KFD2-UT2-2 Temperature Converter
Universal temperature measuring signal converter
Belangrijkste voordelen in één oogopslag
- 2-channel signal conditioner
- 24 V DC supply (Power Rail)
- Thermocouple, RTD, potentiometer or voltage input
- Usable as signal splitter (1 input and 2 outputs)
- Current output 0/4 mA ... 20 mA
- Sink or source mode
- Configurable by PACTware
- Line fault (LFD) and sensor burnout detection
- Up to SIL 2 acc. to IEC/EN 61508 / IEC/EN 61511
Meer weergeven






Opmerking
Alle productgerelateerde documenten, zoals certificaten, conformiteitsverklaringen, enzovoort, die vóór de omzetting onder de naam Pepperl+Fuchs GmbH of Pepperl+Fuchs AG zijn afgegeven, zijn ook van toepassing op Pepperl+Fuchs SE.
EN
- EN
- DE
- ES
- FR
- PL
Technische gegevens van KFD2-UT2-2
| Signal type | Analog input |
| Safety Integrity Level (SIL) | SIL 2 |
| Connection | terminals 14+, 15- or power feed module/Power Rail | |
| Rated voltage | Ur | 20 ... 30 V DC |
| Ripple | within the supply tolerance | |
| Power dissipation | ≤ 1.53 W | |
| Power consumption | max. 1.53 W |
| Programming interface | programming socket |
| Connection side | field side | |||||||||||||
| Connection | terminals 1, 2, 3; 4, 5, 6 | |||||||||||||
| RTD | type Pt10, Pt50, Pt100, Pt500, Pt1000 (EN 60751: 1995) type Pt10GOST, Pt50GOST, Pt100GOST, Pt500GOST, Pt1000GOST (6651-94) type Cu10, Cu50, Cu100 (P50353-92) type Ni100 (DIN 43760) | |||||||||||||
| ||||||||||||||
| Thermocouples | type B, E, J, K, N, R, S, T (IEC 584-1: 1995) type L (DIN 43710: 1985) type TXK, TXKH, TXA (P8.585-2001) | |||||||||||||
| ||||||||||||||
| Potentiometer | 0 ... 20 kΩ (2-wire connection), 0.8 ... 20 kΩ (3-wire connection) | |||||||||||||
| Voltage | selectable within the range -100 ... 100 mV | |||||||||||||
| Input resistance | ≥ 1 MΩ (-100 ... 100 mV) | |||||||||||||
| Connection side | control side | |||||||||||||
| Connection | output I: terminal 7: source (-), sink (+), terminal 8: source (+), terminal 9: sink(-) output II: terminal 10: source (-), sink (+), terminal 11: source (+), terminal 12: sink(-) | |||||||||||||
| Output I, II | Analog current output | |||||||||||||
| ||||||||||||||
| Deviation | ||||||||||||||
| ||||||||||||||
| Reaction time | worst case value (sensor breakage and/or sensor short circuit detection enabled) mV: 1.2 s, thermocouples with CJC: 1.4 s, thermocouples with fixed ref. temp: 1.4 s, 3- or 4-wire RTD: 1.1 s, 2-wire RTD: 920 ms, Potentiometer: 3-wire connection 2.8 s, 2-wire connection 2.25 s | |||||||||||||
| Input/Other circuits | basic insulation according to IEC 61010-1, rated insulation voltage 300 Veff | |
| Output/supply, programming input | functional insulation, rated insulation voltage 50 V AC There is no electrical isolation between the programming input and the supply. The programming cable provides galvanic isolation so that ground loops are avoided. |
| Display elements | LEDs | |
| Configuration | via PACTware | |
| Labeling | space for labeling at the front |
| Electromagnetic compatibility | |||||
| |||||
| Electromagnetic compatibility | NE 21:2006 | |
| Degree of protection | IEC 60529:2001 |
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
| Degree of protection | IP20 | ||||||||||
| Connection | screw terminals | ||||||||||
| Mass | approx. 130 g | ||||||||||
| Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2 | ||||||||||
| |||||||||||
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | ||||||||||
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |