
Installationflush
Assured operating distancesa0 ... 2.02 mm
Reduction factor rAl 0.4
Reduction factor rCu 0.3
Reduction factor r304 0.85
Output type2-wire
Nominal voltageUo8.2 V (Ri approx. 1 kΩ)
Switching frequencyf0 ... 1500 Hz
Current consumption
Measuring plate not detectedmin. 3 mA
Measuring plate detected≤ 1 mA
Safety Integrity Level (SIL)SIL 2
MTTFd5887 a
Mission Time (TM)20 a
Diagnostic Coverage (DC)0 %
Standard conformity
NAMUREN 60947-5-6:2000
IEC 60947-5-6:1999
StandardsEN IEC 60947-5-2
IECEx approval
Equipment protection level GbIECEx PTB 11.0037X
Equipment protection level DaIECEx PTB 11.0037X
Equipment protection level MbIECEx PTB 11.0037X
ATEX approval
Equipment protection level GbPTB 00 ATEX 2048 X
Equipment protection level DaPTB 00 ATEX 2048 X
UL approvalcULus Listed
Load Type: General Purpose
Circuitry: Class 2 Power Source
Enclosure Type Rating: Type 1
Supply/Switching Voltage: 8.2 V DC
CCC approval
Hazardous Location2020322315002258
CML approvalon request
ANZEx18.3018X
Ambient temperature0 ... 90 °C (32 ... 194 °F)
Connection typeConnector plug
Housing materialStainless steel 1.4305 / AISI 303
Sensing facePBT
Degree of protectionIP67
Connector
ThreadingM12 x 1
Number of pins4
Dimensions
Length40 mm
Diameter14 mm
Use in the hazardous areasee instruction manuals
Algemene opmerkingen