ファクトリーオートメーション(FA)
プロセスオートメーション(PA)
Not available for purchase
Not available for purchase

Digital Output with Position Feedback LB2102AR

LB2102AR
  • 1 digital output, 2 digital inputs
  • Inputs and output Ex ia
  • Mounting in Zone 2, Class I/Div.2 or in the safe area
  • Positive or negative logic selectable
  • Simulation mode for service operations (forcing)
  • Line fault detection (LFD)
  • Permanently self-monitoring
  • Output with watchdog
  • Module can be exchanged under voltage

注: Pepperl+Fuchs GmbH(旧社名)で発行された証明書・適合宣言書などすべての製品関連文書は、Pepperl+Fuchs AG(新社名)にそのまま適用されます。

技術データ  LB2102AR

Slots
Occupied slots1
Supply
Connectionbackplane bus
Rated voltage12 V DC , only in connection with the power supplies LB9***
Power dissipation1.8 W
Power consumption2.4 W
Internal bus
Connectionbackplane bus
Interfacemanufacturer-specific bus to standard com unit
Digital input
Number of channels2
Sensor interface
ConnectionNAMUR sensor
Connection [2]volt-free contact
Connectionchannel I: 2+, 5-; channel II: 3+, 6-
Rated valuesacc. to EN 60947-5-6 (NAMUR)
Switching point/switching hysteresis1.2 ... 2.1 mA / ± 0.2 mA
Voltage8.2 V
Internal resistor1 kΩ
Line fault detectioncan be switched on/off for each channel via configuration tool
Connectionmechanical switch with additional resistors (see connection diagram) proximity sensors without additional wiring
Short-circuit< 360 Ω
Open-circuit< 0.35 mA
Minimum pulse duration1 ms
Digital output
Number of channels1
Suitable field devices
Field deviceSolenoid Valve
Field device [2]audible alarm
Field device [3]visual alarm
Connectionchannel I: 1+, 4-
Internal resistor210 Ω
Current limit66 mA
Open loop voltage24 V
Line fault detectioncan be switched on/off for each channel via configuration tool , also when turned off (every 2.5 s the valve is turned on for 2 ms)
Short-circuit< 200 Ω
Open-circuit> 1.2 kΩ
Response time20 ms (depending on bus cycle time)
Watchdogwithin 0.5 s the device goes in safe state, e.g. after loss of communication
Indicators/settings
LED indicationLED green: supply
LED red: line fault, per channel
LED yellow: signal (status), per channel
Codingoptional mechanical coding via front socket
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1
Conformity
Electromagnetic compatibilityNE 21
Degree of protectionIEC 60529
Environmental testEN 60068-2-14
Shock resistanceEN 60068-2-27
Vibration resistanceEN 60068-2-6
Damaging gasEN 60068-2-42
Relative humidityEN 60068-2-78
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Relative humidity95 % non-condensing
Altitudemax. 2000 m
Shock resistanceshock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Vibration resistancefrequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles
frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance
Damaging gasdesigned for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Degree of protectionIP20 when mounted on backplane
Connectionremovable front connector with screw flange (accessory)
wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2)
Massapprox. 110 g
Dimensions16 x 100 x 102 mm (0.63 x 3.9 x 4 inch)
Data for application in connection with hazardous areas
EU-type examination certificatePTB 03 ATEX 2042 X
MarkingEx-Hexagon II (1)G [Ex ia Ga] IIB
Ex-Hexagon II (1)D [Ex ia Da] IIIC
Ex-Hexagon I (M1) [Ex ia Ma] I
Input
Voltage14.1 V
Current16 mA
Power55 mW (linear characteristic)
Internal capacitance1.65 nF
Internal inductance0 mH
Output
Voltage27.83 V
Current183 mA
Power1270 mW
Internal capacitance1.65 nF
Internal inductance0 mH
CertificatePF 08 CERT 1234 X
MarkingEx-Hexagon II 3 G Ex nA IIB T4 Gc
Galvanic isolation
Input/power supply, internal bussafe electrical isolation acc. to EN 60079-11, voltage peak value 375 V
Output/power supply, internal bussafe electrical isolation acc. to EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN IEC 60079-0:2018+AC:2020
EN 60079-11:2012
EN 60079-15:2010
International approvals
ATEX approvalPF 08 CERT 1234 X
PTB 03 ATEX 2042 X
UL approvalE106378
Control drawing116-0321A
IECEx approval
IECEx certificateIECEx BVS 09.0037X
IECEx markingEx nA [ia Ga] IIB T4 Gc
[Ex ia Da] IIIC
General information
System informationThe module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity.
For use in hazardous areas (e. g. Zone 2, Zone 22 or Div. 2) the module must be installed in an appropriate enclosure.
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210101
ECLASS 12.027210101
ECLASS 11.027210101
ECLASS 10.0.127210101
ECLASS 9.027210101
ECLASS 8.027210101
ECLASS 5.127210120
ETIM 9.0EC001485
ETIM 8.0EC001485
ETIM 7.0EC001485
ETIM 6.0EC001485
ETIM 5.0EC001485
UNSPSC 12.139121008

