选择您所在的国家/地区
KCD2-SCD-Ex1 SMART Current Driver
主要优势一览
- 1-channel isolated barrier
- 24 V DC supply (Power Rail)
- Current output up to 650 Ω load
- HART-IP and valve positioner
- Lead breakage monitoring
- Housing width 12.5 mm
- Up to SIL 2 (SC 3) acc. to IEC/EN 61508
显示详情






注意
在转换前以倍加福有限公司或倍加福股份公司名义发布的所有产品文档(如证书、符合性声明等)也适用于倍加福欧洲公司。
EN
- EN
- DE
- ES
- FR
- PL
KCD2-SCD-Ex1 技术数据
| Signal type | Analog output |
| Safety Integrity Level (SIL) | SIL 2 | |
| Systematic capability (SC) | SC 3 |
| Connection | Power Rail or terminals 9+, 10- | |
| Rated voltage | Ur | 19 ... 30 V DC |
| Ripple | ≤ 10 % | |
| Rated current | Ir | ≤ 30 mA at 24 V |
| Power dissipation | ≤ 600 mW at 20 mA and 500 Ω load | |
| Power consumption | ≤ 700 mW |
| Connection side | control side | |
| Connection | terminals 5-, 6+ | |
| Input signal | 4 ... 20 mA , limited to approx. 26 mA | |
| Input voltage | open loop voltage of the control system < 30 V | |
| Voltage drop | approx. 6 V at 20 mA | |
| Input resistance | > 100 kΩ, with field wiring open |
| Connection side | field side | |
| Connection | terminals 1+, 2- | |
| Voltage | ≥ 13 V at 20 mA | |
| Current | 4 ... 20 mA | |
| Load | 0 ... 650 Ω | |
| Ripple | 20 mV rms |
| Deviation | at 20 °C (68 °F), 4 ... 20 mA < 0.1 % of full scale, incl. non-linearity and hysteresis | ||||
| |||||
| Frequency range | field side into the control side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB) control side into the field side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB) | ||||
| Rise time | 10 to 90 % ≤ 10 ms | ||||
| Input/Output | basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
| Input/power supply | basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
| Output/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
| Display elements | LED | |
| Labeling | space for labeling at the front |
| Electromagnetic compatibility | |||||
| |||||
| Electromagnetic compatibility | NE 21:2017 EN 61326-3-2:2018 | |
| Degree of protection | IEC 60529 | |
| Protection against electrical shock | UL 61010-1:2019 |
| Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) |
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Mass | approx. 100 g | |
| Dimensions | 12.5 x 124 x 114 mm (0.5 x 4.9 x 4.5 inch) (W x H x D) , housing type A2 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
| EU-type examination certificate | CESI 06 ATEX 021 X | ||||||||||||||||
| |||||||||||||||||
| Supply | |||||||||||||||||
| |||||||||||||||||
| Equipment | terminals 1+, 2- | ||||||||||||||||
| |||||||||||||||||
| Certificate | CESI 19 ATEX 021 X | ||||||||||||||||
| |||||||||||||||||
| Galvanic isolation | |||||||||||||||||
| |||||||||||||||||
| Directive conformity | |||||||||||||||||
| |||||||||||||||||
| FM approval | ||||||||
| ||||||||
| UL approval | E106378 | |||||||
| ||||||||
| IECEx approval | ||||||||
| ||||||||
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |