Línea de servicio de Sensores Industriales
Atención al cliente para protección contra explosiones
No disponible para compra
No disponible para compra

AS-Interface Safety Monitor VAS-1A1L-K12-S1

VAS-1A1L-K12-S1
  • Two release circuits
  • Supports a secure, decentralized output circuit
  • Fulfills technical safety requirements for Category 4 according to EN 954-1, EN 61508, SIL 3 and Performance Level e (PLe)
  • Logic configuration by means of drag & drop with diagrammatical display on the PC
  • Max. switch-off time 50 ms

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Extracto de la hoja de datos: Información técnica del  VAS-1A1L-K12-S1

Descripción del producto
Safety Monitor, 1 decentralized output circuit
General specifications
AS-Interface specificationV3.0
Switch-on delay< 10 s
Indicators/operating means
LED AS-i 1from: no power supply
green, continuous illuminated: AS-Interface power supply available
LED AS-i 2from: normal operation
red, continuous illuminated: communication error
LED greenOff: contacts of the safety output (OSSD) open
constantly lit: contacts of the safety output (OSSD) closed
flashing: delay time running for Stop Category 1
LED yellowoff: -
constantly lit: startup/restart lock active
flashing: external test required
LED redOff: contacts of the safety output (OSSD) closed
constantly lit: contacts of the safety output (OSSD) open
flashing: error
Electrical specifications
Rated operating voltage24 V DC ± 15 %
Residual ripple ≤ 15 %
18.5 ... 31.6 V from AS-Interface
Rated operating current≤ 200 mA
≤ 45 mA from AS-Interface
Surge protectionovervoltage category III
for rated operating voltage 300 V DC acc. to VDE 0110 Part 1
Interface
Interface typeRS 232, serial
Transfer rate9600 baud, no parity, 1 start bit, 1 stop bit, 8 data bits
Input
Number/Type2 opto-coupling inputs (high-active) "Start" and "protection control (EDM)", input currents about 10 mA at 24 V DC
Output
Safety output2 potential-free NO contacts,
max. contact loading:
1 A DC-13 at 24 V DC,
3 A AC-15 at 230 V AC
Output typeSignal output:
PNP transistor output, 200 mA, short-circuit and reverse-polarity-proof
Response delay< 50 ms
Compliance with standards and directives
Directive conformity
Machinery Directive 2006/42/ECEN 954-1:1996, EN 61496:2005, EN 60204-1:2006
Low Voltage Directive 2006/95/ECEN 60947-5-1:2005
EMC Directive 2004/108/ECEN 61000-6-2:2006, EN 61000-6-4:2007
Standard conformity
AS-InterfaceEN 50295:1999
Functional safetyISO 13849-1:2008 (up to category 4/PL e), IEC 61508:2000/IEC 62061:2005 (up to SIL3)
Electrical safetyEN 50178:1998
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Storage temperature-30 ... 70 °C (-22 ... 158 °F)
Mechanical specifications
Degree of protectionIP20 (only for use in electrical operating rooms / switch cabinet suitable with minimum protection type IP54)
Connectionscrew terminals
Material
HousingPolyamide PA 66 , black
Mass450 g
MountingDIN rail mounting

Classifications

SystemClasscode
ECLASS 13.027243101
ECLASS 12.027243101
ECLASS 11.027243101
ECLASS 10.0.127243101
ECLASS 9.027243101
ECLASS 8.027279215
ECLASS 5.127279215
ETIM 9.0EC001449
ETIM 8.0EC001449
ETIM 7.0EC001449
ETIM 6.0EC001449
ETIM 5.0EC001449
UNSPSC 12.139121535

Details: VAS-1A1L-K12-S1

Datasheet: VAS-1A1L-K12-S1

DatasheetTipo de archivoTamaño
Datasheet VAS-1A1L-K12-S1PDF326 KB
Fiche de données VAS-1A1L-K12-S1PDF334 KB
Datenblatt VAS-1A1L-K12-S1PDF330 KB

Documents: VAS-1A1L-K12-S1

ManualsTipo de archivoTamaño
Manual VAS-*A*-K12*PDF1417 KB
Manual VAZ-SW-SIMONPDF2180 KB
Manual VAS-*A*-K12*PDF1431 KB
Manuel VAZ-SW-SIMONPDF2263 KB
Handbuch VAS-*A*-K12*PDF1673 KB
Handbuch VAZ-SW-SIMONPDF2328 KB
Manual VAS-*A*-K12*PDF1430 KB
Manuale VAZ-SW-SIMONPDF2250 KB
Manual VAS-*A*-K12* / Handbuch VAS-*A*-K12*PDF1593 KB
Manual VAZ-SW-SIMON / Handbuch VAZ-SW-SIMONPDF2373 KB
Manual VAS-*A*-K12*PDF1429 KB
Manual VAZ-SW-SIMONPDF2274 KB
Manual VAS-*A*-K12*PDF1416 KB
Manual VAZ-SW-SIMONPDF2190 KB
Technical information
Configuring a Safe Input on AS-Interface Safety at WorkPDF258 KB

Software: VAS-1A1L-K12-S1

Software ToolsTipo de archivoTamaño
SISTEMA SLB Library AS-Interface Safety / SISTEMA SLB Library AS-Interface SafetyZIP622 KB

Productos asociados: VAS-1A1L-K12-S1

Accessories
Interface cable for connecting the K12 Safety Monitor to a PCfa
Interface cable for connecting two K12-Safety Monitorsfa
Interface converter USB/RS 232fa