Details: LB2102AR

Datasheet: LB2102AR

Datasheetファイルタイプファイルサイズ
Datasheet LB2102ARPDF796 KB
Datenblatt LB2102ARPDF795 KB

Documents: LB2102AR

Manualsファイルタイプファイルサイズ
ManualPDF5367 KB
HandbuchPDF5387 KB
Instruction manuals
ИнструкцииPDF177 KB
Instruction manual / BetriebsanleitungPDF345 KB
Návod k poużitíPDF172 KB
Instruktions manualPDF172 KB
Instruction manualPDF178 KB
KasutusjuhendPDF167 KB
KäyttöohjePDF166 KB
Manuel d'instructionsPDF176 KB
BetriebsanleitungPDF180 KB
Οδηγίες χρήσηςPDF183 KB
HandleidingPDF172 KB
Instruction manual / BetriebsanleitungPDF170 KB
Használati útmutatóPDF174 KB
Manuale di istruzioniPDF172 KB
Lietošanas pamācībaPDF171 KB
Instrukciju vadovasPDF172 KB
Instrukcja obsługiPDF175 KB
Manual de instruçõesPDF173 KB
Manual de utilizarePDF172 KB
Návod na poużitiePDF172 KB
Navodila za uporaboPDF170 KB
Manual de instruccionesPDF174 KB
ManualPDF170 KB
Application reports
Application Report - Communication Redundancy for Uninterrupted OperationPDF529 KB
Application Report - LB and FB Remote I/O Systems for Digitally Connecting Analog Field DevicesPDF208 KB
Application Report - Space Saving Extension for Existing PlantsPDF300 KB
Application Report - The Modern Whiskey DistilleryPDF176 KB
Application Report - Use of Remote I/O in Fluidized Bed SystemsPDF222 KB
Application Report - Using Remote I/O Systems for the Efficient Digitalization of PlantsPDF371 KB
Applikationsbericht - Die moderne Whiskey-BrennereiPDF130 KB
Applikationsbericht - Einsatz von Remote-I/O-Modulen in WirbelschichtanlagenPDF222 KB
Applikationsbericht - Platzsparende Erweiterung für bestehende AnlagenPDF300 KB
Applikationsbericht - Redundanz der Kommunikation für ungestörten BetriebPDF530 KB
Applikationsbericht - Remote-I/O-Systeme Typ LB und FB für digitale Anbindung analoger FeldgerätePDF208 KB
Applikationsbericht - Remote-I/O-Systeme für effiziente AnlagendigitalisierungPDF365 KB
Documents
Functional Safety ManualPDF2422 KB
Selection table - Solenoid driver/valve combinationsPDF299 KB
Auswahltabelle - Kombination Ventil - SteuerbausteinPDF300 KB
Handbuch funktionale SicherheitPDF2435 KB

CAD+CAE: LB2102AR

EPLANファイルタイプファイルサイズ
CAE EPLAN Data Portal / CAE EPLAN Data PortalLINK---
CAE EPLAN macro EDZ / CAE EPLAN Makro EDZEDZ1628 KB
PROFINET Gateway

The new LB/FB PROFINET gateways from Pepperl+Fuchs open the door for IIoT 4.0 applications in process industries.