Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Tam veri sayfasını PDF olarak indirin:
Supply | ||
---|---|---|
Rated voltage | 7 ... 32 V DC | |
Rated current | < 1 mA , max. 25 mA | |
Electrical specifications | ||
Output rated operating current | 3.2 ... 25 mA | |
Supply | loop power for field devices voltage: 1 ... 2.5 V DC, adjustable in steps of 0.5 V |
|
Input | ||
Connection | - 5 wires, 600 mm long, exiting from male thread NPT1/2 - 1 external grounding point |
|
HART communication | ||
Protocol | HART 7.1, backward compatible | |
Number of devices | up to 8 HART field devices (depending on installation) | |
Output | ||
Interface | internal antenna | |
Communication | WirelessHART specifications - physical layer: IEEE 802.15.4.2006 - frequency band: 2.4 GHz (ISM band, licence free) - maximum transmit power: +10 dBm - outdoor transmission range: 235 m - communication standard: WirelessHART acc. to IEC 62591 |
|
Directive conformity | ||
Radio and telecommunication terminal equipment | The usage of 2.4 GHz equipment is bound to local restrictions. Ensure that restrictions allow usage of this product before commisioning. | |
Directive 2014/53/EU | EN 300 328 V2.1.1:2016 EN 301 489-1 V2.2.0:2017 EN 301 489-17 V3.2.0:2017 |
|
FCC CFR47 Part 15 B and C | ANSI C63.4-2003 , FCC ID: X89-WA1101 | |
Conformity | ||
Degree of protection | IEC 60529:2013 | |
Ambient conditions | ||
Ambient temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Relative humidity | max. 100 % | |
Mechanical specifications | ||
Degree of protection | IP67 | |
Material | aluminum alloy with polyurethane enamel paint | |
Mass | 460 g | |
Dimensions | 60.8 x 60.8 x 100 mm (l x w x h) | |
International approvals | ||
FM approval | FM 17 NUS 0010 | |
Control drawing | 116-0425 (cFMus) | |
CSA approval | FM 17 NCA 0004 | |
Control drawing | 116-0425 (cFMus) | |
General information | ||
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
System | Classcode |
---|---|
ECLASS 11.0 | 27219290 |
ECLASS 10.0.1 | 27219290 |
ECLASS 9.0 | 27219290 |
ECLASS 8.0 | 27219290 |
ECLASS 5.1 | 27242692 |
ETIM 8.0 | EC002584 |
ETIM 7.0 | EC002584 |
ETIM 6.0 | EC002584 |
ETIM 5.0 | EC002584 |
UNSPSC 12.1 | 39121008 |
Statements of compliance | Sertifika No. | Dosya Tipi | Dosya Boyutu |
---|---|---|---|
EU-Declaration of Conformity / EU-Konformitätserklärung | DOC-3837B | 383 KB | |
Control drawings | |||
Control drawing CSA / Control drawing CSA | 187 KB |
Commissioning files | Dil | Dosya Tipi | Dosya Boyutu |
---|---|---|---|
FHX WirelessHART Adapter WHA-BLT* "Bullet" / FHX WirelessHART Adapter WHA-BLT* "Bullet" | ALL | ZIP | 1115 KB |
Drivers | Sürüm Bilgileri | Dosya Tipi | Dosya Boyutu |
---|---|---|---|
DD WirelessHART Adapter WHA-BLT* "Bullet" / DD WirelessHART Adapter WHA-BLT* "Bullet" | ZIP | 3513 KB | |
Device type managers | |||
DTM WirelessHART Adapter WHA-BLT* "Bullet" / DTM WirelessHART Adapter WHA-BLT* "Bullet" | ZIP | 16481 KB |
Accessories | ||||||
---|---|---|---|---|---|---|
|
||||||
|
The device upgrades a conventional HART or 4 ... 20 mA field device with a WirelessHART interface.
The supply is ensured via loop power. The adapter is suitable for use in a nonhazardous area and it can be used directly on the field device or it can be integrated in the 4 ... 20 mA loop. Up to 8 HART field devices can be connected to each other in multidrop mode.
The device can be programmed with a configuration tool easily (DTM or DD).