General specifications |
Node type | Safety-Slave |
AS-Interface specification | V2.1 |
Required gateway specification | ≥ V2.0 |
UL File Number | E87056 |
Indicators/operating means |
LED FAULT | error display; LED red red: communication error or address is 0 |
LED PWR | AS-Interface voltage; LED green |
LED IN | switching state (input); 2 LED yellow |
Electrical specifications |
Rated operating voltage | 26.5 ... 31.6 V from AS-Interface |
Rated operating current | ≤ 70 mA |
Protection class | III |
Fault current | max. 90 mA |
Input |
Number/Type | 2 Inputs for SN sensors (category S, EN 60947-5-3; category 3+4, EN 954-1) or for mechanical contacts (category 4, EN 954-1) Inputs for mech. switch, monitored for cross-circuit, cable length < 30 m |
Supply | from AS-Interface |
Current loading capacity | input current limited ≤ 15 mA, overload and short-circuit resistant |
Switching point | SN specification mech. switch current 10 mA pulsed |
Compliance with standards and directives |
Directive conformity | |
| EMC Directive 2004/108/EC | EN 61000-6-2:2005, EN 61000-6-4:2007, EN 50295:1999 The device has been used for the same applications for several years. It therefore features an appropriate electromagnetic field immunity. The device must not be used in new plants. |
Standard conformity | |
| Electromagnetic compatibility | EN 61000-6-2:2005, EN 61000-4-x, EN 61000-4-5:2005 1kV asymmetric, criterion B, EN 61000-6-4:2007, EN 55011:2009 |
| Emitted interference | EN 61000-6-4:2001 |
| Insulation coordination | EN 50178:1998 |
| Functional safety | DIN EN 954-1:1996 (by category 4) , IEC 60947-5-3:1999 |
| Degree of protection | EN 60529:2000 |
| Fieldbus standard | EN 50295:1999, IEC 62026-2:2006 |
| Electrical safety | IEC 60204-1:2007 |
Programming instructions |
Profile | S-0.B |
IO code | 0 |
ID code | B |
ID1 code | F |
ID2 code | E |
Data bits (function via AS-Interface) | InputOutput |
| D0 | dyn. safety code 1 - |
| D1 | dyn. safety code 1 - |
| D2 | dyn. safety code 2 - |
| D3 | dyn. safety code 2 - |
Parameter bits (programmable via AS-i) | function |
| P0 | not used |
| P1 | not used |
| P2 | not used |
| P3 | not used |
Ambient conditions |
Ambient temperature | -25 ... 55 °C (-13 ... 131 °F) |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
Relative humidity | < 95 % |
Shock and impact resistance | 10 g, 16 ms in 6 spatial directions 1000 shocks |
Vibration resistance | 0.75 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles |
Mechanical specifications |
Degree of protection | IP67 |
Connection | cable piercing method or terminal compartment yellow flat cable or standard round cable inputs: M12 x 1.5 cable gland and cage tension spring terminals |
Material | |
| Housing | PA 6 GF30 |
Mass | 180 g |
Dimensions | |
| Height | 51 mm |
| Width | 45 mm |
| Length | 102 mm |
Mounting | DIN rail or screw mounting |