FB8210* Com Unit

Com unit for FOUNDATION Fieldbus modular I/O

主要优势一览

  • Interface between the I/O modules and the PCS/PLC
  • Com unit for 20 analog or 40 digital channels
  • Communication via FOUNDATION Fieldbus H1
  • HART communication via service bus
  • Configured via the process control system
  • Non-volatile memory for configuration and parameter settings
  • Quick communication set-up
  • Permanently self-monitoring
  • Outputs drive to safe state in case of failures
  • Supports multichannel I/O modules
  • Installation in suitable enclosures in Zone 1 or Zone 21
  • Module can be exchanged under voltage (hot swap)
  • Installation in suitable enclosures in Zone 1

显示详情

Product Compliance: Europe – CE
Approval symbol
注意

在转换前以倍加福有限公司或倍加福股份公司名义发布的所有产品文档(如证书、符合性声明等)也适用于倍加福欧洲公司。

EN
  • EN
  • DE

FB8210* 技术数据

Connectionbackplane bus
Rated voltageUr5 V DC , only in connection with the power supplies FB92**
Power consumption2 W
Auxiliary energy24 V DC
Trunk load 20 mA
Fieldbus typeFOUNDATION Fieldbus H1
FOUNDATION Fieldbus
Connectionwired to Ex e terminals via backplane
Baud rate31.25 kBit/s , MBP
ProtocolH1 to IEC 1158-2
Station connectiondirectly at the trunk or via spur protector
Number of stations per bus line
Number of channels per stationmax. 20 analog, max. 40 digital
Supported I/O modules5 slots, to be filled with (combinations possible):
1*08 digital input, 8-channel, NAMUR
3*05 analog input, 4-channel, 20 mA (HART via service bus)
4*05 analog output, 4-channel, 20 mA (HART via service bus)
5204 Pt100 RTD input, 4-channel
5205 thermocouple input, 4-channel
6305 relay output, 4-channel, 230 V
6306 relay output, 8-channel, 24 V
6*08 digital output, 8-channel, Ex i
6210-6215 digital output, 4-channel, Ex i power
* = variable (2=IS, 3=Ex e)
Bus lengthmax. 1900 m
(must not be exceeded by the sum of all trunk and spur lines)
Spur lengthmax. 120 m
(depending on the number of field devices. Modular I/O station = 1 field device)
Addressingvia PCS (software)
Connectionbackplane bus
LED indicationLED green (power supply): On = operating, fast flash = cold start
LED red (collective alarm): On = internal fault, flashing = no fieldbus
LED yellow (operating mode): flashing = active
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1
Electromagnetic compatibilityNE 21
Degree of protectionIEC 60529
Fieldbus standardIEC 61158-2
Environmental testEN 60068-2-14
Shock resistanceEN 60068-2-27
Vibration resistanceEN 60068-2-6
Damaging gasEN 60068-2-42
Relative humidityEN 60068-2-56
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Relative humidity95 % non-condensing
Shock resistanceshock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Vibration resistancefrequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles
frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance
Damaging gasdesigned for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Degree of protectionIP20 (module) , a separate housing is required acc. to the system description
Connectionvia backplane
Massapprox. 750 g
Dimensions
Height107 mm
Width57 mm
Depth132 mm
EU-type examination certificatePTB 97 ATEX 1074 U
MarkingEx-Hexagon II 2 G Ex d IIC Gb
Directive conformity
Directive 2014/34/EUEN 60079-0:2009
EN 60079-1:2007
EN 60079-11:2007
EN 60079-26:2007
EN 61241-11:2006
ATEX approvalPTB 97 ATEX 1075

EAC approvalRussia: RU C-IT.MIII06.B.00129
Marine approval
Lloyd Register15/20021
DNV GL MarineTAA0000034
American Bureau of ShippingT1450280/UN
Bureau Veritas Marine22449/B0 BV
System informationThe module has to be mounted in appropriate backplanes (FB92**) in Zone 1, 2, or outside hazardous areas. Observe the corresponding EC-type examination certificate.
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.