Selecione seu país
KFU8-UFC-Ex1.D Frequency Converter
Frequency converter with limit values
Principais benefícios
- 1-channel isolated barrier
- Universal usage at different power supplies
- Input for NAMUR sensors or dry contacts
- Input frequency 1 mHz ... 5 kHz
- Current output 0/4 mA ... 20 mA
- Relay contact and transistor output
- Start-up override
- Line fault detection (LFD)
- Up to SIL 2 acc. to IEC/EN 61508 / IEC/EN 61511
Mostrar mais






Nota
Todos os documentos relacionados ao produto, como certificados, declarações de conformidade etc., que foram emitidos antes da conversão sob o nome Pepperl+Fuchs GmbH ou Pepperl+Fuchs AG, também se aplicam à Pepperl+Fuchs SE.
EN
- EN
- DE
- ES
- FR
- PL
Dados técnicos de KFU8-UFC-Ex1.D
| Signal type | Digital Input |
| Safety Integrity Level (SIL) | SIL 2 |
| Connection | terminals 23, 24 | |
| Rated voltage | Ur | 20 ... 90 V DC / 48 ... 253 V AC 50 ... 60 Hz |
| Power dissipation/power consumption | ≤ 2 W ; 2.5 VA / 2.2 W ; 3 VA |
| Programming interface | programming socket |
| Connection side | field side | ||||||||||
| Connection | Input I: intrinsically safe: terminals 1+, 3- Input II: non-intrinsically safe: terminals 13+, 14- | ||||||||||
| Input I | sensor acc. to EN 60947-5-6 (NAMUR) or mechanical contact | ||||||||||
| |||||||||||
| Input II | startup override: 1 ... 1000 s, adjustable in steps of 1 s | ||||||||||
| |||||||||||
| Connection side | control side | |||||||||||||
| Connection | output I: terminals 10, 11, 12 output II: terminals 16, 17, 18 outout III: terminasl 19+, 20- output IV: terminals 8+, 7- | |||||||||||||
| Output I, II | signal, relay | |||||||||||||
| ||||||||||||||
| Output III | electronic output, passive | |||||||||||||
| ||||||||||||||
| Output IV | analog | |||||||||||||
| ||||||||||||||
| Input I | |||||||||||||||||
| |||||||||||||||||
| Output I, II | |||||||||||||||||
| |||||||||||||||||
| Output IV | |||||||||||||||||
| |||||||||||||||||
| Input I/other circuits | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
| Output I, II/other circuits | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
| Mutual output I, II, III | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
| Output III/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
| Output III/start-up override | basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff | |
| Output III/IV | basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff | |
| Output IV/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
| Start-up override/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
| Interface/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
| Interface/output III | basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff |
| Display elements | LEDs , display | |
| Control elements | Control panel | |
| Configuration | via operating buttons via PACTware | |
| Labeling | space for labeling at the front |
| Electromagnetic compatibility | |||||
| |||||
| Low voltage | |||||
| |||||
| Electromagnetic compatibility | NE 21:2006 | |
| Degree of protection | IEC 60529:2001 | |
| Input | EN 60947-5-6:2000 |
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Mass | 300 g | |
| Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) (W x H x D) , housing type C2 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
| EU-type examination certificate | TÜV 99 ATEX 1471 | ||||||||||
| |||||||||||
| Supply | |||||||||||
| |||||||||||
| Input I | terminals 1+, 3-: Ex ia | ||||||||||
| |||||||||||
| Input II | terminals 13+, 14- non-intrinsically safe | ||||||||||
| |||||||||||
| Output I, II | terminals 10, 11, 12; 16, 17, 18 non-intrinsically safe | ||||||||||
| |||||||||||
| Output III | terminals 19+, 20- non-intrinsically safe | ||||||||||
| |||||||||||
| Output IV | terminals 8+, 7- non-intrinsically safe | ||||||||||
| |||||||||||
| Interface | RS 232 | ||||||||||
| |||||||||||
| Galvanic isolation | |||||||||||
| |||||||||||
| Directive conformity | |||||||||||
| |||||||||||
| FM approval | ||||||||
| ||||||||
| IECEx approval | ||||||||
| ||||||||
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |