General specifications |
AS-Interface specification | V3.0 |
PLC-Functionality | activateable |
Duplicate address detection | from AS-Interface slaves |
Earth fault detection | integrated |
EMC monitoring | integrated |
Diagnostics function | Extended function via display |
Data decoupling | integrated |
UL File Number | E223772 only from low voltage, limited energy source (SELV or PELV) or listed Class 2 source |
Functional safety related parameters |
MTTFd | 105 a at 30 °C |
Indicators/operating means |
Display | Illuminated graphical LC display for addressing and error messages |
LED PROFIBUS | PROFIBUS communication active; LED green |
LED AS-i ACTIVE | AS-Interface operation normal; LED green |
LED CONFIG ERR | configuration error; LED red |
LED PRG ENABLE | autom. programming; LED green |
LED POWER | voltage ON; LED green |
LED PRJ MODE | projecting mode active; LED yellow |
LED U AS-i | AS-Interface voltage; LED green |
Switch SET | Selection and setting of a slave address |
OK button | Mode selection traditional-graphical/confirmation |
Button MODE | Mode selection PRJ-operation/save configuration/cursor |
ESC button | Mode selection traditional-graphical/cancel |
Electrical specifications |
Insulation voltage | ≥ 500 V |
Rated operating voltage | 24 V DC ( 20 ... 31.6 V ) safe isolated power supplies (PELV) Note 24 V power supply, max. segment length: 50 m Supply via AS-Interface power supply, max. segment length: 100 m |
Rated operating current | approx. 250 mA |
Power supply | max. 4 A per AS-Interface circuit |
Interface 1 |
Interface type | RS-485 |
Protocol | PROFIBUS DP V1 |
Transfer rate | 9.6 kBit/s / 12 MBit/s , Automatic baud rate detection |
Interface 2 |
Interface type | Chip card slot |
Connection |
PROFIBUS | Sub-D interface |
AS-Interface | spring terminals, removable |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007 |
Standard conformity |
Electromagnetic compatibility | EN 61326:2003 |
Degree of protection | EN 60529:2000 |
AS-Interface | EN 62026-2:2013 |
Shock resistance | EN 61131-2:2004 |
Approvals and certificates |
UL approval | An isolated source with a secondary open circuit voltage of ≤ 30 VDC with a 3 A maximum over current protection. Over current protection is not required when a Class 2 source is employed. UL mark does not provide UL certification for any functional safety rating or aspects of the device. |
Ambient conditions |
Ambient temperature | 0 ... 55 °C (32 ... 131 °F) |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
Mechanical specifications |
Degree of protection | IP20 |
Mass | 500 g |
Dimensions | |
| Height | 120 mm |
| Width | 75 mm |
| Length | 83 mm |
Construction type | Low profile housing , Stainless steel |